NORDAC BASE (SK 180E / SK 190E) – Users Manual for Frequency Inverters
94
BU 0180 en-4118
61 =
R rotor ident
the rotor resistance determined by measurement ((P220) Function 2)
62 =
L stray stator ident
the stray inductance determined by measurement ((P220)
Function 2)
63 =
L stator ident
the inductance determined by measurement ((P220) Function 2)
65 =
Reserved
P002
Display factor
(Display factor)
S
0.01 ... 999.99
{ 1.00 }
The selected operating value in parameter P001 >Select of display< is multiplied with the scaling
factor in P000 and displayed in >Operating parameter display<.
It is therefore possible to display system-specific operating such as e.g. the throughput quantity
P003
Supervisor code
(Supervisor code)
0 ... 9999
{ 1 }
0 =
The supervisor parameters and groups P3xx/P6xx are not visible, otherwise all.
1 =
All parameters are visible, except groups P3xx and P6xx.
2 =
All parameters are visible, except group P6xx.
3 =
All parameters are visible.
4 =
... 9999, only parameters P001 and P003 are visible.
Information
Display via NORDCON
If parameterisation is carried out with the NORDCON software, the settings 4 ... 9999 the
settings are as for the 0 setting. Settings 1 and 2 behave like setting 3.
5.2.2 Basic parameters
Parameter
{factory setting}
Setting value / Description / Note
Supervisor
Parameter
set
P100
Parameter set
(
Parameter set)
S
0 ... 3
{ 0 }
Selection of the parameters sets to be parameterised. 4 parameter sets are available. The
parameters to which different values can also be assigned in the 4 parameter sets are known as
"parameter set-dependent" and are marked with a
"P"
in the header in the following descriptions.
The operating parameter set is selected using appropriately parametrised digital inputs or by
means of BUS actuation.
If enabled via the keyboard (SimpleBox, ControlBox, PotentiometerBox or ParameterBox), the
operating parameter set will match the settings in P100.
P101
Copy parameter set
(Copy parameter set)
S
0 ... 4
{ 0 }
After confirmation with the OK / ENTER key, a copy of the parameter set selected in P100
>Parameter set< is written to the parameter set dependent on the value selected here
0 = Do not copy
1 = Copy actual to P1
: Copies the active parameter set to parameter set 1
2 = Copy actual to P2
: Copies the active parameter set to parameter set 2
3 = Copy actual to P3
: Copies the active parameter set to parameter set 3
4 = Copy actual to P4
: Copies the active parameter set to parameter set 4
Summary of Contents for SK 180E Series
Page 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Page 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Page 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Page 211: ...Key word index BU 0180 en 4118 211...
Page 212: ...6071802 4118...