background image

11

installation manual for the proper type and quantity of 
refrigerant.

Refrigerant Charging

The system refrigerant charge can be checked and 

adjusted through the service ports provided at the front 

panel of the outdoor unit. Use only gauge lines which have 

a Schrader depression device present to actuate the valve.

Air Circulation

Running the Blower Continuously

Set the thermostat’s system mode to 

OFF

 and the 

thermostat’s fan mode to any speed level. The blower 

motor should run continuously. Check for air delivery at 

the register(s). Ensure that there are no obstructions at 

the registers or in the ducts.

NOTE:

 If blower is turning opposite of arrow direction, shut 

off main power to the unit and switch any two field wires 

at the disconnect. 

DO NOT 

alter unit wiring.

Turning the Blower Off

Set thermostat’s fan mode to 

AUTO

, the blower will shut 

down immediately.

System Cooling

1. Set the thermostat’s system mode to 

COOL

 and fan 

mode to 

AUTO

. Lower the thermostat’s temperature 

mode below room temperature and observe that the 
blower energizes. Check the air being discharged at 
the register is cooler than room temperature. Verify 
unit refrigerant pressures are in order. Blower should 
be turning in direction indicated by arrow.

 NOTE:

 DO NOT alter unit wiring. Listen for any unusual 

noises. Locate the source and correct as needed.

2. Allow the unit to run for several minutes and then set 

the thermostat’s temperature above room temperature. 
Verify the blower cycles off with the thermostat.

System Heating

1. Set the thermostat’s system mode to 

HEAT

 and the fan 

mode to 

AUTO

. Increase the thermostat’s temperature 

above room temperature and observe that the blower 
energizes. Check the air being discharged at the register 
is warmer than room temperature.

2. Allow the unit to run for several minutes and then set 

the thermostat’s temperature below room temperature. 
Verify the blower cycles off with the thermostat.

Blower Settings

The iQ Drive thermostat controls the blower speed and 

timing to satisfy set temperatures. See iQ Drive thermostat 

user manual.

Dehumidification

The iQ Drive system may provide some dehumidification 

by lowering the airflow to increase the amount of humidity 

that is removed from the circulating air during cooling. See 

iQ Drive thermostat user manual.

STARTUP & ADjUSTMENTS

 WARNING:

The evaporator coil is shipped from the factory 

with a nitrogen charge. Use caution when 

preparing coils for field connections. If repairs 

make it necessary for evacuation and charging, 

it should only be attempted by qualified, 

trained personnel thoroughly familiar with this 

equipment. Some local codes require licensed 

installation service personnel to service this 

type of equipment. Under no circumstances 

should the equipment owner attempt to install 

and/or service this equipment. Failure to comply 

with this warning could result in equipment 

damage, personal injury, or death.

NITROGEN

HEALTH

FLAMMABILITY

REACTIVITY

0 Minimal Hazard

1 Slight Hazard

1

0

0

Before You Start the Unit

Prior to start-up, complete the following inspections:

  Verify the unit is level and properly located with adequate 

clearances for servicing the unit. See Table 1 (page 4).

 Check condensate drain line(s) for proper drainage.

 Verify the surrounding area and top of the unit is free 

from obstructions and debris.

 Check all duct connections. Make sure the duct work 

is adequately sealed to prevent air leakage.

 Check all coil connections for leaks.

 Verify that the line voltage power leads are securely 

connected and the unit is properly grounded. Make sure 
all doors are installed before restoring power to the unit

  Verify the thermostat is wired correctly. Make sure all 

low voltage wires are securely connected.

 Verify the power supply branch circuit overcurrent 

protection is sized properly.

 Verify filter is properly and securely installed.

IMPORTANT:

 Before starting the unit, install the initial 

charge on units that are factory shipped with a nitrogen 

holding charge:
1. Read all installation instructions first.
2. Purge the nitrogen holding charge.
3. Evacuate the unit to 350 - 500 microns.
4. Allow the unit to remain under vacuum for at least 30 

minutes.

