2
www.normagroup.com
NORMA
CONNECT
®
Fitting Instructions
Sealing axial tensile pipe coupling for metal pipes with Ø 26.9 - 711 mm.
T
°
C
bar
0
5
10
15
20
25
30
35
40
C
max
max
C
max
α
max
max
EPDM
NBR
-30 °C...+125 °C
Ø 26.9-168.3 mm
-20 °C...+80 °C
Ø 180-711.2 mm
-20 °C...+80 °C
Ø 26.9-711.2 mm
EPDM
NBR
Ø 26.9-711.2 mm
Ø 26.9-711.2 mm
The max. permissible pressure levels for shipbuilding and industrial applications are stated on the pipe coupling’s label.
For sprinkler and water-based extinguisher systems „VdS“: Ø
33.7-88.9 mm 16 bar,
Ø 114.3 mm 12.5 bar, Ø 139.7 mm 10 bar
EPDM
NBR
For water, air and solids.
For gases, oils and fuels.
If there is a risk of corrosion, use
bolts and bars made from stainless
steel (CrNi). To protect couplings in
the long-term, use shrink sleeves or
protection tapes.
Note:
When used in sprinkler and
water-based extinguisher systems, special flame protection
is needed. In such cases, the coupling is marked as „VdS“.
DISTANCE BETWEEN PIPE ENDS
Ø 26.9 – 33.7 mm
Ø 35.0 – 48.3 mm
Ø 54.0 – 60.3 mm
Ø 76.1 – 114.3 mm
Ø 133.7 – 711 mm
C
max
= 3 mm
C
max
= 8 mm
C
max
= 17 mm
C
max
= 25 mm
C
max
= 35 mm
AXIAL MISALIGNMENT
≤ 1 % OD, but max. 3 mm
(Rectify greater misalignment by means of angular deflection.)
ANGULAR DEFLECTION
α
2° for all Ø in all directions.
(Distance between pipe ends C
max
must be observed.)
PIPE OVALITY
≤ 2 % OD, but max. 5 mm
(Applies to two pipes of similar ovality only.)
OUTER DIAMETER DIFFERENCES
≤ 2 % OD, but max. 5 mm
The specified tolerances must not be exceeded or combined. They refer to static loads and radially rigid pipes.
A safety factor has to be included for dynamic loads such as pressure surges, external forces, etc.
(Contact manufacturer for further information.)
THE FOLLOWING INFORMATION (11-15) MUST BE OBSERVED!
Remove burrs and clean pipe ends. Damage such as scratches, cracks, etc., or coatings such as paint, rust, etc., must be
removed from the sealing lip area.
max
min
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
FGR GRIP / GRIP E / GRIP E-FP
Fitting Instructions English
11.