5.- ELECTRICAL CONNECTIONS STANDARDS.
The electrical installation must fulfil the international standards
CEI 64-8. According to this standards, electrical appliances must be
installed following the below indications at bathrooms and WC:
1.- zone 0: Installation is totally forbidden at this area. It is also forbidden
at zone 1 if it is a prefabricated shower cabin.
2.- zones 1 and 2: IPX4 appliances with a wire which allows connections
1,2 m from shower vertical and with an additional RCS switch.
3.- zone 3: IPX1 appliances allowed.
4.- The earth connection of the water heaters is compulsory.
We recommend the installation of the water heaters at zone 3
(fig.- 5).
Fig. – 5
0.6m
0.6m
2.4m
b) Shower
Zone 1
Zone 2
Zone 3
Zone 0
Zone 1
Zone 2
Zona3
2.25m
Zone 0
Zone 1
Zone 2
Zone 3
2.25m
Zona0
Zone 1
Zone 2
Zone 3
0.6m
2.4m
2.4m
0.6m
2.4m
0.6m
a) Bath tube front view
a) Bath tube
b) Shower without shower plate