Remote Blower Pack
A remote blower pack is available for the RH2 Duct for applications where steam for
humidification must be introduced directly into the conditioned environment but the humidifier
must be installed in a different location.
For instructions on installing the remote blower pack, refer to the installation instructions
supplied with it.
The steam line instructions in this manual are also applicable to remote mounted blower
packs except the slope must be larger because the blower pack does not have a separate
condensate line and the maximum allowable steam line length is 4 ft (1.2 m)
Figure 24: Remote Mounted Blower Pack
Note:
The blower pack requires additional clearance see the instructions that came with it.
The steam line slope for the blower pack is 4 in. / 1 ft (10 cm / 30 cm).