Wiring diagram of parallel system for Garun 30KL, 40KL

Wiring diagram of parallel system for Garun 60KL, 80KL

2.5. Software installation

For optimal computer system protection, install UPS monitoring software 

from 

https://www.power-software-download.com/viewpower.html

.

3.1. Initial operation

  Step 1.

  Before operation, make sure that the two strings of batteries are 

connected correctly  in order     of ”+,GND,-” terminals and the breaker of the 

battery pack is at “ON” position (only for long-run model).

  Step 2.

  Press the   

POWER

 button to set up the power supply for the 

UPS. UPS will enter to power on mode. After initialization, UPS will enter to 

“No Output mode”.

3.2. Screen description

After initialization, the LCD will display main screen. 

There are five sub-menus: Control, measure, setting, information and data log. 

Touch any sub-menu icon to enter into the sub-screen.

Operations

3

Main

Control

Measure

Setting

Info

Data Log

ON/OFF UPS

ON/OFF charger

Battery test

Mute all

Measure 1

Measure 2

Measure 3

Save setting

General

Advance

Basic 1

Basic 2

Electrical

Battery

Miscellaneous

Electrical

Battery

Miscellaneous

UPS self-test

SYS parameter

Install info

VOL CALLI

CURR CALLI

Initial

Data log

Parameters

Calibration

EEPROM

Touch

User

Maintainer

Basic info

Rated info

Parameter info

User mode 

Password: 0000

Maintaner mode 

Password: ****

Summary of Contents for Garun Series

Page 1: ...OUT UPS UP33TOP110KGAAZ01B UP33TOP115KGAAZ01B UP33TOP120KGAAZ01B UP33TOP130KGAAZ01B UP33TOP140KGAAZ01B UP33TOP160KGAAZ01B UP33TOP180KGAAZ01B Before using this product carefully read all product docum...

Page 2: ...contents 1 Safetyand EMC instructions 5 1 1 Transportation and storage 5 1 2 Preparation 5 1 3 Installation 5 1 4 Connection warnings 6 1 5 Operation 7 1 6 Standards 7 2 Installation and operation 8...

Page 3: ...nnect grounding earthing wire to the external UPS battery cabinets or appropriate grounding terminals The UPS can be installed only by qualified maintenance personnel An appropriate disconnect device...

Page 4: ...arning labels should be placed on all primary power switches installed in places away from the unit to alert the electrical maintenance personnel of the presence of a UPS in the circuit The label will...

Page 5: ...e they have been designed to provide maximum protection during transportation and storage 2 2 Wiring terminal view 1 RS 232 communication port 2 USB communication port 3 Emergency power off function c...

Page 6: ...el Diagram 6 Garun 60KL Front view with door open Diagram 4 Garun 40KL Rear panel Diagram 7 Garun 80KL Front view with door open Diagram 8 Garun 60KL 80KL Dual Input Output terminal Diagram 5 Garun 30...

Page 7: ...and efficiency The cable for Garun 20KL should be able to withstand over 40A current It is recommended to use AWG10 or thicker wire for Phase and AWG 6 or thicker wire for Neutral for safety and effic...

Page 8: ...the battery pack is correct Pay high attention to the polarity marking on external battery terminal block And make sure the correct battery polarity is connected Wrong connection may cause permanent...

Page 9: ...PS UPS will enter to power on mode After initialization UPS will enter to No Output mode 3 2 Screen description After initialization the LCD will display main screen There are five sub menus Control m...

Page 10: ...PS when UPS is off It will show Turn off UPS when UPS is on Touch YES to turn on or off the UPS Then the screen will return to main screen Touch Back to return to main screen immediately or No to canc...

Page 11: ...r 3 2 3 Measure screen Touch the icon to enter measure page Touch the icon or to browse information Touch the icon to return to main screen Touch the icon to go back to previous menu Measure screen pa...

Page 12: ...ion of the UPS It s not related to any function parameter ADVANCE It s required to enter password to access to the ADVANCE setting There are two types of authority User and Maintainer SAVE SETTING Thi...

Page 13: ...f the main screen Mode Mute UPS status mode alarm enable disable If Mode Mute is activated it will show icon on the top right corner of the main screen Advance Advance Password Page It s required to e...

Page 14: ...t the bypass voltage range L Low voltage point for bypass The setting range is 176V 209V H High voltage point for bypass The setting range is 231V 264V Bypass FREE Range Set the bypass frequency range...

Page 15: ...fter confirming the pop up screen Restore Delay Min UPS will automatically restart in setting minutes after the UPS shuts down New Password Set up new password to enter ADVANCE User menu Advance Maint...

Page 16: ...re are twelve options 2A 4A 6A 8A 10A 12A 14A 16A 18A 20A 22A 24A BATT Number The total number of installed battery It should be restart UPS after setting The setting range is 16 20 16 is default sett...

Page 17: ...tput voltage calibration VOL CALI Page3 Inverter VOL Inverter voltage calibration Bypass VOL Bypass voltage calibration CURR CALI CURR CALI Page Output CURR Output current calibration NOTE Each click...

Page 18: ...ge INITIAL PARAMETERS page PARAMETERS After pressing the confirmation window it will pop up as shown in above screen Touch YES to restore default value Touch Back or No to cancel this operation and ba...

Page 19: ...30V and 240V Output Rated FRE Select output rated frequency 50Hz The output frequency is setting for 50Hz 60Hz The output frequency is setting for 60Hz CVCF Mode Constant voltage and constant frequenc...

Page 20: ...om Rated output voltage 5V to Rated output voltage 11V Rated output voltage 5V is default setting H High voltage point for ECO mode The setting range is from Rated output voltage 5V to Rated output vo...

Page 21: ...et User password will restore default setting value NO After NO is set the UPS will cancel this operation UPS Selftest UPS Selftest Page This function is only effective when UPS type setting is HV The...

Page 22: ...set in Basic Setting Basic Information Page2 SYS Install Date The date of system installation BAT Install Date The date of battery installation PAR State The information of parallel state PAR ID The U...

Page 23: ...ery mode BATT Warning Voltage HIGH High battery warning voltage LOW Low battery warning voltage Shutdown Voltage If battery voltage is lower this point UPS will automatically shut down Battery Age It...

Page 24: ...Then set the line input breaker at ON position At this time the fan is running and the UPS enter to power on mode for initialization several seconds later UPS operates in Bypass mode and supplies pow...

Page 25: ...uickly once every sec to remind users that the battery is at low level and the UPS will shut down automatically soon Users could switch off some non critical loads to disable the shutdown alarm and pr...

Page 26: ...UPS with a multi meter Calibrate the inverter output voltage by configuring inverter voltage adjustment Refer to SETTING VOL CALI screen in LCD menu until the inverter output voltage difference of ea...

Page 27: ...emaining UPS according to the previous section Before turning on the parallel system to activate inverter make sure that all unit s maintenance switch at the same position When parallel system is turn...

Page 28: ...re 41 Over temperature 78 LCD MCU communication failed 42 DSP communication failure 3 7 Warning Code Warning code Warning event Warning code Warning event 01 Battery unconnected 21 Line situations are...

Page 29: ...move excess loads from UPS output and restart it Troubleshooting 4 Problem Possible cause Solutions Fault code is shown as 14 15 16 17 18 or 19 The UPS shut down automatically because short circuit oc...

Page 30: ...place batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and the ground is present before maintenanc...

Page 31: ...ems EU Declaration of Conformity We manufacturer importer declare that the products UPS Garun Series UP33TOP110KGAAZ01B UP33TOP115KGAAZ01B UP33TOP120KGAAZ01B UP33TOP130KGAAZ01B UP33TOP140KGAAZ01B UP33...

Page 32: ...Memo Memo...

Page 33: ......

Reviews: