NORDAC START (SK 135E / SK 175E) – Users Manual for Motor Starters
40
BU 0135 en-4118
2.3.2 Electrical connection of power unit
NOTICE
EMC Interference to the environment
This device produces high frequency interference, which may make additional suppression measures necessary
in domestic environments (
Section 8.1 "Electromagnetic compatibility (EMC)").
The use of shielded motor cables is essential in order to maintain the specified radio interference suppression
level.
When the device is being connected, please note the following:
1. Ensure that the mains supply provides the correct voltage and is suitable for the current required
(
Section 7 "Technical data").
2. Ensure that suitable electrical fuses with the specified nominal current range are installed between
the voltage source and the device.
3. Mains cable connection: to terminals
L1
-
L2/N
-
L3
and
PE
(depending on device)
4. Motor connection: to terminals
U
-
V
-
W
A 4-core motor cable must be used if the device is being wall-mounted As well as
U
-
V
-
W
,
PE
must
also be connected. If present, in this case the cable shielding must be connected to a large area of
the metallic screw connector of the cable gland.
The use of wire end rings is recommended for connecting to PE.
Information
Connection cables
Only use copper cables with temperature class 80°C or equivalent for connection. Higher temperature classes are
permissible.
When using
wiring sleeves
, the maximum connection cross-section can be reduced.
Device
Cable Ø [mm²]
AWG
Tightening torque
Size
rigid
flexible
[Nm]
[lb-in]
1 … 2
0.5 … 10
0.5 … 10
20-6
1.2 … 1.5
10.62 … 13.27
Table 6: Connection data
2.3.2.1 Mains supply (L1, L2, L3, PE)
No special fuses are required at the mains input side, nor is the use of a motor protection switch
required. It is advisable to use normal mains fuses (see technical data) and a main switch.
Device data
Permissible mains data
Type
Voltage
Power
3 ~ 230 V
3 ~ 400 V
SK…340-B
400 VAC
≥ 0.25
kW
X
X
Connections
L1/L2/L3
L1/L2/L3
Isolation from or connection to the mains must always be carried out for all the poles and
synchronously (L1/L2/L3).
It is advisable to use a fuse module of type SK CU4-FUSE (
Section 3.2 "Optional modules").
Permissible network types
Size 1
devices can in principle be operated in
TN/TT
networks, as well as in
IT
networks. With
operation in an
IT
network, compliance with the EMC limit value class B cannot be ensured under the
Summary of Contents for NORDAC START Series
Page 1: ...BU 0135 en NORDAC START SK 135E SK 175E Users Manual for Motor Starters...
Page 4: ...NORDAC START SK 135E SK 175E Users Manual for Motor Starters 4 BU 0135 en 4118...
Page 111: ...8 Additional information BU 0135 en 4118 111 8 1 4 EU Declaration of Conformity...
Page 119: ...Key word index BU 0135 en 4118 119...
Page 120: ...6071302 4118...