background image

FOAMING:

The phenomenon which can occur in

water when impurities, already in the water reach an
excess concentration as a result of boiling away pure
water and the continued boiling action agitating the
contained water. The humidifier electronics are
designed to prevent this occurrence although in
extreme cases, water will foam with little concentration
making it necessary to have the drain time of the
water, contained in the cylinder, increased. Foaming
is normally caused by short cycling, a restricted drain,
or back pressure. The foam, generated in these
instances, is conductive and may lead to false full
cylinder indication if the level of the foam approaches
the top of the cylinder.

BACK PRESSURE:

The restriction of steam flow

caused by long steam runs, improperly sloped steam
lines, elbows changing the direction of steam flow from
horizontal to vertical without a drain leg, any plumbing
detail allowing the accumulation of condensate,
undersized steam line, improper steam distributor,
downward air flow onto the distributor causing excess
static pressure at the steam outlets, or high static
pressure ducts (not probable). To overcome excess
static pressure in the duct, a fill cup extension kit
should be used. In down flow applications, a down
flow distributor should be used, but in some cases the
fill cup extension will also be required.

RESET UNIT (HUMIDIFIER):

To reset the

humidifier, the auto on/off/drain switch at the front of
the humidifier should be switch to the “Off” position for
a minimum of five seconds and then switched back to
the “On” position.

MONITORED LEG:

Refers to the primary wire to

the cylinder which loops through the current sensing
devise of the main PCB. This wire is terminated at the
red cylinder plug at the cylinder.

STARTING POINT

Auto On/Off/Drain switch in “On” position - unit
will not fill:

When the on/off control circuit is made and the

“auto on/off/drain” switch is pushed to “on”, the 24 volt
holding coil of the primary contactor should energize.
The resulting magnetic pull closes the high voltage
contacts with a distinct and audible “clunk”. If the
contactor will not make, then inspect the following
while referring to the wiring diagram:

1. Check for 24 Vac across terminals 18 and 26

on PC board.

2. Jumper the humidistat on external control

terminal strip. If contactor operates, then
control system is at fault.

3. The low voltage 3 amp fuse located in the

control box could be blown.

4. The contactor holding coil could be open or

shorted.

5. The switch could be defective.

Recheck that the “auto on/off/drain” switch is still

at “on”. If it is, then shut off the main disconnect and
check fuses or breaker of the main disconnect. If they
are serviceable, turn power back on.

To test for a defective “auto on/off/drain” switch,

connect a wire from the fuse directly to terminal 6 on
the external controls strip. If the contactor activates,
the “on” side of the switch is defective. If the contactor
does not activate, the PC board could be defective.

If the 3 amp control fuse blows when the wire from

the fuse touches terminal 6 on the external controls
strip, contactor holding coil could be shorted. Replace
contactor if necessary.

After the necessary components have been

replaced and the contactor pulls in, there is line
voltage to the cylinder and the control sequence can
begin.

Approximately 30 seconds after the contactor pulls

in, the fill valve coil should energize. There is also a
visible fill relay on the printed circuit board. It is the
one located farthest from the C.T. core. The points on
this relay must be touching in order for the fill valve coil
to be energized.

If the points will not touch after the built-in time

delay, then the sensor input may be interfering. To
confirm, remove the black and red sensor wires from
the terminals 6 and 10 on the PC board. Wait 30
seconds and if the fill relay points not touch, then
sensor should be replaced. If they do not touch, then
the basic PC board could be faulty. To confirm,
disconnect the red wire from terminal 18 and touch it
to terminal 14. If the fill valve coil activates then the
basic PC board should be replaced. If it still does not
activate then the fill valve coil should be replaced.

Having changed the necessary components, water

starts filling the cylinder and begins to submerge the
electrodes. Because of the high voltage across the
electrodes, the water can now conduct electricity.

Red “Change Cylinder” light on - Water at top of
cylinder:

This is a common occurrence on start-up. See

Start-Up and Operation section of this manual.

- 5 -

Summary of Contents for MES Electrode

Page 1: ...ectrode Steam Humidifiers Installation Operation Maintenance Spare Parts and Exploded Views Guide IMPORTANT Read and save this guide for future reference This guide to be left with equipment owner Form 07 111 ...

Page 2: ......

Page 3: ...LINDER REPLACEMENT 3 WHEN TO REPLACE THE STEAM CYLINDER 3 REMOVING THE OLD CYLINDER 4 INSTALLING THE NEW CYLINDER 4 MAINTENANCE 4 EXTENDED SHUTDOWN 4 TROUBLESHOOTING 4 TERMS USED 4 STARTING POINT 5 DIAGNOSTIC PROCEDURES TROUBLESHOOTING GUIDE 7 SOFTWARE REQUIREMENT FOR MODBUS RTU 8 PHYSICAL DIMENSIONS DIAGRAM 11 WIRING DIAGRAMS 12 SPARE PARTS LIST 14 EXPLODED VIEWS DIAGRAM 15 ...

Page 4: ...ible materials shall be placed in the duct and or the air plenum PRINCIPAL OF OPERATION When the humidistat calls the cylinder fills to 100 of the Full Load Amperage F L A or to the top of the cylinder whichever comes first See Figure 1 If it reaches 100 F L A the water heats and boils away to a level giving 80 F L A An electronic timer uses the rate of amp fall to determine the water level The ob...

Page 5: ...lative humidity location for humidifiers 5 rh 80 rh Check to see that the unit is securely mounted on a level surface with the proper drain and water supply Check for correct voltage with appropriately sized service Check that the steam distributor steam supply hose and condensate line are correctly installed and routed back to the unit Ensure that the external control humidistat is located in an ...

Page 6: ...spoon of table salt no more in a cup of water and add it to the cylinder by means of the fill cup attached to the plumbing section Open the plumbing compartment and add salt solution through cylinder outlet Excessive amounts of salt will result in erratic operation of the unit however normalization of the unit will occur automatically through the solid state control sequence CAPACITY ADJUSTMENT Th...

Page 7: ...ug on all units is for the sensor pin which always goes on the single pin offset from the others See Figure 6 4 Ensure that cylinder plugs are very snug on the pins Replace any loose fitting plugs as these may result in hazardous operation MAINTENANCE WARNING The plumbing and electrical compartments contain high voltage components and wiring The access cover is attached with screws Access should b...

Page 8: ...iring diagram 1 Check for 24 Vac across terminals 18 and 26 on PC board 2 Jumper the humidistat on external control terminal strip If contactor operates then control system is at fault 3 The low voltage 3 amp fuse located in the control box could be blown 4 The contactor holding coil could be open or shorted 5 The switch could be defective Recheck that the auto on off drain switch is still at on I...

Page 9: ...nder up into spout If the red light is not on and fill is still activated jumper across the connection of sensor on basic PC board If fill remains on when connection is jumped then basic PC board is faulty If fill shuts off then verify primary voltage to cylinder contactor energized If primary voltage is present the high water sensor PCB is defective Unit drains continually May be caused by foamin...

Page 10: ...me possible drain restrictions Check if fill valve leaks not holding supply water Back pressure may also cause very conductive water conditions Was the humidifier short cycling Check for short cycling Water conductivity too high 2 flashes in sequence Off No current detection for 30 minutes with continuous call for humidity Check water level in the cylinder should be more than full If not check fil...

Page 11: ...ill be accepted to clear if the request has not been cleared itself Set MODBUS address Change the humidifier controller s MODBUS address Range is 1 247 This setting shall be non volatile with a default setting of 1 40550 The value changes will only take effect following a hardware reset of the control board Set MODBUS Baud rate Changes the humidifier s baud rate Range is 4800 9600 and 19200 B sec ...

Page 12: ...t time the run hour counter was reset 30414 Hex value representing the number of humidifier oper additional hours since the last reset Resolution 5 minutes Maximum count 5460 Hours Example 07D0 2000 hours Firmware version The firmware version of the humidifier controller 30361 Packed BCD version 3 52 would be 0x0352 Humidifier state Describes the current state of the humidifier and it s I O s Cont...

Page 13: ...ng maximum unit capacity 100 fill off amps Unit voltage Required by the control board for current and capacity calculations 40610 Format is Hexadecimal numeration table see below Unit phase Required by the control board for current and capacity calculations 40620 Bit Allocation Single phase 1 Three phase 2 Three phase 6 electrode 4 10 Hex Value Unit Type 0 110 120 1 208 2 220 240 3 230 4 277 5 347...

Page 14: ... 11 MES ...

Page 15: ... 12 ...

Page 16: ... 13 ...

Page 17: ...ll Cup 142 1050 1 1 1 1 1 1 1 1 21 Fill Valve Assembly 1 132 1061 1 1 1 1 1 1 1 n a n a 22 Fill Valve Assembly 2 132 1062 n a n a n a n a n a n a n a 1 1 23 Fill Valve Hose Specify Length 132 8850 1 1 1 1 1 1 1 1 24 Fill Valve Spring Clamp 132 5023 2 2 2 2 2 2 2 2 25 Fill Valve Screw 145 5004 2 2 2 2 2 2 2 2 26 Fitting 1 to 3 8 149 5072 1 1 1 1 1 1 1 1 27 Fitting 3 8 to 1 4 compression 90 degree 1...

Page 18: ... 15 ...

Page 19: ...pressed or implied by law No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product Any further warranty must be in writing signed by an officer of THE COMPANY THE COMPANY s limited warranty on accessories not of Walter Meier s manufacture such as controls humidista...

Page 20: ... Equipment Ltd 2740 Fenton Road Ottawa Ontario K1T3T7 Walter Meier Climate Equipment Inc 826 Proctor Avenue Ogdensburg New York 13669 Tel 866 NORTEC 1 Fax 613 822 7964 nortec humidity com www humidity com PRINTED IN CANADA ...

Reviews: