pmm5111a0600p_01
5 / 32
3.
TECHNICAL DATA
Type
PMM-5-
-
Pt100 RTD: -199 ºC...+800 ºC
Thermocouple: J, T, K, L, N, B, R, S, C, Pt Rh
-240 ºC...+2320 ºC
Current: (DC) 4-20 mA, 0-20 mA
Sensor,
or analogue input
Voltage: (DC) 0-50 mV, 10-50 mV,
0-5 V, 1-5 V, 0-10 V, 2-10 V
Input resistance
Pt100 RTD: >10 MOhm,
Current input (20 mA): 5 Ohm
Voltage input (10 V): 47 kOhm
Input
Other data
Input Sampling rate: 4 / sec
Digital Input Filter time constant: 0.5...100 sec
Pt100 Sensor Current: 150 µA
Isolated from all outputs (except SSR driver)
Relay
Max. 3 pcs., SPDT (Single pole double throw) 240 V AC, 2A, AC11
SSR
Max. 2 pcs., SSR (Solid State Relay) driver, 0-10 V DC / 20 mA
Analogue DC
4-20 mA, 0-20 mA / 500 Ohm max.
0-5 V, 0-10 V, 2-10 V/500 Ohm min.
Short-circuit protected
Accuracy: ±0.25 %
Reinforced safety isolation from the input and other outputs
Transmitter power
supply
19-28 V DC not regulated, Nominal value: 24 V DC / 22mA,
Reinforced safety isolation from the input and other outputs
Out
puts
Serial communication
RS485 MODBUS RTU, Address range: 1-255, Bit rate: 1200-19200 Baud
Features Operation
range
Resolution
Proportional Bands (P)
0.5-999.9%
0.1 %
Derivative Time Constant (D)
0 - 100 min
1 sec
Integral Time Constant (I)
1 sec - 100 min
1 sec
Cycle Times
0.5 sec - 512 sec
binary steps
ON/OFF Differential
0.1% - 10 % of input span
0.1 %
Controls:
ON / OFF
P, PD, PI, PID, Dual PID
AT
AUTO / MANUAL
Cooling / Heating
Deadband/Overlap
-20 % ...+20 % of input span
0.1 %
Process Value (PV): 4 digit, red, height of characters: 10 mm
7-segment LED
display
Set Value (SV): 4 digit, green, height of characters: 8 mm
Indicati
on
LED
Operation modes:
Select mode, configuration
Automatic Tune
Alarms
Over-range indication
Under-range indication
Configuration
With press buttons of the front panel from -1999 to +9999 range
Measurement accuracy
±0.1% of range ±1LSD, Thermocouple: ±0.1% of full range span ±1LSD
Linearization accuracy
Better than ±0.2°C any point, any 0.1°C range ( ±0.05°C typical). Better than ±0.5°C any point,
any 1 °C range
Temperature stability
0.01% of range/°C change in ambient temperature
Sensor break protection
Process Control outputs turn OFF within two seconds
In case of analogue input: applicable for 4 to 20mA, 1 to 5V and 2 to 10V ranges only
Cold junction compensation
> ±1 ºC
Wire compensation
3-wire Pt100, automatic
100-240 V AC 50/60 Hz 7.5 VA
Power supply
20-48 V AC 50/60 HZ 7.5 VA; 22-65 V DC 5 W
Electrical connection
Screw type terminals
Memory protection
Data stored in EEPROM
Electrical protection
Class II.
Ingress protection
Front panel: IP66 Back panel: IP20
Ambient temperature
0 ºC…+55 ºC
Storage temperature
-20 º…+80 ºC
Relative humidity
Max. 85%
Dimensions
48 x 48 x 110 mm
Mass
~0.25 kg