11
Shaded boxes indicate fl ooded conditions.
Rated design values. The suction pressure will vary from design value if indoor air fl ow, entering dry bulb,
or entering wet bulb temperatures are lower than design.
1. All pressures are listed in psig and all temperatures in ° F
2. Discharge temperatures greater than charted values indicate an undercharged system.
REFRIGERANT CHARGING TABLES
Table 7. Charging Table for JS5BD-030KB Series (2.5 Ton Units with Microchannel Coil)
Suct.
Press.
OUTDOOR TEMPERATURE (° F)
70
75
80
85
90
95
100
105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
68
139
94
70
142
100
158
108
72
144
105
160
113
176
120
74
142
118
162
118
178
125
194
133
76
145
121
161
127
180
130
196
137
212
144
78
165
130
180
137
198
142
214
149
230
156
80
184
140
199
147
216
153
232
160
248
167
82
203
151
218
158
234
164
250
171
266
178
84
206
154
222
161
237
168
252
175
268
182
86
225
165
241
173
256
180
270
186
88
244
177
260
184
275
191
90
263
188
279
196
92
282
200
94
Table 8. Charging Table for JS5BD-036KB Series (3 Ton Units with Microchannel Coil)
Suct.
Press.
OUTDOOR TEMPERATURE (° F)
70
75
80
85
90
95
100
105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
69
147
99
71
150
105
167
113
73
152
110
169
118
186
126
75
150
124
171
123
188
131
205
139
77
153
126
170
133
190
136
207
144
224
151
79
174
136
190
143
209
148
226
156
243
163
81
194
146
210
153
228
160
245
168
262
175
83
214
157
230
164
247
172
264
179
281
186
85
217
161
234
168
251
176
266
183
283
190
87
237
172
254
180
271
187
285
194
89
257
184
274
192
291
199
91
277
196
294
204
93
297
208
95