1.2 Steam nozzle
1.3 Fitting the humidifier
Positioning the humidifier
For smaller outputs of up to 4 kg/h, we offer a steam nozzle which can
be either fitted in air ducts, for instance, or used for direct room
humidification. The rules for vaporisation lines (lines needed to mix
the steam adequately with air) must be observed here, too.
When the steam nozzle is employed, the length of the steam hose
should not exceed 1.5 metres.
All installation work must be performed by trained personnel.
The customer himself is responsible for verifying their qualifications.
When fitting the humidifier, use only the material supplied with the unit
and observe the various minimum distances that have been stipulated.
To open the humidifier, turn the screw, using the correct screwdriver,
in an anti-clockwise direction; the door to the water componentry or the
electrics then opens. To close, simply push back into place (no screwing
down is necessary).
Ensure that there is sufficient room to perform servicing
and maintenance work, and that the unit is easily accessible.
To facilitate such work, mount the unit at eye level.
We recommend that you fit the humidifier as near as
possible to the steam-distribution pipes. The highest degree of
efficiency is attained when the humidifier is linked to the
steam-distribution pipe by the shortest possible steam hose.
When installing the double units sizes 64 and 90 kg/h next to
each other, ensure that each drainage pipe is fed to a funnel of
adequate size.