F. 

START-UP

1. 

For heaters with a tamper-proof thermostat, to set 
temperature, disconnect the power and remove the socket 
head cap screw. Set the thermostat to the desired room 
temperature with a screw driver and replace cap screw.

2. 

For heaters with an externally adjustable thermostat, set 
thermostat to desired temperature by adjusting the dial.

NOTE:   

The thermostat temperature range is 0ºF – 100ºF 

(-18 ºC– 40ºC) with an operating differential of 5ºF – 7ºF 
(3 ºC– 4ºC).

NOTE:   

High ambient thermostat temperature range is 0ºF–158ºF 

(-18ºC–70ºC) with an operating differential of 5ºF – 7ºF 
(3 ºC– 4ºC).

3. 

Install the terminal box cover and tighten securely.

4. 

Check to ensure that all plugs, screws, and covers are 
securely in place.

5. 

Check associated electrical equipment.

6. 

Check that all wall/floor mounting bracket connections 
are tight.

7. 

Turn on the supply power.

WARNING

WARNING. 

To prevent unsafe operation of the heater 

do not exceed the maximum allowable ambient 
operating temperature of 104ºF (40ºC).

G. 

MAINTENANCE

1. 

Periodically inspect the heater installation to ensure that all 
connections, fittings, plugs, screws, covers, etc. are tight 
and free of corrosion.

2. 

Check that the reflector baffles (if required) have not moved 
upwards or downwards in relation to the heat sink.

3. 

Check the extrusions of the heater for dust and debris. 
A blast of compressed air is recommended for cleaning 
the heat sink. If air is not available, disconnect the power 
supply to the heater and when cool, wipe it down with 
a damp cloth or soft brush. Remove wire guards prior 
to cleaning.

4. 

The heat sink is anodized or painted black to ensure that 
the maximum area code temperature is not exceeded. 
After an extended period of use or in extremely harsh 
environments the anodization/paint may wear away 
leaving bare surfaces. For continued safe operation, these 
surfaces must be repainted. When repainting use only 
black high temperature resistant paint.

5. 

Except for thermostat replacement, field repair of the 
heater shall not be normally undertaken. In the event that 
the heater must be repaired, contact the factory for a 
return authorization number.

H. 

SPARE PARTS

Table 5 –  Replacement thermostats

Voltage

Thermostat Part No.

One Phase Heaters

XTKW04481

Three Phase Heaters

XTKW04483

Table 6 –  Replacement thermostats (High Ambient)

Voltage

Thermostat Part No.

One Phase Heaters

XTKW07481

Three Phase Heaters

XTKW07483

WARNING

WARNING. 

To prevent unsafe operation of the heater 

do not exceed the maximum allowable ambient 
operating temperature of 158ºF (70ºC) on high ambient 
models.

WARNING

WARNING. 

Disconnect power from the heater before 

performing any maintenance. Failure to do so can result 
in property damage, injury, or death.

CAUTION

CAUTION. 

Do not use water to clean heater.

9

 S

ta

rt-

U

p \ M

ain

te

na

nc

e \ S

pa

re P
ar

ts

Summary of Contents for XB Series

Page 1: ...nance sections Each serves a special purpose and is displayed in the format shown This symbol indicates a potentially hazardous situation which if not avoided can result in personal injury or damage to the equipment This symbol indicates a potentially hazardous situation which if not avoided may be a shock hazard This symbol indicates an imminently hazardous situation which if not avoided could re...

Page 2: ...Certification 3 B Pre Installation 3 C Installation 4 C 1 General Requirements 4 C 2 Reflector Baffles 4 C 3 Wall Mounting 6 C 4 Floor Mounting 6 D Thermostat Installation 7 E Wiring 7 F Start Up 9 G Maintenance 9 H Spare Parts 9 ...

Page 3: ...N 1 Initially inspect the heater for possible damage due to shipping and handling Claims for shipping damages shall be placed with the carrier 2 Check the heater nameplate to ensure that the heater area classification and temperature code are suitable for the hazardous area classification For details of hazardous locations with potential for explosion refer to the Canadian Electrical Code or Natio...

Page 4: ...uard rails in front of the heater if there is a possibility that moving equipment could come in contact with the heater C 2 Reflector Baffles 1 REFLECTOR BAFFLES T2D units only Refer to Figure 1 page 4 when installing reflector baffles Figure 1 Reflector Baffles Installation Table 1 Reflector Baffle Pairs per Heat Sink Heat Sink Extrusion Length of Pairs Size in mm in mm 5 1 130 0 11 8 300 1 8 203...

Page 5: ...0 9 625 244 7 125 181 8 250 210 5 125 130 17 000 432 16 375 416 11 875 300 23 625 600 23 000 584 18 500 471 30 375 772 29 750 756 15 250 640 XB3 25 000 635 10 250 260 9 625 244 13 750 349 17 125 435 5 125 130 17 000 432 16 375 416 11 875 300 23 625 600 23 000 584 18 500 471 30 375 772 29 750 756 15 250 640 XB4 33 875 860 10 250 260 9 625 244 22 625 575 26 000 664 5 125 130 17 000 432 16 375 416 11...

Page 6: ... mounting brackets C 4 Floor Mounting Step 1 Position heater face down on the floor with terminal box towards the wall Figure 6 Figure 6 Floor mounting diagram Step 2 Fasten top stabilizing bracket s and floor mounting bracket s to the unit Floor mounting brackets may be mounted in one of three orientations Figure 7 Figure 7 Install mounting bracket to heater Step 3 Lift top of unit and position h...

Page 7: ...minal housing covers are secure before powering the heater 2 Use supply wires suitable for 221 F 105 C or 302 F 150 C for high ambient XB models 3 Use approved conduit and conduit seals as required by the code for hazardous locations 4 To provide maximum protection each Norseman XB heater should be fused individually using the nearest standard fuse size which is not less than 120 of the expected l...

Page 8: ... 6060T6 XB3 6125T4A XB3 6225T3B XB3 6375T2D XB4 1150T2D Fig 4 Except XB4 6160T4A 600V XB3 3250T2D 600V use Fig 10 Fig 7 XB4 3250T2D XB4 4225T3B XB4 4375T2D XB4 6080T6 XB4 6160T4A XB4 6300T3B XB4 6450T2D XB4 6500T2D Table 4 Wiring Configuration High Ambient Part No Wiring Diagram Figure 9 1Ø 3Ø XB1 1005T4A Fig 1 XB1 1010T3C XB1 1017T3C XB1 1030T3 XB1 3047T3 XB1 6020T4A XB1 6045T3C XB2 4100T3B Fig 2...

Page 9: ... the heater for dust and debris A blast of compressed air is recommended for cleaning the heat sink If air is not available disconnect the power supply to the heater and when cool wipe it down with a damp cloth or soft brush Remove wire guards prior to cleaning 4 The heat sink is anodized or painted black to ensure that the maximum area code temperature is not exceeded After an extended period of ...

Page 10: ...int finishes except for manufacturing defects apparent within 30 days from the date of installation The Company neither assumes nor authorizes any person to assume for it any other obligation or liability in connection with the product s The Purchaser agrees that all warranty work required after the initial commissioning of the product will be provided only if the Company has been paid by the Purc...

Page 11: ...on particulière et est illustré comme suit Ce symbole indique une situation potentiellement dangereuse pouvant provoquer des blessures corporelles ou des dommages à l appareil dans l éventualité où celle ci ne pourrait être évitée Ce symbole indique une situation potentiellement dangereuse pouvant présenter un danger d électrocution dans l éventualité où celle ci ne pourrait être évitée Ce symbole...

Page 12: ...ue du radiateur afin de s assurer que la zone déterminée pour l installation du radiateur ainsi que les codes de température correspondent à la classification de zone dangereuse Pour obtenir plus de renseignements relativement aux emplacements présentant des dangers potentiels de déflagration se reporter au Code canadien de l électricité ou au Code national de l électricité 3 S assurer que la tens...

Page 13: ...5 Utiliser des grilles de protection à l avant du radiateur s il existe un risque que des équipements mobiles puissent entrer en contact avec celui ci C 2 Réflecteurs 1 Réflecteurs uniquement pour les unités T2D Se reporter à la pour effectuer l installation des réflecteurs Figure 1 Installation des réflecteurs Tableau 1 Paires de réflecteurs par dissipateur de chaleur Longueur de la pièce extrudé...

Page 14: ...32 16 375 416 11 875 300 23 625 600 23 000 584 18 500 471 30 375 772 29 750 756 25 250 640 XB2 16 125 410 10 250 260 9 625 244 7 125 181 8 250 210 5 125 130 17 000 432 16 375 416 11 875 300 23 625 600 23 000 584 18 500 471 30 375 772 29 750 756 15 250 640 XB3 25 000 635 10 250 260 9 625 244 13 750 349 17 125 435 5 125 130 17 000 432 16 375 416 11 875 300 23 625 600 23 000 584 18 500 471 30 375 772...

Page 15: ... du radiateur aux supports de montage C 4 Fixation au sol Étape 1 Placer la partie avant du radiateur sur le sol en positionnant le caisson de borne vers le mur Figure 6 Figure 6 Schéma de fixation au sol Étape 2 Fixer le s support s de fixation et de stabilisation au sol sur l unité Les supports de fixation au sol peuvent être fixés selon l une des trois positions illustrées Figure 7 Figure 7 Ins...

Page 16: ...r sous tension 2 Utilisez des câbles d alimentation adaptés à une température ambiante de 105 C 221 F ou de 150 C 302 F 3 Utiliser des conduits et des joints d étanchéité de conduit homologués conformes au code relatif aux emplacements dangereux 4 Afin d assurer une protection maximale chaque radiateur NorsemanMC XB doit être individuellement protégé par un fusible en utilisant un calibre de fusib...

Page 17: ... XB3 6375T2D XB4 1150T2D Fig 4 Sauf pour les modèles XB4 6160T4A 600V et le XB3 3250T2D 600V utiliser la figure 10 Fig 7 XB4 3250T2D XB4 4225T3B XB4 4375T2D XB4 6080T6 XB4 6160T4A XB4 6300T3B XB4 6450T2D XB4 6500T2D Tableau 4 Configuration du câblage ambience élevée Part No Schéma du câblage Figure 9 1Ø 3Ø XB1 1005T4A Fig 1 XB1 1010T3C XB1 1017T3C XB1 1030T3 XB1 3047T3 XB1 6020T4A XB1 6045T3C XB2 ...

Page 18: ... douce Retirer les dispositifs de protection avant le nettoyage 4 Le dissipateur de chaleur présente un fini peint noir ou anodisé afin d assurer que la température maximale ne dépasse pas le code de zone Après une longue période d utilisation ou en raison d une utilisation dans un environnement extrêmement rigoureux le fini peint ou anodisé peut s effriter et mettre à nu les surfaces Ces surfaces...

Page 19: ...NOTES REMARQUES ...

Page 20: ...généralité de ce qui précède une mauvaise utilisation physique chimique ou mécanique un accident une mauvaise installation du produit de mauvaises conditions de stockage ou de manipulation du produit une application inappropriée ou en défaut d alignment des pièces Aucune garantie ne s applique à la finition de peinture excepté dans le cas de défauts de fabrication apparents dans les 30 jours à com...

Reviews: