background image

5

4. REFRIGERANT LINE  

 

    CONNECTIONS

 

WARNING:

This coil is pressurized with Nitrogen.  
Avoid direct face exposure or contact 
with valve when gas is escaping. 
Always ensure adequate ventilation 
is present during the depressurization 
process.  Any uncertainties should be 

addressed before proceeding.

Line Connections:

1.   Remove the valve cap from the end of the 

liquid line.  Relieve all pressure from the coil 
by depressing the valve.

2.  Remove the valve core and valve core holder 

on the liquid line. DO NOT reuse the valve, 
threaded valve holder or O-ring.

3. It is recommended to wrap a wet rag around 

the suction line between the sensing bulb 
and the line set braze joint before applying 
any heat.

4.   Unbraze and remove the cap on the suction line.
5.  Properly dispose of all removed parts.
6.  When included, install condensation 

deflector and lock washer onto TXV. 
Condensation deflector is to be installed 
so that any condensation collecting on 
the TXV is directed away from the cabinet 
insulation and towards the drain pan. Fix 
TXV into position using nut. See Figure 3. 
Condensation deflector is not required if 
TXV is not installed directly on cabinet.

7.  Cut the line set tubing to the proper 

length. Be sure that the tubing has been 
sized in accordance with the outdoor unit 
specifications.

8.  Inspect both refrigerant lines. The ends 

of the lines must be round, clean, and free 
of any burrs.

9.  Insert the suction line set tube into the coil 

suction tube stub until it bottoms out.

10.  Slip the nut from the schrader valve holder 

onto the liquid line - check for correct 
orientation. Insert liquid line into liquid line 
stub until it bottoms out. Liquid line stub is 
shipped with the coil, but is not attached.

11.  It is recommended to wrap a wet rag around 

the suction line between the sensing bulb 
and the lineset braze joint before applying 
any heat.

12.  Braze the individual connections with dry 

nitrogen flowing through the joint to eliminate 
internal oxidation and scaling.

13.  Fasten nut to secure the liquid line to the 

bulkhead fitting. No O-Ring is required.

14.  Check the assembly for leaks.
15.  On horizontal applications of models with 

TXV valve, re-position the sensing bulb on 
the suction line so it is in the 4 o'clock or 8 
o'clock position on the suction tube.

5.  COMPLETING THE INSTALLATION

 CAUTION:

The indoor coil must be checked to 
ensure a level installation. Failure to do 
so may result in improper condensate 
disposal, causing structural damage, 
premature equipment failure, or 
possible personal injury.

Condensate Drain 

1.  The coil condensate pan is furnished with 

3/4" NPSC drain connections. Use a PVC 
or similar material fitting to attach the drain 
line to the pan. The fitting should be only 
hand tightened.

 

Overtightening may crack the drain pan 
and create a condensate leak.

2.  Connect the drain line and run to a suitable 

drain avoiding sharp bends and pinching of 
the line. Install a condensate trap and prime 
with water.

3.  During the system checkout, inspect the 

drain line and connections to verify proper 
condensate disposal.

4.  Perform any necessary adjustments to the 

coil components to ensure that all drip points 
fall within the outline of the drain pan.

Air Filter —

 Air filters are not provided as an 

integral part of this coil, however, a filter must 
be installed upstream of the coil and inspected 
frequently. When the filter becomes clogged with 
dust or lint, it should be replaced (disposable type) 
or cleaned (washable type). The filter should be 
inspected and replaced or cleaned at least twice 
during the year, generally at the start of each 
heating and cooling season.

 

Close-Off Plates and Panels —

 Install the 

necessary air close-off plates around the 

NITROGEN

HEALTH

FLAMMABILITY

REACTIVITY

0 Minimal Hazard

1 Slight Hazard

1

0

0

Summary of Contents for C6B-T

Page 1: ...nd or furnace air h a n d l e r m a r k i n g s before proceeding with installation of the coil These instructions are primarily intended to assist qualified individuals experienced in the proper inst...

Page 2: ...2...

Page 3: ...Furnace Air Handler 4 Downflow Horizontal 4 3 Pressure Verification 4 4 Refrigerant Line Connections 5 5 Completing the Installation 5 Condensate Drain 5 Air Filters 5 Close off Plates and Panels 5 Re...

Page 4: ...when an add on coil is installed Refer to Coil Specifications for recommended CFM and allow for pressure drop across the coil and filters 2 COIL INSTALLATION Upflow Furnace WARNING Electricfurnacesma...

Page 5: ...the sensing bulb and the lineset braze joint before applying any heat 12 Braze the individual connections with dry nitrogenflowingthroughthejointtoeliminate internal oxidation and scaling 13 Fasten nu...

Page 6: ...ical power to the furnace and outdoor condensing unit is off before performing any maintenance or service on the system To ensure optimum system performance and to minimize the possibility of equipmen...

Page 7: ...17 1 2 17 1 2 17 1 2 17 1 2 17 1 2 23 1 2 23 1 2 23 1 2 23 1 2 27 27 27 27 27 HS Height of Suction Line in 15 1 2 15 1 2 15 1 2 15 1 2 15 1 2 15 1 2 21 1 2 21 1 2 21 1 2 21 1 2 25 25 25 25 25 Connect...

Page 8: ...Condensation Deflector 690071 Insulation Case Nut 606287 Distributor Figure 3 Condensation Deflector Positioning 708821D Replaces 708821C Specifications illustrations subject to change without notice...

Reviews: