background image

8

See the unit wiring label for proper high and low 
voltage wiring. Make all electrical connections 
in accordance with all applicable codes and 
ordinances.

Use a separate branch electrical circuit for this 
unit. A means of electrical disconnect must be 
located within sight of and readily accessibility 
to the unit. Internally mounted circuit breakers 
are available as fi eld installed options. These 
circuit breakers can be used as an electrical 
disconnect.

The unit is shipped from the factory wired for 240 
volt transformer operation. For 208 volt operation, 
remove the lead from the transformer terminal 
marked 240V and connect it to the terminal 
marked 208V. For maximum ampacity and over 
current protection, see the unit rating plate.

Provide power supply (or supplies) for the unit in 
accordance with the unit wiring diagram, and the 
unit rating plate. Connect the line-voltage leads 
to the corresponding terminals on the contactor 
(or the circuit breaker when the fi eld installed 
circuit breaker kits are used) inside the control 
compartment. Use only copper wire for the line 
voltage power supply to this unit. Use proper code 
agency listed conduit and a conduit connector 
for connecting the supply wires to the unit and 
for obtaining proper grounding. Grounding may 
also be accomplished by using the grounding 
lug provided in the control box.

 WARNING:

The unit cabinet must have and 
uninterrupted or unbroken electrical 
ground to minimize personal injury if 
an electrical fault should occur. This 
ground may consist of electrical wire 
or approved conduit when installed in 
accordance with existing national or 
local codes.

Selecting Proper Airfl ow for Variable Speed 
Units —

 Variable speed packaged heat pump units 

are equipped with a microprocessor-controlled 
variable speed motor that is pre-programmed to 
deliver optimum airfl ow in a variety of conditions 
and system confi gurations. The packaged heat 
pump units respond directly to the thermostat 
inputs, as well as the optional humidistat (Page 
11) (If installed) and bonnet switch (Page 11) (if 
installed). During normal operation, the motor will 
gradually change speeds during start-up, shut 
down, when thermostat inputs change, and when 

the duct static pressure changes (vents closed or 
opened, fi lter clogging, etc.). The packaged heat 
pump unit is confi gured by setting the selector 
switches and removing jumper connectors as 
directed below. 

IMPORTANT! This  packaged 

heat pump unit has been designed to give 
the installer maximum fl exibility to optimize 
system performance, effi ciency, and comfort. 
Because there are so many different ways 
to set up the packaged heat pump unit it is 
important to read and follow these directions 
carefully.

Selecting the Basic Cooling/Heat Pump 
Airfl ow

— 

The basic cooling/heat-pump airfl ow 

is selected by setting switches 1 through 4 
on the thermostat input board located on the 
blower. All airfl ows for other modes of operation 
(except electric heat) are determined by this 
basic setting.

Table 1 shows the basic airfl ow values versus the 
airfl ow selector switch settings. Table 1 also shows 
the range of basic air fl ow settings recommended 
for each nominal system capacity. 

NOTE:

 The CFM values listed in the tables are 

not dependent on duct static pressure. The motor 
automatically compensates for changes in duct 
static pressure (within the limits of the motor). 

For maximum capacity and energy effi ciency, 
select an airfl ow at or near the top of the 
range for that nominal capacity. For maximum 
dehumidifi cation, select an airfl ow near the 
middle or bottom of the range for that nominal 
capacity. Additional information on humidity 
control can be found in the sections labeled 
“Humidistat” and “Delay Setting”.

NOTE:

 If coil icing is observed, the basic cooling/

heat-pump airfl ow selected may be too low. 
Double-check to be sure the setting selected is 
within the range shown in Table 1. Also check 
to be sure the system is properly charged (see 
charging charts). If icing continues to occur, raise 
the selected airfl ow one or two steps.

When operating in the heat pump mode, a higher 
basic airfl ow setting will increase the energy 
effi ciency and capacity but will also decrease 
the supply air temperature. The optional Bonnet 
Control Switch may be added to increase the 
supply air temperature in the heat-pump mode 
when the supply air temperature is below a 
comfortable level. For more details see the 
section labeled “Bonnet Control Switch”.

Summary of Contents for Q4SD-X24K

Page 1: ...oning appliances Some local codes require licensed installation service personnel for this type equipment All installations must be in accordance with these instructions and with all applicable nation...

Page 2: ...gas to a liquid 5 The blower circulates the heat throughout the home via the supply duct 6 The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat SUMMER COOLING 1 In...

Page 3: ...eat Some thermostats will include a system switch position termed EM HT or AUX HT etc This is a back up heating mode to be used only if there is a suspected problem With the system switch set to EM HT...

Page 4: ...containedintheseinstructions All electrical wiring must be made in accordance with local codes and regulations and with the National Electric Code ANSI NFPA 70 or in Canada the Canadian Electric Code...

Page 5: ...35 3 X30 455 28 0 25 5 39 0 35 3 X36 460 28 0 25 5 39 0 35 3 X42 565 29 5 26 0 43 0 39 3 X48 570 29 5 26 0 43 0 39 3 X60 580 29 5 26 0 43 0 39 3 Model Number Q4SD PPH1SD Unit Weight Center of Gravity...

Page 6: ...rdance with the standards of the National Fire Protection Association Standard for Installation of Air Conditioning Systems NFPA 90A StandardforInstallationofResidenceType WarmAirHeatingandAirConditio...

Page 7: ...er nominal ton of cooling capacity Duct work should be attached directly to the unit flanges for horizontal applications On roof curb installations the ducts must be attached to the curb hangers not t...

Page 8: ...themotorwill gradually change speeds during start up shut down whenthermostatinputschange andwhen theductstaticpressurechanges ventsclosedor opened filter clogging etc The packaged heat pump unit is c...

Page 9: ...A also provides a 60 second off delay at 50 airflow DelayB hasasinglestep30second on delayat 50 airflow Delay B also provides a 90 second off delay at 50 airflow Select the delay profile which is most...

Page 10: ...e wire entrance in the packaged heat pump unit and remove jumper connector between B1 and B2 wire switch to close on temperature rise Set the thermostat as desired near 105 F CAUTION To avoid personal...

Page 11: ...is sized properly Verifythatthethermostatiswiredcorrectly The thermostat function switch should be set to Off and the thermostat fan switch should be set to Auto Start Up Procedure Close all electrica...

Page 12: ...Note The delay no delay pin concerns compressoroperationduringdefrosts Thedefault setting is delay Reciprocating compressors should only use this setting in conjunction with an approved hard start kit...

Page 13: ...ake it necessary for evacuation and charging it should only be done by qualified trained personnel thoroughly familiarwiththisequipment Somelocal codes require licensed installation service personnel...

Page 14: ...stat E O G R Y1 INDOOR THERMOSTAT SUB BASE Green Y2 W2 C DEFROST BOARD 1 2 3 4 5 6 7 8 9 Brown Orange Accessory Heat Plug Optional Outdoor Thermostat Field Supplied O E O G R Y1 INDOOR THERMOSTAT SUB...

Page 15: ...2 67 25 7 21 2 2 95 24 5 20 6 3 26 1100 80 62 28 6 29 1 2 42 27 4 27 7 2 68 26 3 26 6 2 96 25 3 25 3 3 26 80 67 30 9 24 9 2 43 29 5 24 2 2 69 28 2 23 6 2 97 26 9 23 0 3 27 80 72 33 4 20 1 2 43 31 9 19...

Page 16: ...0 5 4 12 40 2 29 6 4 58 38 2 28 7 5 13 1400 80 62 44 4 40 6 3 72 42 6 40 1 4 13 40 7 39 3 4 60 38 8 38 3 5 14 80 67 48 0 34 0 3 78 46 0 33 1 4 19 43 9 32 3 4 66 41 7 31 2 5 21 80 72 51 6 27 0 3 84 49...

Page 17: ...0 24 3 1 58 4 52 29 6 1 90 4 57 31 9 2 03 4 59 39 4 2 48 4 67 46 9 2 90 4 74 52 2 3 20 4 79 54 5 3 32 4 81 62 0 3 72 4 89 Q4SD X60K OUTDOOR TEMPERATURE Deg F Indoor T 10 17 20 30 40 47 50 60 CFM Deg F...

Page 18: ...1 80 24 3 1 58 4 52 29 6 1 90 4 57 31 9 2 03 4 59 39 4 2 48 4 67 46 9 2 90 4 74 52 2 3 20 4 79 54 5 3 32 4 81 62 0 3 72 4 89 Q4SD X60K OUTDOOR TEMPERATURE Deg F Indoor T 10 17 20 30 40 47 50 60 CFM De...

Page 19: ...1 80 24 3 1 58 4 52 29 6 1 90 4 57 31 9 2 03 4 59 39 4 2 48 4 67 46 9 2 90 4 74 52 2 3 20 4 79 54 5 3 32 4 81 62 0 3 72 4 89 Q4SD X60K OUTDOOR TEMPERATURE Deg F Indoor T 10 17 20 30 40 47 50 60 CFM De...

Page 20: ...s 7084390 Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 08 08 708439I INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH...

Reviews: