Miscellaneous
Miscellaneous setting page
Auto Restart:
Enable: After “Enable” is set, once UPS shutdown occurs due to low
battery and then utility restores, the UPS will return to line mode.
Disable: After “Disable” is set, once UPS shutdown occurs and the utility
restores, the UPS will not automatically turn on.
Shutdown Delay Min:
UPS will shut down in setting minutes. The countdown
will start after confirming the pop-up screen.
Restore Delay Min:
UPS will automatically restart in setting minutes after the
UPS shuts down.
New Password:
Set up User new password to enter “ADVANCE
►
User”
menu page.
DefaultUserPassword:
YES: After “YES” is set, User password will restore default setting value.
NO: After “NO” is set, the UPS will cancel this operation.
•
UPS Selftest
UPS Selftest Page
This function is only effective when UPS type setting is “HV”. Therefore,
please disconnect all loads and utility first before executing this function.
Then, please change UPS type to “HV”. For the detailed operation, please
check “System Parameter” menu under Advance-Maintainer directory.
After changing UPS type to “HV”, you have to restart the UPS. After the UPS
is restarted, please enter Advance screen and enter Maintainer password. It
will show “UPS SELFTEST” selection in the screen. In the screen, all tested
items are shown “unknown”. Simply click “UPS SELFTEST” button, the UPS
will start self-test. If the UPS is normal, it will show “Normal” in all columns.
Otherwise, “Unknown” will be displayed in the columns.