11.3.2
W
ORD
P
ARAMETERS
MODBUS PARAMETER
NUMBER MODE
CONTROLLING
PARAMETER
NOTES
1
RO
Process Variable
Current value of PV
If under-range = 62976,
If over-range = 63232
2
R/W
Setpoint
Value of currently selected setpoint.
Target setpoint if ramping.
3
R/W
Output Power
0% to 100% for single output; -100%
to +100% for dual output control.
Read Only if not in manual control
4
RO
Deviation
Difference between Process Variable
and Setpoint (value = PV-SP)
5 R/W
Secondary
Proportional
Band
Adjustable 0.0% to 999.9% of input
span. Read only when Self-Tuning
6 R/W
Primary
Proportional
Band
Adjustable 0.0% to 999.9% of input
span. Read only when Self-Tuning
7
R/W
Direct / Reverse Acting
1 = Direct Acting,
0 = Reverse
8
R/W
Automatic Reset Time
(or Loop Alarm Time)
Integral Time Constant value. (or Loop Alarm Time
value in ON/OFF control mode if Loop Alarm
Enabled)
Read only if Self-Tuning.
Modbus range: 0 to 5999
9
R/W
Rate
Derivative Time Constant value. Read only if Self-
Tuning.
Modbus range: 0 to 5999
10
R/W
Output 1 Cycle time
0.5, 1, 2, 4, 8, 16, 32, 64,128, 256 or 512 seconds
11
R/W
Scale Range Lower
Limit
Lower limit of scaled input range
selectable between-1999…+9999
12
R/W
Scale Range Upper
Limit
Upper limit of scaled input range
selectable between-1999…+9999
13
R/W
Alarm 1 Value
Alarm 1 active at this level
14
R/W
Alarm 2 Value
Alarm 2 active at this level
15
R/W
Manual Reset
Bias value. 0% to 100% for single
control output or
-100% to +100% for dual outputs
16
R/W
Overlap / Deadband
20% to +20% of
(
+
)
Negative value = Deadband,
Positive value = Overlap
17
R/W
ON - OFF Differential
0.1% to 10.0% of input span
Used for Primary output on/off
differential and for combined Primary
and Secondary on/off differential.
18
R/W
Decimal Point Position
0 = xxxx, 1 = xxx.x, 2 = xx.xx, 3 = x.xxx
Read only if not Linear Input
19
R/W
Output 2 Cycle Time
0.5, 1, 2, 4, 8, 16, 32, 64,128, 256 or 512 seconds
20
R/W
Primary Output Power
Limit
Safety power limit; 0 to 100 %
21
RO
Actual Setpoint
Current (ramping) value of selected setpoint
22
R/W
Setpoint Upper Limit
Maximum setpoint value. Current SP to Input
Range Maximum
23
R/W
Setpoint Lower Limit
Minimum setpoint value. Current SP to Input
Range Minimum
24
R/W
Setpoint Ramp Rate
0 = OFF, 1 to 9999 increments / hour.
Dec Point position as for input range.
25
R/W
Input Filter Time
Constant
0 to 100 seconds
26
R/W
Process Value Offset
Modified PV = Actual PV + PV Offset. Limited by
Scale Range Maximum and Scale Range
Minimum
-999…+999