5. Weigh in the proper amount of new (or reclaimed) 

refrigerant. Refer to the air conditioner or heat pump  

Summary of Contents for B6VMAI

Page 1: ...type of equipment Improper installation service adjustment or maintenance may cause explosion fire electrical shock or other hazardous conditions which may result in personal injury or property damage...

Page 2: ...t SAFETY INFORMATION INSTALLER Please read all instructions before servicing this equipment Pay attention to all safety warnings and any other special notes highlighted in the manual Safety markings a...

Page 3: ...operations The information listed below is for reference purposes only and does not necessarily have jurisdiction over local or state codes Always consult with local authorities before installing any...

Page 4: ...ons Applicable building codes may require additional clearance to equipment Refer to applicable building codes for details Static pressure drop through louvered openings and through return air plenums...

Page 5: ...must be properly insulated to minimize duct losses and prevent condensation Use insulation with an outer vapor barrier Refer to local codes for insulation material requirements Air Filters B6VMAI Ser...

Page 6: ...and floor Upflow Installations All air handlers are factory shipped ready for upflow installation The horizontal drain pan may be removed from the air handler when installing the unit in an upflow con...

Page 7: ...he horizontal drain pan IMPORTANT If the webbing is not removed the condensate will not drain properly and ceiling damage may occur 3 Insert the plug from horizontal drain pan into the open and unused...

Page 8: ...during installation Ifpreciseformingofrefrigerantlinesisrequired acopper tubing bender is recommended Avoid sharp bends and contact of the refrigerant lines with metal surfaces Refrigerant lines shou...

Page 9: ...ng or pvc pipe and adequately trapped Both drain tubes must have a minimum diameter of 3 4 and be trapped separately IMPORTANT Failure to install a trap may resultincondensationoverflowingthedrainpan...

Page 10: ...operation maybeadverselyaffectedbyradiantheatfromfireplaces sunlight or lighting fixtures and convective heat from warm air registers or electrical appliances Refer to the thermostat manufacturer s i...

Page 11: ...SeeiQDrivethermostat user manual Dehumidification The iQ Drive system may provide some dehumidification by lowering the airflow to increase the amount of humidity that is removed from the circulating...

Page 12: ...s on the air handler after servicingorcleaning changingthefilters Donotoperate the air handler without all doors and covers in place Verify that the thermostat is properly installed and is not being a...

Page 13: ...D B 43 5 16 19 11 16 18 1 4 No Tall B 49 5 16 19 11 16 18 1 4 No C 55 15 16 22 7 16 21 Yes 3 4 3 4 3 4 13 1 1 4 1 5 8 1 7 8 1 1 4 3 1 4 2 5 8 11 8 K O Typ 1 3 4 K O Typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1...

Page 14: ...tor Mount Kit Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Control Board Filter Door Upper Door Assembly Lower Door Assembl...

Page 15: ...15 79 1 80 54 1 60 25 0 25 69 0 70 47 4 50 21 6 25 20 104 1 125 54 1 60 50 0 50 90 7 100 47 4 50 43 3 50 25 N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A 30 N A N A N A N A N A N A...

Page 16: ...R W2 W H OD UNIT BLOWER COIL THERMISTOR Figure 10 B6VMAI EXV Control Board R R 410A 1 2 3 4 5 6 7 8 ON OFF R 22 THERM THERM PRESS C Y COMM EXV Figure 11 B6VMAI Interface Control Board LED 1 BLWDTC BLW...

Page 17: ...TOR R4 SW Y EXV R C ID BLWR R DX DX GND R C R C W2 W H Y DX DX GND THERMISTOR EXV 6 WIRE CABLE SUCTION TEMP SENSOR CABLE N O I T C U S E R U S S E R P R O S N E S HARNESS THRU CORE RING THRU CORE RING...

Page 18: ...18...

Page 19: ...19...

Page 20: ...oteshighlightedinthemanual Improper installation of the air handler or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedto...

Reviews: