Nokeval 2022Setp User Manual Download Page 3

INSTALLATION

Connectors

 

6

 

5

 

4

 

3

 

2

 

1

 

2022Setp

 

+V

 

Com

 

+24V

 

+mA

 

!

 

2W

 

6

5

4

3

2

1

OUT

V

Com

mA

6

5

4

3

2

1

SERIAL

A

R

S

-485

R

S

-232

B

TxD

Com

RxD

6

5

4

3

2

1

REL2

1

2

6

5

4

3

2

1

REL3

1

2

3

9

8

7

Power

supply

+L

-N

Slot A = 2022Setp input card
Slot B = Analog output (or other option card)
Slot C = The second option card

An active milliamp signal is connected to A5+ and
A3-. A two-wire transmitter may be connected to
A6+ and A5-. Voltage signal is brought to
terminals A1+ and A3-. 

Note that slot A

connectors 3 and 4 must always be linked
together!

If a pre-fuse is used in 230V power supply
connection, it should be at least T500mA. The
indicator has an internal pre-fuse. The polarity of
the power supply has no matter.

Jumpers

on

o

ff

on

o

ff

on

o

ff

Term

Fs

Te
rm

Fs

Te
rm

Fs

RS232

RS485

(Factory setting)

RS485

Last unit on bus

2000-RS

on

o

ff

Ter

m

Fs

Configuration

Using front panel

The indicator can be fully configured using the
front panel keys. The configuration settings are
explained in chapter Settings, and using the front
panel is described in chapter User interface.

The indicator keeps measuring and updating the
alarms, but the serial output is not available.

Using configuration software

MekuWin program (free from Nokeval web site) is
used to configure the device using RS-232 or RS-
485 communication. If connection fails, check the
communications settings using front panel keys to

match those in MekuWin. The settings are
described in chapter Settings / Serial
communications, and the MekuWin program has a
manual of its own.

The Slot parameter in Mekuwin is used to select
which “slot” or card is configured. 0=Master
(setpoint), 1=slot A (input), 2=slot B (output),
3=slot C.

The indicator keeps measuring during the
configuration, and the MekuWin monitor function
can be used to see the current readings.

3

Summary of Contents for 2022Setp

Page 1: ...1 Setpoint unit 2022Setp USER MANUAL 5 8 2008 V1 3 Nokeval...

Page 2: ...nce 1 1 Mohms Physical range 0 12 V Calibr accuracy 5 mV Linearity 2 mV Tempco 100 ppm C Analog output card Galvanic isolation Yes shared with serial communication and another output card mA output Ma...

Page 3: ...t unit on bus 2000 RS on off Term Fs Configuration Using front panel The indicator can be fully configured using the front panel keys The configuration settings are explained in chapter Settings and u...

Page 4: ...ble sample points e g 4 112 mA corresponds to 0 bar and 16 501 mA corresponds to 6 bar This is set up in slot A configuration menu The reading is put available on internal channel 1 to be available fo...

Page 5: ...to show the setpoint by pressing or v for the time specified in the settings The setpoint can then be adjusted The display is returned to input display when no buttons is pressed for a while The indic...

Page 6: ...ons are shown Save to keep the settings made and Undo to discard all the changes Select Save or Undo and push Finally exit from the slot selection by third or select another slot with v and so on Moni...

Page 7: ...again you can exit with The password consists of six keypresses using all the buttons Setpoint Mode Operation mode as described in chapter User interface Normal mode Normal Displaying channel number r...

Page 8: ...Monitor menu The monitor menu has only one item Mainch which tells which internal channel is currently being displayed 8...

Page 9: ...the input reading 2 Two point scaling Input signal Mea1 in mA or V is converted to scaled reading Sca1 in any engineering units and Mea2 is converted to Sca2 Linear interpolation and extrapolation is...

Page 10: ...first point in output scaling The reading Rdg1 in engineering units produces physical output Out1 in mA or V Rdg2 Out2 The other point in output scaling Linear interpolation and extrapolation is appl...

Page 11: ...unt It tells the number of serial commands processed After 255 it will roll over to 0 Serial commands Serial communications is based on Nokeval SCL protocol There is a separate manual SCL manual avail...

Page 12: ...tes when the input reading goes above setpoint 5 and deactivates at setpoint 4 The alarm also activates when the input reading goes below setpoint 5 and deactivates at setpoint 4 From The channel that...

Page 13: ...Monitor menu The monitor menu has only one item Alarms It tells the state of the alarms 0 no alarms 1 alarm1 2 alarm2 4 alarm3 and any sum of these Can be locked to manually test the relays 13...

Page 14: ...14 Nokeval Yritt j katu 12 37100 Nokia Finland Tel 358 3 3424800 Fax 358 3 3422066 www nokeval com...

Reviews: