background image

Copyright 

©

 2020 Nortek Security & Control   

5

4

    Copyright 

©

 2020 Nortek Security & Control

Thermostat Power

The thermostat can be powered by either 24VAC from the HVAC system or from four (4) type AA 

internal batteries. 

DO NOT

 use this thermostat for line voltage controls (120/240VAC).

The C Wire

If the 24VAC common wire (usually blue) is present and is connected to 24VAC common at the HVAC 

system end, the thermostat can be powered from the HVAC system. If there is no common wire, 

batteries are required.

24VAC Power

Powering the thermostat with 24VAC power 

requires

 both the 24VAC “C” common wire (typically a 

blue wire) and the 24VAC ”R” return wire (typically a red wire). 

Battery Power

Powering the thermostat from batteries 

does not 

require a “C” wire connection.

DO NOT

 install batteries if the thermostat is powered by 24VAC. They are NOT required for backup. 

If the thermostat is powered by batteries, the thermostat will operate for approximately (2) two 

years on four (4) AA Alkaline batteries depending on the frequency of user operations and backlight 

operation. Always use Alkaline batteries and replace them in complete sets of four (4). 

Z-Wave Operation when Battery-Powered

IMPORTANT: When the thermostat is installed on a Z-Wave network, while it is battery 

powered, it will NOT work as a Z-Wave repeater .

Remove Existing Thermostat

• 

Turn the thermostat power off. This is usually done at the heating/cooling system or circuit 

breaker panel.

• 

Remove the cover of old thermostat to expose the wiring terminals.

• 

Take a picture of the wiring terminals and wires before disconnecting them!

• 

Mark  the  existing  thermostat  wires  with  the  labels  (not  included)  according  to  the  terminal 

markings. Some installations may have additional wires not shown in the example illustration 

below (Y1, Y2, W1, W2, O,B).

• 

Use the thermostat terminal “names/marking” (not the wiring color) to mark the wires.

• 

Remove the old thermostat base.

CAUTION: When removing thermostat, don’t let the wires slip into the wall and 

don’t let the wires touch each other.

• 

If the old thermostat was a mercury style thermostat, dispose of it properly as described below.

Figure 2. 

Label Wire Terminals

Note: 

Taking a picture is critical if problems are encountered. This will allow reinstallation of the old 

thermostat and help with troubleshooting later if needed.

Terminal

Typical Wire Color

Function

Y

YELLOW

Cool

W

WHITE

Heat

G

GREEN

Fan

R

RED

24VAC Return

C

BLUE

24V Common (typically BLUE). When the wire is present, 

the thermostat can be powered without batteries. When 

the wire is absent, the thermostat must be powered by 

batteries if 24VAC is present across the R&C wires

Wiring Colors

While the thermostat terminal markings are intended to match the wire color (R=RED, G=GREEN, 

W=WHITE, Y=YELLOW), be sure to follow the terminal marking when marking the wires, even if the 

wire color doesn’t match. 

WARNING: If the existing thermostat is a mercury-containing device, it must be 

disposed of in compliance with federal, state and local regulations. Many states and/

or local agencies have collection/exchange programs or hazardous waste collection 

programs for mercury-containing-devices. For more information, see the U.S. 

Environmental Protection Agency website at: 

https://www.epa.gov/large-scale-residential-demolition/mercury-containing-devices-and-

demolition

C

R

G

W

Y

C

R

G

W

Y

LABEL THE WIRES TO MATCH
THE OLD THERMOSTAT TERMINAL
MARKINGS. LABELS NOT INCLUDED.

Existing Thermostat Terminals

TAKE A PICTURE!

Summary of Contents for 2GIG Z-Wave Plus

Page 1: ...N 10028238 Rev C INK BLACK PANTONE 3005 C MATERIAL 60 LB MEAD BOND SIZE 8 500 X 5 500 TOL 0 125 SCALE 1 1 FOLDING ALBUM FOLD BINDING SADDLE STITCH 72 SET 70 Fan Auto Cool F 47 User Guide 2GIG Security Automation System 2GIG Z Wave Plus Battery Powered Thermostat ...

Page 2: ...Thermostat Operation 19 Main Thermostat Screen 19 Backlight and Button Operation 19 Display 19 Staging Indicators 19 Setting the System Mode 20 System Modes 20 Special Heat Pump Mode Emergency Heat 20 Setting the Heating or Cooling Temperature Setpoint 21 Automatic Setpoint Push 21 Frost Protection 21 Setting the Fan Mode 22 Fan Modes 22 User Customization 23 User preference settings 23 Error Disp...

Page 3: ...HEATING AND COOLING TRANSFORMERS PLEASE REMOVE THE JUMPER CONNECTING RC AND RH TERMINALS FIRST AND THEN CONNECT HEATING R TO RH AND COOLING R TO RC PLEASE SEE PAGE 8 W2 HEAT STAGE 2 Typical Wiring for Heat Pump HVAC System THERMOSTAT CONNECTION C 24VAC COMMON HUM HUM W3 RH RC 24VAC POWER W1 HEAT STAGE 1 G FAN Y1 COMPRESSOR STAGE 1 Y2 COMPRESSOR STAGE 2 TYPICAL THERMOSTAT WIRING COLORS CAUTION VERI...

Page 4: ...labels not included according to the terminal markings Some installations may have additional wires not shown in the example illustration below Y1 Y2 W1 W2 O B Use the thermostat terminal names marking not the wiring color to mark the wires Remove the old thermostat base CAUTION When removing thermostat don t let the wires slip into the wall and don t let the wires touch each other If the old ther...

Page 5: ...y have one or two transformers The R wire connects differently depending on the system Single Transformer System Most HVAC systems have a single 24VAC transformer For these systems there is only one R wire that can be connected to either the thermostat s RC or RH terminal because a pre installed jumper wire connects the two terminals If installing a Standard HVAC system connect the wires from the ...

Page 6: ...e separate heating and cooling systems with their own 24VAC transformers there is an R wire from the heating system and an R wire from the cooling system For dual transformer systems connect the C wire from the cooling system to the thermostat s C terminal DO NOT CONNECT THE C WIRE FROM THE HEATING SYSTEM IMPORTANT Remove the Jumper connecting RC and RH terminals see illustration below Figure 7 Du...

Page 7: ...ction desired If the backlight is already on button touches work with the first touch Wait Mode The thermostat has a Minimum Off Time MOT delay after any heating or cooling cycle ends This delay prevents rapid heating cooling cycles and also provides short cycle protection for the system compressor This delay may be noticeable when you change a setpoint and it does not respond immediately due to t...

Page 8: ...ype for Standard HVAC systems only Gas or Electric Changeover Type available with Heat Pump setup The changeover or reversing valve is used to change from heating to cooling operation The HVAC system is either a Changeover with Cooling type O or Changeover with Heating type B Most are changeover with cooling which is the default setting For Changeover with Cooling systems select WITH COOL This is ...

Page 9: ...HID Home ID and ZNID Node ID located in the thermostat INFO screen For other specific tasks such as adding the thermostat to Scenes or Groups or deleting the thermostat from an existing network refer to the Z Wave controller instructions Removing from a Z Wave Network To remove the thermostat from the network use the following steps 1 Set your primary controller to exclude or remove mode to remove...

Page 10: ...buttons to scroll through the menu options to the desired setting Touch FAN Select to change a setting Once it begins to flash use the buttons to select the desired setting Touch FAN Select to accept the new setting flashing will stop Select MODE Done to exit the option and return to the SETUP screen Feature Description Range Test Mode Temporary shorten Minimum Run Time Minimum Off Time to 10 seco...

Page 11: ...ing off This will be Aux Stage off Threshold if 2nd Stage Heat Enable Aux Heat Enable in Heat Pump System 32 48 F 0 9 C Cool Stage 1 on Threshold Delta from Set point that stage 1 cooling start 34 45 F 1 7 C Cool Stage 1 off Threshold Delta from Set point that stage 1 cooling off 32 45 F 0 7 C Cool Stage 2 on Threshold Delta from Set point that stage 2 cooling start 36 46 F 2 8 C Cool Stage 2 off ...

Page 12: ...rent setpoint of the current heating or cooling mode Adjust the setpoint temperature up or down with the buttons Note When in the Setpoint Change screen pressing the MODE button will switch the setpoint being displayed between the Heating and Cooling setpoints Default Figure 21 Accessing Setpoints Figure 22 Setpoint Change Screen Automatic Setpoint Push The cooling setpoint cannot be set below the...

Page 13: ...play mode BACKLIGHT TIMEOUT Sets the time from last button touch that the backlight will turn OFF Range 10 30 seconds Default is 20 seconds Note Long backlight timeouts will reduce battery life SENSOR CALIBRATION Change the temperature calibration by 7 degrees Default is 0 Touch the UP or DOWN arrow buttons to change to the desired display temperature STATUS LINE Sets Status Line to Setpoints or C...

Page 14: ...the Main Screen once either battery have been removed See Battery Installation page 10 Figure 26 Error Screen Figure 27 Battery Error Display Specifications Type Programmable thermostat for 24VAC 3H 2C non heat pump or 24VAC 3H 2C heat pump systems with humidifier de humidifier support Room Temperature Measurement Temp Scale Fahrenheit Celsius user selectable Temp Range 32 122 F 0 50 C Operating T...

Page 15: ...ing Energy Heat Cool Setpoint Exit Energy Saving Mode by setting the Thermostat Mode to Off Heat Cool Auto through Z Wave Please note that Restore Default would set the Energy Heat Set Point to 72 F 22 C and Energy Cool Set Point to 80 F 26 5 C thus exiting Energy Saving Mode Scheduling Scheduling is only available for those with a compatible Z Wave controller gateway that supports scheduling func...

Page 16: ...A PARTICULAR PURPOSE SHALL NOT EXCEED THE WARRANTY PERIOD PROVIDED HEREIN Some states do not allow limitations on how long an implied warranty lasts so the above limitation may not apply to you NSC SHALL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING FROM THE BREACH OF ANY WRITTEN OR IMPLIED WARRANTY Some states do not allow the exclusion or limitation of incidental or consequ...

Page 17: ...Copyright 2020 Nortek Security Control 10028238 Rev C or dial ...

Reviews: