1.8 USS
– Frequency inverter settings
BU 0050 GB-3111
Subject to technical amendments
55
Parameter
Setting value / Description / Note
Comments
P546 (P)
Function Bus setpoint 1
(Function of bus setpoint 1)
0 ... 7 (47)
{ 1 }
In this parameter, a function is assigned to the delivered setpoint 1 (SW1) for bus control.
NOTE:
Further details can be found in the respective FI manual or in the description of P400.
SK 300E, SK 700E SK 750E
0 =
Off
1 =
Setpoint frequency (16 bit)
2 =
16 Bit setpoint position
(only
POSICON SK700/750E
)
3 =
32 Bit setpoint position
(only
POSICON, SK700/750E
and if
PPO- type 2 or 4 are selected)
4 =
Control terminals
POSICON (
only
POSICON, SK700/750E
, 16Bit)
5 =
Setpoint position (16 Bit) increment
1
(only
POSICON, SK700/750E
)
6 =
Setpoint position (32 Bit) increment
1
(only
POSICON, SK700/750E
)
7 =
Bus IO In Bits 0-7
SK 500E
0 =
Off
1 =
Setpoint frequency (16 bit)
2 =
Torque current limit (P112)
3 =
Actual frequency PID
4 =
Frequency addition
5 =
Frequency subtraction
6 =
Current limit (P536)
7 =
Maximum frequency (P105)
8 =
Actual PID frequency limited
9 =
Actual PID frequency monitored
10 =
Torque servo mode (P300)
11 =
Lead torque (P214)
12 =
Reserved
13 =
Multiplication
14 =
PI process controller actual value
15 =
PI process controller setpoint
16 =
PI process controller lead
17 =
Digital In bits 0...7
18 =
Reserved
19 =
Set relay (P434/441/450/455=38)
20 =
Set analog output (P418=31)
21 =
Setpoint position Low word
(SK 530E and above)
22 =
Setpoint position High word
(SK 530E and above)
23 =
Setpoint position increment Low word
(SK 530E and above)
24 =
Setpoint position increment High word
(SK 530E and above)
25 =
... 45 reserved
46 =
Setpoint torque process controller
47 =
Gearing transfer factor
NOTE:
For
SK 540 and SK545E
5 setpoints are available. These are all set in parameter
P546, which is divided into 5 array elements for this purpose. Parameters P547
and P548 are not required for this inverter version.
[-01] =
Bus setpoint 1
[-02] =
Bus setpoint 2
[-03] =
Bus setpoint 3
[-04] =
Bus setpoint 4
[-05] =
Bus setpoint 5
P547 (P)
Function Bus setpoint 2
(Function of bus setpoint 2)
except SK 54xE
0 ... 46 (47)
{ 0 }
In this parameter, a function is assigned to the delivered setpoint 2 (SW2) for bus control.
0 =
Off
1 =
Setpoint frequency
2 =
Torque current limit (P112)
3 =
Actual frequency PID
4 =
Frequency addition
5 =
Frequency subtraction
6 =
Current limit (not SK 300E)
7 =
Maximum frequency (not SK 300E)
8 =
Actual PID frequency limited
9 =
Actual PID frequency monitored
10 =
Torque (not SK 300E)
11 =
Torque lead (not SK 300E)
12 =
Control terminals
POSICON
(not
SK 300E)
13 =
Multiplication (not SK 300E)
14 =
PI process controller actual value
15 =
PI process controller setpoint
16 =
PI process controller lead
17 =
Digital In bits 0...7
18 =
Curve travel calculator (not SK 300E)
19 =
Set relay
20 =
Set analog output
21 =
Setpoint position Low word
(SK 530E and above)
22 =
Setpoint position High word
(SK 530E and above)
23 =
Setpoint position increment Low word
(SK 530E and above)
24 =
Setpoint position increment High word
(SK 530E and above)
25 =
... 45 reserved
46 =
Setpoint, torque process controller
(not SK 300E)
47 =
Gearing transfer factor (only SK 500E)