background image

Copyright 

©

 2020 Nortek Security & Control   

21

20

    Copyright 

©

 2020 Nortek Security & Control

Setting the System Mode

Figure 20. 

Setting the System Mode

System Modes

• 

Off*:

 System is off. No heating or cooling will come on. If system was on, it will turn off 

immediately.

• 

Heat:

 Only heating will occur.

• 

Cool:

 Only cooling will occur.

• 

Auto: 

Heating  or  cooling  will  activate  according  to  the  heating  and  cooling  setpoints.  The 

system will automatically switch between heating and cooling modes as needed to maintain 

the setpoints. 

* = Default

Special Heat Pump Mode: Emergency Heat

An additional system mode, “Heat-E” for Emergency Heat will be displayed if the HVAC System Type 

is set to 

Heat Pump

. If there is a compressor failure with the Heat Pump system, setting the mode 

to 

Emergency Heat

 will allow the supplemental Aux Heat to activate first whenever there is a call 

for heating. It also disables the compressor output to prevent further damage to the HVAC system.

CAUTION!

 

Emergency Heat

 should only be used for emergencies until the HVAC 

system can be repaired . Running the system in 

Emergency Heat

 mode is commonly 

the most expensive mode since only the electric heat strips are being used instead of 

the more efficient heat pump compressor. 

Setting the Heating or Cooling Temperature Setpoint

To change the setpoint, touch the 



  buttons.  The  screen  will  switch  to  the  setpoint  change 

screen, and show the current setpoint of the current heating or cooling mode. Adjust the setpoint 

temperature up or down with the 



 buttons.

Note:

 

When in the Setpoint Change screen, pressing the 

MODE

 button will switch the setpoint being 

displayed between the 

Heating*

 and 

Cooling

 setpoints.

* = Default

Figure 21. 

Accessing Setpoints

Figure 22. 

Setpoint Change Screen

Automatic Setpoint Push

The cooling setpoint cannot be set below the heating setpoint. The thermostat will “push” the heating 

setpoint lower if the cooling setpoint is set below the current heating setpoint. A three (3) degree 

separation is maintained between the heating and cooling setpoints. The same is true for raising the 

heating setpoint above the cooling setpoint. The thermostat will “push” the cooling setpoint up to 

maintain the 3 degree separation.

Frost Protection

Frost Protection

 is used to prevent rooms from being too cold. Once enabled, frost protection activates 

at 41 °F (5 °C) and stops at 47 °F (8 °C) regardless of System Mode and Heat / Cool Set Point. To activate 

the feature, go to 

Advanced Systems Settings Menu (p17).

Heat

F

65

Fan Auto

SET       70

TOUCH EITHER 

▲▼ 

BUTTON TO GO TO 
THE 

SETPOINT

 

CHANGE SCREEN

41

%

72

Select

Heat

TOUCH THE 

▲▼ 

BUTTONS 

TO SET THE 
DESIRED 

SETPOINT

RAISE SETPOINT

LOWER SETPOINT

TOUCHING THE 

▲▼ 

BUTTONS

WILL CHANGE THE SETPOINT 
1 DEGREE. TOUCH AND HOLD 
THE BUTTON TO RAMP THE 
SETPOINT

TOUCH 

FAN (Select) 

TO 

SET THE SETPOINT AND 
EXIT BACK TO THE MAIN 
THERMOSTAT SCREEN

TOUCH 

MODE

 TO

CYCLE BETWEEN THE 

HEAT SETPOINT 

OR 

COOL SETPOINT

SETPOINT CHANGING

SET TO

F

41

%

TOUCH THE 

MODE

BUTTON TO CHANGE  
SYSTEM MODE

67

Fan Auto

Heat

F

SET       70

41

%

Summary of Contents for 2GIG Z-Wave Plus

Page 1: ...N 10028238 Rev C INK BLACK PANTONE 3005 C MATERIAL 60 LB MEAD BOND SIZE 8 500 X 5 500 TOL 0 125 SCALE 1 1 FOLDING ALBUM FOLD BINDING SADDLE STITCH 72 SET 70 Fan Auto Cool F 47 User Guide 2GIG Security Automation System 2GIG Z Wave Plus Battery Powered Thermostat ...

Page 2: ...Thermostat Operation 19 Main Thermostat Screen 19 Backlight and Button Operation 19 Display 19 Staging Indicators 19 Setting the System Mode 20 System Modes 20 Special Heat Pump Mode Emergency Heat 20 Setting the Heating or Cooling Temperature Setpoint 21 Automatic Setpoint Push 21 Frost Protection 21 Setting the Fan Mode 22 Fan Modes 22 User Customization 23 User preference settings 23 Error Disp...

Page 3: ...HEATING AND COOLING TRANSFORMERS PLEASE REMOVE THE JUMPER CONNECTING RC AND RH TERMINALS FIRST AND THEN CONNECT HEATING R TO RH AND COOLING R TO RC PLEASE SEE PAGE 8 W2 HEAT STAGE 2 Typical Wiring for Heat Pump HVAC System THERMOSTAT CONNECTION C 24VAC COMMON HUM HUM W3 RH RC 24VAC POWER W1 HEAT STAGE 1 G FAN Y1 COMPRESSOR STAGE 1 Y2 COMPRESSOR STAGE 2 TYPICAL THERMOSTAT WIRING COLORS CAUTION VERI...

Page 4: ...labels not included according to the terminal markings Some installations may have additional wires not shown in the example illustration below Y1 Y2 W1 W2 O B Use the thermostat terminal names marking not the wiring color to mark the wires Remove the old thermostat base CAUTION When removing thermostat don t let the wires slip into the wall and don t let the wires touch each other If the old ther...

Page 5: ...y have one or two transformers The R wire connects differently depending on the system Single Transformer System Most HVAC systems have a single 24VAC transformer For these systems there is only one R wire that can be connected to either the thermostat s RC or RH terminal because a pre installed jumper wire connects the two terminals If installing a Standard HVAC system connect the wires from the ...

Page 6: ...e separate heating and cooling systems with their own 24VAC transformers there is an R wire from the heating system and an R wire from the cooling system For dual transformer systems connect the C wire from the cooling system to the thermostat s C terminal DO NOT CONNECT THE C WIRE FROM THE HEATING SYSTEM IMPORTANT Remove the Jumper connecting RC and RH terminals see illustration below Figure 7 Du...

Page 7: ...ction desired If the backlight is already on button touches work with the first touch Wait Mode The thermostat has a Minimum Off Time MOT delay after any heating or cooling cycle ends This delay prevents rapid heating cooling cycles and also provides short cycle protection for the system compressor This delay may be noticeable when you change a setpoint and it does not respond immediately due to t...

Page 8: ...ype for Standard HVAC systems only Gas or Electric Changeover Type available with Heat Pump setup The changeover or reversing valve is used to change from heating to cooling operation The HVAC system is either a Changeover with Cooling type O or Changeover with Heating type B Most are changeover with cooling which is the default setting For Changeover with Cooling systems select WITH COOL This is ...

Page 9: ...HID Home ID and ZNID Node ID located in the thermostat INFO screen For other specific tasks such as adding the thermostat to Scenes or Groups or deleting the thermostat from an existing network refer to the Z Wave controller instructions Removing from a Z Wave Network To remove the thermostat from the network use the following steps 1 Set your primary controller to exclude or remove mode to remove...

Page 10: ...buttons to scroll through the menu options to the desired setting Touch FAN Select to change a setting Once it begins to flash use the buttons to select the desired setting Touch FAN Select to accept the new setting flashing will stop Select MODE Done to exit the option and return to the SETUP screen Feature Description Range Test Mode Temporary shorten Minimum Run Time Minimum Off Time to 10 seco...

Page 11: ...ing off This will be Aux Stage off Threshold if 2nd Stage Heat Enable Aux Heat Enable in Heat Pump System 32 48 F 0 9 C Cool Stage 1 on Threshold Delta from Set point that stage 1 cooling start 34 45 F 1 7 C Cool Stage 1 off Threshold Delta from Set point that stage 1 cooling off 32 45 F 0 7 C Cool Stage 2 on Threshold Delta from Set point that stage 2 cooling start 36 46 F 2 8 C Cool Stage 2 off ...

Page 12: ...rent setpoint of the current heating or cooling mode Adjust the setpoint temperature up or down with the buttons Note When in the Setpoint Change screen pressing the MODE button will switch the setpoint being displayed between the Heating and Cooling setpoints Default Figure 21 Accessing Setpoints Figure 22 Setpoint Change Screen Automatic Setpoint Push The cooling setpoint cannot be set below the...

Page 13: ...play mode BACKLIGHT TIMEOUT Sets the time from last button touch that the backlight will turn OFF Range 10 30 seconds Default is 20 seconds Note Long backlight timeouts will reduce battery life SENSOR CALIBRATION Change the temperature calibration by 7 degrees Default is 0 Touch the UP or DOWN arrow buttons to change to the desired display temperature STATUS LINE Sets Status Line to Setpoints or C...

Page 14: ...the Main Screen once either battery have been removed See Battery Installation page 10 Figure 26 Error Screen Figure 27 Battery Error Display Specifications Type Programmable thermostat for 24VAC 3H 2C non heat pump or 24VAC 3H 2C heat pump systems with humidifier de humidifier support Room Temperature Measurement Temp Scale Fahrenheit Celsius user selectable Temp Range 32 122 F 0 50 C Operating T...

Page 15: ...ing Energy Heat Cool Setpoint Exit Energy Saving Mode by setting the Thermostat Mode to Off Heat Cool Auto through Z Wave Please note that Restore Default would set the Energy Heat Set Point to 72 F 22 C and Energy Cool Set Point to 80 F 26 5 C thus exiting Energy Saving Mode Scheduling Scheduling is only available for those with a compatible Z Wave controller gateway that supports scheduling func...

Page 16: ...A PARTICULAR PURPOSE SHALL NOT EXCEED THE WARRANTY PERIOD PROVIDED HEREIN Some states do not allow limitations on how long an implied warranty lasts so the above limitation may not apply to you NSC SHALL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING FROM THE BREACH OF ANY WRITTEN OR IMPLIED WARRANTY Some states do not allow the exclusion or limitation of incidental or consequ...

Page 17: ...Copyright 2020 Nortek Security Control 10028238 Rev C or dial ...

Reviews: