09/06/2018 27
BI903
Load Management Connection
If this system is being interfaced to a dual fuel or off-peak rate. Make the connection as shown
below.
Note:
The LMC circuit is a powered circuit and must be connected to a dry contact. If an
external power source is connected to this circuit, intermittent operation or circuit board
failure can be expected.
Flow Switch Hookup
This NorAire does NOT include a system flow switch. If one is required, it must be added in the
field. Connect as shown below. NOTE: J4 jumper must be removed.
Safety Flow Switch Option
The standard IDU does not come with an interlocking flow switch. The control board has a hookup
provision for this kit. The compressor has high pressure protection if there is no water flow, but if there is
no water flow during defrost and the ODU has an extended defrost time, it is feasible the heat exchanger
coax coil could freeze and be damaged.
Optional kit is 6027-75
Connect the two wires to the spade tab labeled “FLOW” (T4) and any C tab
In addition, there is a jumper above the “FLOW” tab labeled J4, this must be pulled off
Summary of Contents for EB-HPH Series
Page 3: ...09 06 2018 1 BI903 ...
Page 5: ...09 06 2018 3 BI903 Basic System Overview ...
Page 7: ...09 06 2018 5 BI903 Product Configurator ...
Page 8: ...09 06 2018 6 BI903 Specification Table ...
Page 9: ...09 06 2018 7 BI903 Dimensional Drawing ...
Page 11: ...09 06 2018 9 BI903 Installation Overview ...
Page 17: ...EB HPH 03 17 17 1 of 1 BC909 02 ...
Page 18: ...09 06 2018 16 BI903 ...
Page 22: ...09 06 2018 20 BI903 Circuit Board Layout ...
Page 24: ...09 06 2018 22 BI903 ...
Page 35: ...09 06 2018 33 BI903 ...
Page 36: ...09 06 2018 34 BI903 ...
Page 37: ...09 06 2018 35 BI903 ...
Page 38: ...09 06 2018 36 BI903 ...
Page 39: ...09 06 2018 37 BI903 ...
Page 40: ...09 06 2018 38 BI903 ...
Page 41: ...09 06 2018 39 BI903 ...
Page 42: ...09 06 2018 40 BI903 ...
Page 43: ...09 06 2018 41 BI903 ...
Page 46: ...09 06 2018 44 BI903 Troubleshooting General Operation ...
Page 49: ......
Page 50: ......