background image

6

to avoid damage to the ceiling in the event of condensate 

overflow. Additionally, it is recommended that an approved 

water level indicator or float switch device be used to shut 

down the unit in the event water is detected in the auxiliary 

drain pan.
NotE 2: In horizontal right applications where the air 

handler is in a humid location in an unconditioned space, 

it is recomended to install a condensate shield kit over the 

control board.
If suspending the air handler from the ceiling, assemble a 

support frame (

Figure 4

) using slotted iron channel and full 

threaded rod. Fasten the frame together with nuts, washers, 

and lockwashers. Secure the support frame to the rafters 

with lag bolts. The air handler can also be suspended using 

steel straps around each end of the unit. The straps should 

be attached to the air handler with sheet metal screws and 

to the rafters with bolts.

Horizontal Left Installations:

1. Remove the coil access door.

2. Remove the plug from one of the threaded holes in the 

horizontal drain pan. Completely remove the webbing 

located in the threaded holes of the horizontal drain pan. 

  IMPoRtANt: If the webbing is not removed, the 

condensate will not drain properly and ceiling damage 

may occur.

3. Insert the plug (from horizontal drain pan) into the open 

and unused drain hole in the drain pan at the bottom of 

the unit to block bypass air.

4. Remove the corresponding drain line knockout from the 

coil access door to allow access to the horizontal drain.

5. Replace the door and attach the drain line.

Horizontal Right Installations:

1. Remove the coil access door. Unscrew the line-set tube 

close-off plate from the front left cabinet rail.

2. Slide the coil and drain pan assembly out of the unit.

3. Remove the sheet metal hairpin covers (if supplied) from 

the back of the coil and discard.

4. Place the horizontal drain pan on the opposite side of the 

coil. On units with 2 sets of knockouts, remove the other set 

of knockouts in the coil spacing plates and insert support 

rod.

5. Slide the coil and the horizontal drain pan assembly back 

into the unit. Re-attach the tube close off plate.

 

NotE: For A-size cabinet applications, it may be preferrable 

to remove the blower assembly prior to installing the coil 

& drainpan. In this case follow instructions 1-4 as listed 

above but also remove the blower access door and blower 

assembly. The blower assembly is secured with two 

screws on either side near the front. With these removed 

the blower assembly can slide out of the front of the unit. 

Install the coil and drain pan as described in step 5 and 

then replace the blower assembly. Make sure the flanges 

on the sides of the blower assembly are captured by the 

pockets in the blower deck. It may be necessary to lift 

the blower assembly during insertion to allow the lower 

blower leg to clear the side of the drain pan. The blower 

will stop against the back of the blower deck. Replace the 

two screws and the blower access door and procede with 

steps 6-9.

6. Remove the plug from one of the threaded holes in the 

horizontal drain pan. Completely remove the webbing 

located in the threaded holes of the drain pan.

  IMPoRtANt: If the webbing is not removed, the 

condensate will not drain properly and ceiling damage 

may occur.

Horizontal

Drain Pan

Return

Air

Figure 1. 

upflow Installation

Figure 2. 

Downflow Installation

Tube

Close-off 

Plate

Coil

Cabinet

Adaptor Kit

Threaded 

Rod

Lag
Bolt

Nuts (x2)

Washer 

and 

Lockwasher

Nuts (x2)

Figure 4. 

unit Horizontally Suspended

Figure 3. 

Horizontal configurations

HORIZONTAL RIGHT

HORIZONTAL LEFT

RETURN

AIR

RETURN

AIR

Summary of Contents for B6BM Series

Page 1: ...ole as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious...

Page 2: ...tion 12 Turning the Blower Off 12 System Cooling 12 System Heating 12 Selecting Minimum Electric Heat Airflow 12 Blower Configurations 12 Determining Nominal System Capacity 12 3 Speed Units 12 High E...

Page 3: ...installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could resu...

Page 4: ...ment Refer to applicable building codes for details Static pressure drop through louvered openings and through return air plenums should be considered in the overallductdesigninthedeterminationoftheto...

Page 5: ...install all the needed gaskets and grommets around penetrations into the air handler such as for electrical wiring Air handler INSTALLATION B6 series air handler s are shipped ready for vertical upflo...

Page 6: ...oil and drain pan assembly out of the unit 3 Remove the sheet metal hairpin covers if supplied from the back of the coil and discard 4 Place the horizontal drain pan on the opposite side of the coil O...

Page 7: ...equipment damage personal injury or death The installer should make every effort to ensure the field installed refrigerant containing components of the system have been installed in accordance with t...

Page 8: ...htenanadditional1 4turnusingtwowrenches The movement of the two lines will show how much the nut is tightened If a torque wrench is used tighten to 10 12 ft lbs or 14 16 Nm Connecting the Linesets The...

Page 9: ...d tubing or pvc pipe and adequately trapped Both drain tubes must have a minimum diameter of 3 4 and be trapped separately IMPORTANT Failure to install a trap may result in condensation overflowing th...

Page 10: ...of the original wires supplied with the unit the replacement wire must be copper wire consisting of the same gauge and temperature rating Provide power supply for the unit in accordance with the unit...

Page 11: ...ions The motor control board has a DHUM or D connection that allows the system to increase the amount of humidity that is removed from the circulating air See Figure 17 Figure 18 page 27 This is accom...

Page 12: ...control boards do not support non electric heat because the heating air flow cannot be set independently Blower Configurations Determining Nominal System Capacity To select the appropriate airflows f...

Page 13: ...ed the basic cooling heat pump airflow selected may be too low Verify the setting selected is within the range shown in Table 9 and that the the system is properly charged Please refer to the instruct...

Page 14: ...etailers WARNING Never operate the air handler without a filter in place Dust and lint in the return air can build up on internal components resulting in loss of efficiency equipment damage and possib...

Page 15: ...11 4 15 8 17 8 11 4 3 1 4 2 5 8 11 8 K O typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W 1 1 8 1 7 8 7 8 K O H 22 A Cabinet Size H W A Detail D A 43 5 16 14 3 16 12...

Page 16: ...Motor Mount Kit Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Motor Control Board Filter Door Upper Door Assembly Lower Door...

Page 17: ...764 701 631 555 Corrected ESP1 0 00 0 04 0 16 0 27 0 39 0 51 0 62 0 74 Medium 1265 1232 1188 1133 1067 991 903 805 Corrected ESP1 0 00 0 00 0 03 0 15 0 28 0 41 0 54 0 68 High 1427 1385 1333 1270 1196...

Page 18: ...805 750 1 1 1 0 1155 1105 1060 1010 965 920 870 825 0 0 0 1 1230 1185 1140 1090 1045 1010 965 920 1 0 0 1 1285 1260 1210 1165 1125 1080 1040 1010 0 1 0 1 1330 1290 1245 1205 1170 1125 1085 1045 1 1 0...

Page 19: ...ttings for these airflows A Cabinet B Cabinet C Cabinet CFM Nominal Capacity CFM Nominal Capacity CFM Nomical Capacity 525 1 5 TON 525 1 5 TON 1100 3 TON 560 560 1200 3 5 TON 600 600 1250 625 650 2 TO...

Page 20: ...1100 1 0 1 0 0 700 1 15 1300 1 0 1 0 1 750 1 20 1500 1 0 1 1 0 800 1 25 n a 1 0 1 1 1 850 1 30 n a 1 1 0 0 0 875 1 1 0 0 1 950 1 1 0 1 0 1050 1 1 0 1 1 1150 1 1 1 0 0 1250 1 1 1 0 1 1350 1 1 1 1 0 14...

Page 21: ...7 67 6 50 25 70 020H XX 52 6 50 0 102 6 60 60 110 46 0 43 3 89 3 50 45 90 009Q XX 29 7 30 26 1 30 015Q XX 45 9 50 40 2 45 B 42 48 None 3 1 3 1 15 15 3 1 3 1 15 15 005H XX 28 1 28 1 30 30 24 8 24 8 25...

Page 22: ...ase MCA MOP MCA MOP Circuit A Circuit B Circuit C Single Circuit Circuit A Circuit B Circuit C Single Circuit Circuit A Circuit B Circuit C Single Circuit Circuit A Circuit B Circuit C Single Circuit...

Page 23: ...seconds delay Stage 3 Heat on after 10 seconds delay Stage 4 Heat on after 15 seconds delay Stage 5 Heat on after 20 seconds delay Stage 6 Heat on after 25 seconds delay Off Heat stages off instantly...

Page 24: ...econd delay Stage 2 Heat on after 5 seconds delay Stage 3 Heat on after 10 seconds delay Stage 4 Heat on after 15 seconds delay Stage 5 Heat on after 20 seconds delay 30 KW Stage 1Heat on instantly Co...

Page 25: ...Typical 2 Stage Heat Pump with 2 Stage Air Handler Y2 Y2 Y2 Y2 OUT W E R Air Conditioner Air Handler Air Conditioner Air Handler Heat Pump Air Handler Heat Pump O R C Y Air Handler Heat Pump NOTE Jum...

Page 26: ...1 BLWDTC BLWDTC_R HEAT COOL EAC L 1 L 2 P2 R C G W Y 3A Fuse HEATER P1 Figure 15 Single Stage Control Board C R G Y2 Y O 1W 2W 1Y L LED 1 HEATER P1 L 2 HUM EAC P2 3A Fuse P3 Figure 16 Two Stage Contro...

Page 27: ...N TEST PORT BLOWER MOTOR RED INPUTS COOL HEAT FAN SPEED OUTPUTS STATUS LIGHTS 2 3 4 5 6 7 8 OFF ON A B Figure 18 Variable Speed Motor Control Board Figure 17 Fixed Speed Motor Control Board 3A Fuse EA...

Page 28: ...e transformateur peut avoir un robinet principal double tension Agencez la position du robinet au type de tension de l installation 4 Si le c blage interne est remplac utilisez seulement un fil de cui...

Page 29: ...sse du moteur du ventilateur peut diff rer de l illustration Consultez les Instructions d installation 2 D branchez toutes les sources d alimentation avant l entretien 3 Le transformateur peut avoir u...

Page 30: ...ons d installation 2 D branchez toutes les sources d alimentation avant l entretien 3 Le transformateur peut avoir un robinet principal double tension Agencez la position du robinet au type de tension...

Page 31: ...31...

Page 32: ...INSTALLERS Itisyourresponsibilitytoknowthisproductbetterthanyourcustomer This includes being able to install the product according to strict safety guidelines and instructing the customer on how to o...

Reviews: