background image

10

chemical contaminants are detergents, bleaches, 
aerosol sprays, cleaning solvents, and a wide variety 
of commercial and household products.

 WARNING:

Combustible air must not be drawn from a 
contaminated atmosphere. Excessive exposure 
to contaminated combustion air will result in 
safety and performance related problems.

CIRCULATING AIR SUPPLY

 WARNING:

Products of combustion must not be allowed to 
enter the return air ductwork or the circulating air 
supply. Failure to prevent products of combustion 
from being circulated into the living space can 
create potentially hazardous conditions including 
carbon monoxide poisoning that could result in 
personal injury or death.

All return ductwork must be adequately sealed, 
all joints must be taped, and the ductwork must 
be secured to the unit with sheet metal screws. 
When return air is provided through the bottom 
of the unit, the joint between the unit and the 
return air plenum must be air tight.

The roof curb or cement pad on which the unit is 
mounted must provide sound physical support of 
the unit with no gaps, cracks, or sagging between 
the unit and the curb or pad.

Return air and circulating air ductwork must 
not be connected to any other heat producing 
device such as a fi replace insert, stove, etc. 

 

Doing so may result in fi re, explosion, carbon 
monoxide poisoning, personal injury, or property 
damage.

This unit is designed only for use with a supply and return 
duct. Air ducts should be installed in accordance with all 
applicable local codes and the standards of the National 
Fire Protection Association “Standard for Installation of 
Air Conditioning Systems” (NFPA 90A), and “Standard for 
Installation of Residence Type Warm Air Heating and Air 
Conditioning Systems” (NFPA 90B).

Design the ductwork according to methods described 
by the Air Conditioning Contractors of America (ACCA) 
Manual D. The ducts must be properly sized not to exceed 
0.2 inches WC pressure drop at 400 scfm per nominal 
ton of cooling capacity.

Ductwork should be attached directly to the unit fl anges 
for horizontal applications. On roof curb installations the 
ducts must be attached to the curb duct supports, not 
the unit.

It is recommended that the outlet duct be provided with 
a removable access panel. This opening should be 
accessible when the unit is installed in service and shall 
be of a size such that the smoke or refl ected light may 
be observed inside the casing to indicate the presence 
of leaks in the heat exchanger.  The cover for the opening 
shall be attached in such a manner as to prevent leaks.

If outside air is utilized as return air to the unit for ventilation 
or to improve indoor air quality, the system must be 
designed so that the return air to the unit is not less than 
50°F (10°C) during heating operation. If a combination 
of indoor and outdoor air is used, the ducts and damper 
system must be designed so that the return air supply to 
the furnace is equal to the return air supply under normal, 
indoor return air applications.

Unconditioned Spaces — 

All ductwork passing through 

unconditioned space must be properly insulated to 
minimize duct losses and prevent condensation.  Use 
insulation with an outer vapor barrier.  Refer to local codes 
for insulation material requirements.

Acoustical Ductwork — 

Certain installations may require 

the use of acoustical lining inside the supply ductwork.  
Acoustical insulation must be in accordance with the 
current revision of the Sheet Metal and Air Conditioning 
Contractors National Association (SMACNA) application 
standard for duct liners.  Duct lining must be UL classifi ed 
batts or blankets with a fi re hazard classifi cation of FHC-
25/50 or less.  Fiber ductwork may be used in place of 
internal duct liners if the fi ber ductwork is in accordance 
with the current revision of the SMACNA construction 
standard on fi brous glass ducts.  Fibrous ductwork and 
internal acoustical lining must be NFPA Class 1 air ducts 
when tested per UL Standard 181 for Class 1 ducts.

Horizontal to Down fl ow Conversion —

 The unit is 

shipped ready for horizontal duct connections.  If down fl ow 
ducts are required, the unit must be converted following 
the steps below for both the supply and return ducts.

1.  Locate the duct cap inside the duct openings and 

remove the screw holding it in place.

Summary of Contents for R6GD-X36C072

Page 1: ...agency or the gas supplier These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance Some local codes require licensed installa...

Page 2: ...eral 13 Line Voltage 14 Blower Speed 14 Electrical Data Table 15 Room Thermostat 15 SYSTEM CHECK 15 Pre Start Check List 15 START UP PROCEDURE 16 Air Circulation 16 System Cooling 16 System Heating 16...

Page 3: ...he data label This furnace is NOT to be used for temporary heating of buildings or structures under construction Equipment Check All units have been securely packaged at the point of shipment After un...

Page 4: ...Supply Entry Low Voltage Entry Gas Supply Entry 16 6 24 6 31 0 2 9 1 8 4 0 12 45 12 45 4 0 55 8 8 75 Horizontal Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing C...

Page 5: ...DIMENSIONS Continued Top View Denotes either C or X Model Number R6GD Unit Weight Shipping Weight Center of Gravity Height in inches A B C with base rails without base rails X36C072 470 480 26 5 26 5...

Page 6: ...the unit such that exhaust from the vent termination is directed into window wells stairwells under decks or in alcoves or similarly recessed areas The vent termination must not be located above any...

Page 7: ...nner as the first Again check to insure that the media is captured by the channels of the filter rack 3 Replace access cover by sliding the top edge of panel under the lip of the unit s Top Panel Secu...

Page 8: ...llation on combustible flooring or class A B or C roofing material Can be C or X B A C D E Minimum Clearances to Combustible Material Model Number Heating Input Btuh Minimum Clearances Inches Blower C...

Page 9: ...ors and liquids in the vicinity of the unit Figure 5 Ground Level Installation AIR SUPPLY FOR COMBUSTION AND VENTILATION Provisions must be made in the installation of this unit to provide an adequate...

Page 10: ...zontal applications On roof curb installations the ducts must be attached to the curb duct supports not the unit It is recommended that the outlet duct be provided with a removable access panel This o...

Page 11: ...5 66 99 980 70 75 925 74 95 875 820 785 T2 1410 49 17 1330 52 13 1250 55 47 1195 58 02 1140 60 82 1085 63 90 1030 67 31 975 71 11 T3 1525 45 46 1450 47 82 1370 50 61 1320 52 53 1270 54 59 1210 57 30 1...

Page 12: ...sure Theplugshouldbereadilyaccessibleforservice use A drip leg should be installed in the pipe run to the unit Table 4 lists gas flow capacities for standard pipe sizes as a function of length in typi...

Page 13: ...n Canada at altitudes between zero and 4500ft abovesealevel Followtheinstallationinstructions supplied with the kit for proper installation WARNING To avoid the risk of electrical shock personal injur...

Page 14: ...box Do not use gas piping as an electrical ground CAUTION To avoid personal injury or property damage make certain that the motor leads cannot come into contact with any uninsulated metal components...

Page 15: ...cted the fan only speed can be different than the heating or cooling speed If no jumper is present thecontroldefaultstothe 2 SPD modeofoperation A call for heating or cooling takes priority over fan o...

Page 16: ...st the manifold pressure remove the regulator cap and turn the adjusting screw clockwise to increase pres sure or counterclockwise to reduce pressure Replace the regulator cap after adjustments are co...

Page 17: ...eating and cooling speed selection is made by moving the leads on the blower motor terminal block The wiring diagram on the unit and in Figure 10 show the speed taps for adjusting motor speed Refer to...

Page 18: ...opper conductors only 3 Not suitable on systems that exceed 150v to ground 4 If any of the original wire as supplied with the furnace must be replaced it must be replaced with wiring material having a...

Page 19: ...perate if the over temperature limit control opens UNIT MAINTENANCE WARNING To avoid risk of electrical shock personal injury or death disconnect all electrical power to the unit before performing any...

Page 20: ...ompagnie du gaz en utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Ne jamais utiliser d...

Page 21: ...the electrical connections for tightness at the beginning of each heating and cooling season Service as necessary CAUTION Label all wires prior to disconnection when servicing controls Wiring errors c...

Page 22: ...ytheuseofaroundwirebrushattachedtoalength of high grade stainless steel cable such as drain cleanout cable Attach variable speed reversible drill to the other end of the spring cable Slowly rotate the...

Page 23: ...ble until the limit circuit closes While the limit is open the red LED will pulse at a rate of 1 blink per unit time 3 Thefurnacecontrolchecksforcontinuityacrossthe pressure switch 24 VAC If the press...

Page 24: ...n place 5 The 3 amp fuse is operational 6 The anti short cycle timer s 5 minute cycle has finished for single phase units If the unit does not operate in the heating mode be certain to check the follo...

Page 25: ...mperature F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve R6GD X48 Charging Chart Cooling 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 52...

Page 26: ...220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Temperature F Liquid Pressure psig Add refrigerant when below cur...

Page 27: ...he homeowner _________________________________ Has the Literature Package been left with the homeowner _________________________________ Minimum Clearances per Table 1 ________________ Electrical Conn...

Page 28: ...7088280 Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 02 08 O Fallon MO INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WI...

Reviews: