Installation
Connect all controls
to terminal block A
B
A
Double Unit Control Wiring
NH-EL double units (150-200) have two low voltage terminal blocks. The units can be
configured to operate the cylinders in series or parallel from one set of control signals, or
independently from two sets of control signals. See Double Mode (NH-EL 150-200 only) on
page 56 for more information.
Parallel or Series
- One set of control signals (Double Mode = Series or Parallel) wire the
controls to terminal block A.
Figure 25: Parallel or Series Mode Control Wiring (Double Unit)
Always select Parallel operating mode when connecting both cylinders to one SAM-e. Use
separate steam distributors for each cylinder if configured for sequence operation.