is normally caused by short cycling, a restricted drain,
or back pressure. The foam, generated in these
instances, is conductive and may lead to false full
cylinder indication if the level of the foam approaches
the top of the cylinder.

BACK PRESSURE: The restriction of steam flow

caused by long steam runs, improperly sloped steam
lines, elbows changing the direction of steam flow from
horizontal to vertical without a drain leg, any plumbing
detail allowing the accumulation of condensate,
undersized steam line, improper steam distributor,
downward air flow onto the distributor causing excess
static pressure at the steam outlets, or high static
pressure ducts (not probable). To overcome excess
static pressure in the duct, a fill cup extension kit
should be used. In down flow applications, a down
flow distributor should be used, but in some cases the
fill cup extension will also be required.

RESET UNIT (HUMIDIFIER): To reset the

humidifier, the auto on/off/drain switch at the front of
the humidifier should be switch to the “Off” position for
a minimum of five seconds and then switched back to
the “On” position.

MONITORED LEG: Refers to the primary wire to

the cylinder which loops through the current sensing
devise of the main PCB. This wire is terminated at the
red cylinder plug at the cylinder.

STARTING POINT

Auto On/Off/Drain switch in “On” position - unit will
not fill:

When the on/off control circuit is made and the

“auto on/off/drain” switch is pushed to “on”, the 24 volt
holding coil of the primary contactor should energize.
The resulting magnetic pull closes the high voltage
contacts with a distinct and audible “clunk”. If the
contactor will not make, then inspect the following
while referring to the wiring diagram:

1.

Check for 24 Vac across terminals 18 and 26 on
PC board.

2.

Jumper the humidistat on external control terminal
strip. If contactor operates, then control system is
at fault.

3.

The low voltage 3 amp fuse located in the control
box could be blown.

4.

The contactor holding coil could be open or
shorted.

5.

The switch could be defective.

Recheck that the “auto on/off/drain” switch is still

at “on”. If it is, then shut off the main disconnect and
check fuses or breaker of the main disconnect. If they
are serviceable, turn power back on.

To test for a defective “auto on/off/drain” switch,

connect a wire from the fuse directly to terminal 6 on
the external controls strip. If the contactor activates,
the “on” side of the switch is defective. If the contactor
does not activate, the PC board could be defective.

If the 3 amp control fuse blows when the wire from

the fuse touches terminal 6 on the external controls
strip, contactor holding coil could be shorted. Replace
contactor if necessary.

Return wires to normal.

After the necessary components have been

replaced and the contactor pulls in, there is line
voltage to the cylinder and the control sequence can
begin.

Approximately 30 seconds after the contactor pulls

in, the fill valve coil should energize. There is also a
visible fill relay on the printed circuit board. It is the
one located farthest from the C.T. core. The points on
this relay must be touching in order for the fill valve
coil to be energized.

If the points will not touch after the built-in time

delay, then the sensor input may be interfering. To
confirm, remove the black and red sensor wires from
the terminals 6 and 10 on the PC board. Wait 30
seconds and if the fill relay points not touch, then
sensor should be replaced. If they do not touch, then
the basic PC board could be faulty. To confirm,
disconnect the red wire from terminal 18 and touch it
to terminal 14. If the fill valve coil activates then the
basic PC board should be replaced. If it still does not
activate then the fill valve coil should be replaced.

Having changed the necessary components, water

starts filling the cylinder and begins to submerge the
electrodes. Because of the high voltage across the
electrodes, the water can now conduct electricity.

Red “Change Cylinder” light on - Water at top of cyl-
inder:

This is a common occurrence on start-up. See

Start-Up and Operation section of this manual.

If the cylinder is old, it indicates end of cylinder life.

Time to replace the cylinder. See “When To Replace
The Steam Cylinder” section of this manual.

- 5 -

Summary of Contents for MES-U

Page 1: ...trode Steam Humidifiers Installation Operation Maintenance Spare Parts and Exploded Views Guide IMPORTANT Read and save this guide for future reference This guide to be left with equipment owner Form 03 111 Rev 1 ...

Page 2: ... UP AND OPERATION 2 CAPACITY ADJUSTMENT 3 CYLINDER REPLACEMENT 3 WHEN TO REPLACE THE STEAM CYLINDER 3 REMOVING THE OLD CYLINDER 3 INSTALLING THE NEW CYLINDER 4 MAINTENANCE 4 EXTENDED SHUTDOWN 4 TROUBLESHOOTING 4 TERMS USED 4 STARTING POINT 5 PHYSICAL DIMENSIONS DIAGRAM 7 WIRING DIAGRAM 8 SPARE PARTS LIST 9 EXPLODED VIEWS DIAGRAM 10 ...

Page 3: ...e materials shall be placed in the duct and or the air plenum PRINCIPAL OF OPERATION When the humidistat calls the cylinder fills to 110 of the Full Load Amperage F L A or to the top of the cylinder whichever comes first See Figure 1 If it reaches 110 F L A the water heats and boils away to a level giving 90 F L A An electronic timer uses the rate of amp fall to determine the water level The objec...

Page 4: ...rrect voltage with appropriately sized service Check that the steam distributor steam supply hose and condensate line are correctly installed and routed back to the unit Ensure that the external control humidistat is located in an area to properly sense the relative humidity to be maintained by the humidifier and that the interconnecting low voltage wires between the humidistat and the unit s cont...

Page 5: ...nit will occur automatically through the solid state control sequence CAPACITY ADJUSTMENT The MES U series of humidifiers come with adjustable capacity AC PC boards These boards have a pot labeled 20 to 100 See Figure 3 CYLINDER REPLACEMENT After an extended period of operation in accordance with life expectancy information the cylinder is completely used as indicated by the red high water sensor ...

Page 6: ...he access cover is attached with screws Access should be limited to authorized personnel only EXTENDED SHUTDOWN Before disconnecting power to the humidifier for a period of extended shutdown ALWAYS DRAIN the cylinder first Otherwise the electrodes are subject to harmful corrosion which drastically shortens the cylinder life Do NOT leave the switch in the DRAIN position indefinitely as the drain co...

Page 7: ...The switch could be defective Recheck that the auto on off drain switch is still at on If it is then shut off the main disconnect and check fuses or breaker of the main disconnect If they are serviceable turn power back on To test for a defective auto on off drain switch connect a wire from the fuse directly to terminal 6 on the external controls strip If the contactor activates the on side of the...

Page 8: ...jumper across the connection of sensor on basic PC board If fill remains on when connection is jumped then basic PC board is faulty If fill shuts off then verify primary voltage to cylinder contactor energized If primary voltage is present the high water sensor PCB is defective Unit drains continually May be caused by foaming and or back pressure or leaking drain valve Cylinder is almost empty che...

Page 9: ... 10 7 27 1 cm 17 3 43 9 cm 15 8 4 21 3 cm 10 5 26 7 cm 12 6 32 2 cm 19 4 49 3 cm 20 8 4 21 3 cm 10 5 26 7 cm 12 6 32 2 cm 19 4 49 3 cm 25 10 5 26 7 cm 10 5 26 7 cm 12 6 32 2 cm 21 3 54 0 cm 30 10 5 26 7 cm 10 5 26 7 cm 12 6 32 2 cm 21 3 54 0 cm CONFIGURATION 1 2 3 4 5 6 7 8 9 MES U MES P lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg 5 8 2 3 7 9 6 4 3 9 0 4 1 10 4 4 7 13 7 6 2 13 1...

Page 10: ...EADS BY OTHERS OR INCLUDED WITH PVC UNIT 2 LEADS FOR SINGLE PHASE 3 LEADS FOR THREE PHASE PRIMARY TERMINAL BLOCK provided with PVC unit PRIMARY POWER MES U CONTROL BOARD CURRENT TRANSFORMER CHANGE CYLINDER LAMP DRAIN VALE FILL VALVE HIGH WATER SENSOR PCB ON SWITCH OFF DRAIN 187 insulated fast on For field connection 3 AMP FUSE PRIMARY CONTACTOR 24 vac By Others ON OFF CONTROLS 24 VAC INPUT By Othe...

Page 11: ......

Page 12: ......

Page 13: ...all other warranties expressed or implied by law No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product Any further warranty must be in writing signed by an officer of THE COMPANY THE COMPANY s limited warranty on accessories not of NORTEC s manufacture such as c...

Page 14: ...er Last Replaced _________________________ MTH DAY YR _________________________ MTH DAY YR _________________________ MTH DAY YR NORTEC INDUSTRIES INC P O Box 698 826 Proctor Avenue Ogdensburg NY 13669 NORTEC AIR CONDITIONING INDUSTRIES LTD 2740 Fenton Road Ottawa ON K1T 3T7 A WMH COMPANY PRINTED IN CANADA ...

Reviews: