background image

3

REQUIREMENTS & CODES

 WARNING:

This unit must be installed in accordance with 
instructions outlined in this manual during 
the installation, service, and operation of 
this unit. Unqualified individuals should not 
attempt to interpret these instructions or 
install this equipment. Failure to follow safety 
recommendations could result in possible 
damage to the equipment, serious personal 
injury or death.

•  The  installer  must  comply  with  all  local  codes  and 

regulations which govern the installation of this type 
of equipment. Local codes and regulations take 
precedence over any recommendations contained in 
these instructions. Consult local building codes for 
special installation requirements.

•  This equipment contains nitrogen gas. Installation or 

servicing should only be performed by qualified trained 
personnel thoroughly familiar with this type equipment.

•  All electrical wiring must be completed in accordance 

with local, state and national codes and regulations 
and with the National Electric Code (ANSI/NFPA 70) 
or in Canada the Canadian Electric Code Part 1 CSA 
C.22.1.

•  Installation of equipment may require brazing operations. 

Installer must comply with safety codes and wear 
appropriate safety equipment (safety glasses, work 
gloves, fire extinguisher, etc.) when performing brazing 
operations.

The information listed below is for reference purposes only 
and does not necessarily have jurisdiction over local or state 
codes. Always consult with local authorities before installing 
any gas appliance.

Duct Systems

•  US and CANADA: Air Conditioning Contractors Association 

(ACCA) Manual D, Sheet Metal and Air Conditioning 
Contractors National Association (SMACNA), or American 
Society of Heating, Refrigeration, and Air Conditioning 
Engineers (ASHRAE) Fundamentals Handbook

Electrical Connections

•  US: National Electrical Code (NEC) ANSI/NFPA 70
•  CANADA: Canadian Electrical Code CSA C22.1

Safety

•  US:  (NFGC)  NFPA  54–1999/ANSI  Z223.1  and  the 

Installation Standards, Warm Air Heating and Air 
Conditioning Systems ANSI/NFPA 90B.

•  CANADA:  CAN/CGA-B149.1  and  .2–M00  National 

Standard of Canada. (NSCNGPIC)

•  Install this unit only in a location and position as specified 

on pages 4 & 5. This unit is designed only for Indoor 
installations and should be located with consideration 
of minimizing the length of the supply and return ducts. 

•  Follow  all  precautions  in  the  literature,  on  tags,  and 

on labels provided with the equipment. Read and 
thoroughly understand the instructions provided with 
the equipment prior to performing the installation and 
operational checkout of the equipment.

•  This  air  handler  may  be  used  for  temporary  heating 

of buildings or structures under construction. See the 
guidelines listed on page 4.

•  Air handler installations in a residential garage must be 

installed as specified on page 5.

Summary of Contents for B6VMAI

Page 1: ...type of equipment Improper installation service adjustment or maintenance may cause explosion fire electrical shock or other hazardous conditions which may result in personal injury or property damage...

Page 2: ...t SAFETY INFORMATION INSTALLER Please read all instructions before servicing this equipment Pay attention to all safety warnings and any other special notes highlighted in the manual Safety markings a...

Page 3: ...operations The information listed below is for reference purposes only and does not necessarily have jurisdiction over local or state codes Always consult with local authorities before installing any...

Page 4: ...ons Applicable building codes may require additional clearance to equipment Refer to applicable building codes for details Static pressure drop through louvered openings and through return air plenums...

Page 5: ...must be properly insulated to minimize duct losses and prevent condensation Use insulation with an outer vapor barrier Refer to local codes for insulation material requirements Air Filters B6VMAI Ser...

Page 6: ...and floor Upflow Installations All air handlers are factory shipped ready for upflow installation The horizontal drain pan may be removed from the air handler when installing the unit in an upflow con...

Page 7: ...he horizontal drain pan IMPORTANT If the webbing is not removed the condensate will not drain properly and ceiling damage may occur 3 Insert the plug from horizontal drain pan into the open and unused...

Page 8: ...during installation Ifpreciseformingofrefrigerantlinesisrequired acopper tubing bender is recommended Avoid sharp bends and contact of the refrigerant lines with metal surfaces Refrigerant lines shou...

Page 9: ...ng or pvc pipe and adequately trapped Both drain tubes must have a minimum diameter of 3 4 and be trapped separately IMPORTANT Failure to install a trap may resultincondensationoverflowingthedrainpan...

Page 10: ...operation maybeadverselyaffectedbyradiantheatfromfireplaces sunlight or lighting fixtures and convective heat from warm air registers or electrical appliances Refer to the thermostat manufacturer s i...

Page 11: ...SeeiQDrivethermostat user manual Dehumidification The iQ Drive system may provide some dehumidification by lowering the airflow to increase the amount of humidity that is removed from the circulating...

Page 12: ...s on the air handler after servicingorcleaning changingthefilters Donotoperate the air handler without all doors and covers in place Verify that the thermostat is properly installed and is not being a...

Page 13: ...D B 43 5 16 19 11 16 18 1 4 No Tall B 49 5 16 19 11 16 18 1 4 No C 55 15 16 22 7 16 21 Yes 3 4 3 4 3 4 13 1 1 4 1 5 8 1 7 8 1 1 4 3 1 4 2 5 8 11 8 K O Typ 1 3 4 K O Typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1...

Page 14: ...tor Mount Kit Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Control Board Filter Door Upper Door Assembly Lower Door Assembl...

Page 15: ...15 79 1 80 54 1 60 25 0 25 69 0 70 47 4 50 21 6 25 20 104 1 125 54 1 60 50 0 50 90 7 100 47 4 50 43 3 50 25 N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A 30 N A N A N A N A N A N A...

Page 16: ...R W2 W H OD UNIT BLOWER COIL THERMISTOR Figure 10 B6VMAI EXV Control Board R R 410A 1 2 3 4 5 6 7 8 ON OFF R 22 THERM THERM PRESS C Y COMM EXV Figure 11 B6VMAI Interface Control Board LED 1 BLWDTC BLW...

Page 17: ...TOR R4 SW Y EXV R C ID BLWR R DX DX GND R C R C W2 W H Y DX DX GND THERMISTOR EXV 6 WIRE CABLE SUCTION TEMP SENSOR CABLE N O I T C U S E R U S S E R P R O S N E S HARNESS THRU CORE RING THRU CORE RING...

Page 18: ...18...

Page 19: ...19...

Page 20: ...oteshighlightedinthemanual Improper installation of the air handler or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedto...

Reviews: