ELEctRIcAL coNNEctIoNS

 WARNING:

ELEctRIcAL SHocK, FIRE oR

EXPLoSIoN HAZARD

Failure to follow safety warnings exactly could 

result in serious injury or property damage.
Improper servicing could result in dangerous 

operation, serious injury, death or property 

damage.
Before servicing, disconnect all electrical power 

to furnace.
•  Before  servicing,  disconnect  all  electrical 

power to the air handler.

•  When servicing controls, label all wires prior 

to disconnecting. Reconnect wires correctly.

•  Verify proper operation after servicing.

•  Electrical  connections  must  be  in  compliance  with 

all applicable local codes and ordinances, and with 

the current revision of the National Electric Code  

(ANSI/NFPA 70).

•  For Canadian installations, the electrical connections and 

grounding shall comply with the current Canadian Electrical 

Code (CSA C22.1 and/or local codes).

Pre-Electrical checklist

 Verify the voltage, frequency, and phase of the supply 

source match the specifications on the unit rating plate.

 Verify that the service provided by the utility is sufficient 

to handle the additional load imposed by this equipment. 

See the unit wiring label or 

Table 11, (page 21)

 & 

Table 

12, (page 22)

 for proper MCA & MOP information.

 Verify factory wiring is in accordance with the unit wiring 

diagram (

Figure 19 (page 28)

Figure 20 (page 29)

, & 

Figure 21 (page 30)

). Make sure the connections didn’t 

loosen during shipping or installation.

Line Voltage

• 

An electrical disconnect must be located within sight 

of and readily accessible to the unit. This switch shall 

be capable of electrically de-energizing the outdoor unit. 

See unit data label for proper incoming field wiring. Any 

other wiring methods must be acceptable to authority 

having jurisdiction.

•  It  is  recommended  that  the  line  voltage  to  the  unit  be 

supplied from a dedicated branch circuit containing the 

correct fuse or circuit breaker for the unit.

•  Overcurrent  protection  must  be  provided  at  the  branch 

circuit distribution panel and sized as shown on the unit 

rating label and according to applicable local codes. See 

the unit rating plate and 

Table 11, (page 21)

 & 

Table 12, 

(page  22)

 for maximum circuit ampacity and maximum 

overcurrent protection limits.

•  The installer should become familiar with the wiring diagram/

schematic before making any electrical connections to the 

unit. See the unit wiring label or 

Figure 19 (page 28)

Figure 20 (page 29)

, & 

Figure 21 (page 30)

.

•  Use only copper wire for the line voltage power supply 

to this unit. Use proper code agency listed conduit and a 

conduit connector for connecting the supply wires to the 

unit. Aluminum supply wire may be used if a heater kit is 

installed.

•  If replacing any of the original wires supplied with the unit, 

the replacement wire must be copper wire consisting of 

the same gauge and temperature rating.

•  Provide power supply for the unit in accordance with the 

unit wiring diagram, and the unit rating plate. Use UL listed 

conduit and conduit connectors for connecting the supply 

wires to the unit and for proper grounding. Field supplied 

bushings for the power supply cables must be added to 

support and protect the power supply cables. 

•  All 208/230 Volt units are shipped from the factory wired for 

240 volt operation. For 208V operation, remove the lead 

from the transformer terminal marked 240V and connect 

it to the terminal marked 208V.

thermostat connections

•  Thermostat connections shall be in accordance with the 

instructions supplied with the thermostat. The thermostat 

used with this equipment must operate in conjunction 

with any installed accessories. Typical AC and air handler 

hookups are shown in 

Figure 13 (page 25)

.

 cAutIoN:

Isolation must be maintained from the external 

class 2 output of any transformer in a cooling 

circuit. use a thermostat with isolating contacts 

to prevent inter-connection of class 2 outputs.

•  Where local codes require that the thermostat wiring must 

be routed through a conduit or raceway, splices can be 

made inside the unit; however, all wiring must be NEC 

Class 1 and separated from incoming power leads.

•  The thermostat should be mounted about 5 feet above the 

floor on an inside wall. DO NOT install the thermostat on 

an outside wall or any other location where its operation 

may be adversely affected by radiant heat from fireplaces, 

sunlight, or lighting fixtures, and convective heat from 

warm air registers or electrical appliances. Refer to the 

thermostat manufacturer’s instruction sheet for detailed 

mounting and installation information.

•  Install the grommet, which is packed with the unit, in the 

hole for low-voltage wires. Properly connect the low-voltage 

wiring between the thermostat, outdoor unit, and control 

board. 

NotE: When the low voltage wires are positioned 

in this grommet, the grommet will prevent chafing and/or 

shorting of the low voltage leads.

Grounding

 WARNING:

the unit cabinet must have an uninterrupted or 

unbroken electrical ground to minimize personal 

injury if an electrical fault should occur. Do not 

use gas piping as an electrical ground!

This unit must be electrically grounded in accordance with 

local codes or, in the absence of local codes, with the National 

Electrical Code (ANSI/NFPA 70) or the CSA C22.1 Electrical 

Code. Use the grounding lug provided in the control box for 

grounding the unit.

control Board

The control board in the air handler controls the timing 

sequence of the elements. The board is equipped with a 3 

second blower on delay and a 15 second blower off delay in 

heating and a 40 second blower off delay in cooling.

Summary of Contents for B6BM Series

Page 1: ...ole as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious...

Page 2: ...tion 12 Turning the Blower Off 12 System Cooling 12 System Heating 12 Selecting Minimum Electric Heat Airflow 12 Blower Configurations 12 Determining Nominal System Capacity 12 3 Speed Units 12 High E...

Page 3: ...installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could resu...

Page 4: ...ment Refer to applicable building codes for details Static pressure drop through louvered openings and through return air plenums should be considered in the overallductdesigninthedeterminationoftheto...

Page 5: ...install all the needed gaskets and grommets around penetrations into the air handler such as for electrical wiring Air handler INSTALLATION B6 series air handler s are shipped ready for vertical upflo...

Page 6: ...oil and drain pan assembly out of the unit 3 Remove the sheet metal hairpin covers if supplied from the back of the coil and discard 4 Place the horizontal drain pan on the opposite side of the coil O...

Page 7: ...equipment damage personal injury or death The installer should make every effort to ensure the field installed refrigerant containing components of the system have been installed in accordance with t...

Page 8: ...htenanadditional1 4turnusingtwowrenches The movement of the two lines will show how much the nut is tightened If a torque wrench is used tighten to 10 12 ft lbs or 14 16 Nm Connecting the Linesets The...

Page 9: ...d tubing or pvc pipe and adequately trapped Both drain tubes must have a minimum diameter of 3 4 and be trapped separately IMPORTANT Failure to install a trap may result in condensation overflowing th...

Page 10: ...of the original wires supplied with the unit the replacement wire must be copper wire consisting of the same gauge and temperature rating Provide power supply for the unit in accordance with the unit...

Page 11: ...ions The motor control board has a DHUM or D connection that allows the system to increase the amount of humidity that is removed from the circulating air See Figure 17 Figure 18 page 27 This is accom...

Page 12: ...control boards do not support non electric heat because the heating air flow cannot be set independently Blower Configurations Determining Nominal System Capacity To select the appropriate airflows f...

Page 13: ...ed the basic cooling heat pump airflow selected may be too low Verify the setting selected is within the range shown in Table 9 and that the the system is properly charged Please refer to the instruct...

Page 14: ...etailers WARNING Never operate the air handler without a filter in place Dust and lint in the return air can build up on internal components resulting in loss of efficiency equipment damage and possib...

Page 15: ...11 4 15 8 17 8 11 4 3 1 4 2 5 8 11 8 K O typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W 1 1 8 1 7 8 7 8 K O H 22 A Cabinet Size H W A Detail D A 43 5 16 14 3 16 12...

Page 16: ...Motor Mount Kit Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Motor Control Board Filter Door Upper Door Assembly Lower Door...

Page 17: ...764 701 631 555 Corrected ESP1 0 00 0 04 0 16 0 27 0 39 0 51 0 62 0 74 Medium 1265 1232 1188 1133 1067 991 903 805 Corrected ESP1 0 00 0 00 0 03 0 15 0 28 0 41 0 54 0 68 High 1427 1385 1333 1270 1196...

Page 18: ...805 750 1 1 1 0 1155 1105 1060 1010 965 920 870 825 0 0 0 1 1230 1185 1140 1090 1045 1010 965 920 1 0 0 1 1285 1260 1210 1165 1125 1080 1040 1010 0 1 0 1 1330 1290 1245 1205 1170 1125 1085 1045 1 1 0...

Page 19: ...ttings for these airflows A Cabinet B Cabinet C Cabinet CFM Nominal Capacity CFM Nominal Capacity CFM Nomical Capacity 525 1 5 TON 525 1 5 TON 1100 3 TON 560 560 1200 3 5 TON 600 600 1250 625 650 2 TO...

Page 20: ...1100 1 0 1 0 0 700 1 15 1300 1 0 1 0 1 750 1 20 1500 1 0 1 1 0 800 1 25 n a 1 0 1 1 1 850 1 30 n a 1 1 0 0 0 875 1 1 0 0 1 950 1 1 0 1 0 1050 1 1 0 1 1 1150 1 1 1 0 0 1250 1 1 1 0 1 1350 1 1 1 1 0 14...

Page 21: ...7 67 6 50 25 70 020H XX 52 6 50 0 102 6 60 60 110 46 0 43 3 89 3 50 45 90 009Q XX 29 7 30 26 1 30 015Q XX 45 9 50 40 2 45 B 42 48 None 3 1 3 1 15 15 3 1 3 1 15 15 005H XX 28 1 28 1 30 30 24 8 24 8 25...

Page 22: ...ase MCA MOP MCA MOP Circuit A Circuit B Circuit C Single Circuit Circuit A Circuit B Circuit C Single Circuit Circuit A Circuit B Circuit C Single Circuit Circuit A Circuit B Circuit C Single Circuit...

Page 23: ...seconds delay Stage 3 Heat on after 10 seconds delay Stage 4 Heat on after 15 seconds delay Stage 5 Heat on after 20 seconds delay Stage 6 Heat on after 25 seconds delay Off Heat stages off instantly...

Page 24: ...econd delay Stage 2 Heat on after 5 seconds delay Stage 3 Heat on after 10 seconds delay Stage 4 Heat on after 15 seconds delay Stage 5 Heat on after 20 seconds delay 30 KW Stage 1Heat on instantly Co...

Page 25: ...Typical 2 Stage Heat Pump with 2 Stage Air Handler Y2 Y2 Y2 Y2 OUT W E R Air Conditioner Air Handler Air Conditioner Air Handler Heat Pump Air Handler Heat Pump O R C Y Air Handler Heat Pump NOTE Jum...

Page 26: ...1 BLWDTC BLWDTC_R HEAT COOL EAC L 1 L 2 P2 R C G W Y 3A Fuse HEATER P1 Figure 15 Single Stage Control Board C R G Y2 Y O 1W 2W 1Y L LED 1 HEATER P1 L 2 HUM EAC P2 3A Fuse P3 Figure 16 Two Stage Contro...

Page 27: ...N TEST PORT BLOWER MOTOR RED INPUTS COOL HEAT FAN SPEED OUTPUTS STATUS LIGHTS 2 3 4 5 6 7 8 OFF ON A B Figure 18 Variable Speed Motor Control Board Figure 17 Fixed Speed Motor Control Board 3A Fuse EA...

Page 28: ...e transformateur peut avoir un robinet principal double tension Agencez la position du robinet au type de tension de l installation 4 Si le c blage interne est remplac utilisez seulement un fil de cui...

Page 29: ...sse du moteur du ventilateur peut diff rer de l illustration Consultez les Instructions d installation 2 D branchez toutes les sources d alimentation avant l entretien 3 Le transformateur peut avoir u...

Page 30: ...ons d installation 2 D branchez toutes les sources d alimentation avant l entretien 3 Le transformateur peut avoir un robinet principal double tension Agencez la position du robinet au type de tension...

Page 31: ...31...

Page 32: ...INSTALLERS Itisyourresponsibilitytoknowthisproductbetterthanyourcustomer This includes being able to install the product according to strict safety guidelines and instructing the customer on how to o...

Reviews: