Nordyne P6 Series /installation User Manual Download Page 12

12

Install the heater kits as directed by the in-
stallation instructions that come as part of the 
heater kit. Follow all cautions and warnings as 
directed.

START UP AND SYSTEM CHECK

Pre-Start Check List
• 

Verify that the unit is level to allow proper 
condensate drainage.

• 

Verify that there is free airfl ow to and from 
the outdoor coil and that all clearance 
requirements are met.

• 

Verify that the duct work is sealed to prevent 
air leakage. 

• 

Verify that the line voltage power leads are 
securely connected and the unit is properly 
grounded.

•   

Verify that the low voltage wires are securely 
connected to the correct leads on the low 
voltage terminal strip.

• 

Verify that all exterior panels are replaced 
and securely fastened.

• 

Verify that the outdoor fan turns freely.

• 

Verify that the power supply branch circuit 
overcurrent protection is sized properly. 

• 

Verify that the thermostat is wired correctly. 
The thermostat function switch should be 
set to "Off" and the thermostat fan switch 
should be set to "Auto'.

Start-Up Procedure

Close all electrical disconnects to energize the 
system.

 WARNING:

If the unit is equipped with a crankcase 
heater, allow 24 hours prior to 
continuing  the start up procedures 
to allow for heating of the refrigerant 
compressor crankcase. Failure to 
comply may result in damage and could 
cause premature failure of the system. 
This warning should be followed at 
initial start up and any time the power 
has been removed for 12 hours or 
longer.

Air Circulation — Leave the thermostat system 
switch set to “Off” and set the thermostat fan 
switch to “On". The blower motor should run 
continuously. Check for air delivery at the 
register(s). Ensure that there are no obstructions 
at the registers or in the duct work. Set thermostat 
fan switch to “Auto.”

System Cooling

1.  Set the thermostat system switch to 

“Cool” and the thermostat fan switch to 
“Auto". Gradually lower the thermostat 
temperature switch below room temperature 
and observe that the blower, compressor, 
and fan energize. Check that air cooler than 
room temperature is being discharged 
at the register. Listen for any unusual 
noises. Locate the source and correct as 
needed.

2.  After allowing the unit to run for several 

minutes, set the temperature selector 
above room temperature.

 

 

- The fan and compressor cycles  

 

 

  off with the thermostat.

 

 

- The blower should also stop   

 

  

  unless fan switch is set to “ON”  

    

 

position

.

System Heating — If the unit has been equipped 
with optional electric heater kits, set the system 
thermostat switch to HEAT and set the thermostat 
fan switch to AUTO. Verify that the compressor 
and outdoor fan are not energized but that the 
blower and heaters are. Check for warm air at 
the supply registers.

UNIT MAINTENANCE

 WARNING:

To avoid risk of electrical shock, 
personal injury, or death, disconnect 
all electrical power to the unit before 
performing any maintenance or service. 
The unit may have more than one elec-
trical supply.

Refrigerant Charging — Packaged air 
conditioners are fully charged with R-410A 
refrigerant at the factory.  The system refrigerant 
charge can be checked and adjusted through 
the service ports provided on the front panel. 
Use only gauge lines which have a “Schrader” 
depression device present to actuate the valve. 
Draw a vacuum on gauge lines to remove air 
before attaching them to the service ports on 
the unit. Refrigerant charging must be done 
by qualifi ed personnel familiar with safe and 
environmentally responsible refrigerant handling 
procedures.

Summary of Contents for P6 Series /installation

Page 1: ...censed installation service personnel for this type equipment All installations must be in accordance with these instructions and with all applicable national and local codes and standards Read these...

Page 2: ...UNIT INSTALLATION 7 Ground Level 7 Rigging and Hoisting 7 Rooftop 8 AIR SUPPLY 8 Unconditioned Spaces 9 Acoustical Ductwork 9 Horizontal to Down Flow Conversion 9 Clearance 9 ELECTRICAL WIRING 9 Gener...

Page 3: ...Let it control the operation of the air conditioning system If you get chilly turn it up a degree at a time until comfort is restored 3 It takes longer for an air conditioner to cool your dwelling tha...

Page 4: ...Code ANSI NFPA 70 or in Canada the Canadian Electric Code Part 1 CSA C 22 1 Air Ducts must be installed in accordance with the standards of the National Fire Protection Association Standards for Inst...

Page 5: ...gure 2 Dimensions 1 25 Power Entry 1 75 Power Entry Capped 0 88 Control Wiring Entry 23 6 27 2 30 0 1 8 4 00 13 5 16 0 14 7 13 5 16 0 13 45 11 75 22 75 55 8 C SUPPLY RETURN 4 0 CONDENSING COIL 5 0 8 C...

Page 6: ...tor coil of this unit All return air to this unit must pass NFPA publications are available by writing National Fire Protection Association Batterymarch Park Quincy Maine 02269 Unit Location This air...

Page 7: ...Refer to local codes and restrictions for proper condensate disposal requirements UNIT INSTALLATION Ground Level When installing the unit at ground level provide a concrete mounting pad separate from...

Page 8: ...Reinforce the roof if required AIR DUCTS This unit is designed only for use with a supply and return duct Air ducts should be installed in accordance with the standards of the National Fire Protectio...

Page 9: ...and with the current revision of the National Electric Code NFPA 70 or in Canada CSA C 22 1 Canadian Electrical CodePart1 Ifanyoftheoriginalwireassupplied with the unit must be replaced it must be re...

Page 10: ...heorangewirecontrols cooling operation while the red wire controls heating operation 3 Verify the required speed from the airflow data found in table 1 Place appropriate wire on the appropriate motor...

Page 11: ...for 1 Stage Cool 1 Stage Heat Typical Wiring Field Supplied for 2 Stage Cool 2 Stage Heat with an Optional Outdoor Thermostat Figure 8 Typical Air Conditioner Thermostat Connections R Y1 Y2 C G 1 2 3...

Page 12: ...r delivery at the register s Ensurethattherearenoobstructions attheregistersorintheductwork Setthermostat fan switch to Auto System Cooling 1 Set the thermostat system switch to Cool and the thermosta...

Page 13: ...ers as necessary using a mild detergentandwater Rinsethoroughly with water 3 Inspect the electrical connections for tightness at the beginning of each heating and cooling season Service as necessary I...

Page 14: ...p T1 1515 1450 1380 1350 1280 1250 1200 1160 Tap T2 1580 1520 1460 1400 1300 1280 1260 1230 X60 Tap T3 1740 1690 1650 1600 1360 1500 1460 1390 Tap T4 1960 1910 1840 1820 1540 1740 1700 1600 Tap T5 209...

Page 15: ...uid Temperature F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve P6SD X60 Charging Chart Cooling 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480...

Page 16: ...RED RED RED RED ORANGE ORANGE ORANGE ORANGE ORANGE BLACK BLACK BLACK BLACK BLACK BLACK BLUE BROWN YELLOW YELLOW BLACK BLACK BK 208 230 Volt z H 0 6 e s a h P e e r h T r e n o i t i d n o C r i A d e...

Page 17: ...NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 If any of the original wire as supplied with th...

Page 18: ...H 0 6 e s a h P e l g n i S r e n o i t i d n o C r i A d e g a k c a P e l b i t r e v n o C NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not su...

Page 19: ...E RED ORANGE BLUE YELLOW BLACK RED RED RED RED GREEN GRAY BLUE YELLOW BLACK GRAY GREEN RED BLACK ORANGE GN YE STRIPE BLUE WHITE GREEN BLACK RED RED GREEN NOTES FIELD WIRING LEGEND LOW VOLTAGE HIGH VOL...

Page 20: ...7089330 7089330 Specifications and illustrations subject to change without notice and without incurring obligations 10 08 O Fallon MO INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE H...

Reviews: