NIVELCO NIPRESS DD-400 User Manual Download Page 9

ddc4f52a0600p_01   9 / 17 

6. PROGRAMMING 

 

6.1 CONFIGURATION 

 

 

The status of the outputs is indicated by 2 LEDs. 
The LEDs will light up when the respective point has 
been reached, and the contact is active. The green 
LED 1 is on if switching point 1 is reached and the 
switch output 1 is active. The yellow LED 2 lights up 
when switching point 2 is reached, and the switch 
output 2 is active (optional). 

Regardless of the number of PNP switches, the menu structure is the same for all device types. They differ 
only in the number of menu items. Following the chart (6.5) and the menu list (6.6) they guide you through 
all possible menu items. 
The 4-digit 7-segment display shows the measured value and provides information about the menu items. 
The two buttons below the display are for moving in the menu and setting the parameters. 

Button “ ”: 

moves forward in the menu system or increases the displayed value. 

Button “ ”: 

moves backwards in the menu system or decreases the displayed value. 

Pressing the two buttons simultaneously:

 pressing both buttons at the same time changes between 

display mode and configuration mode and confirms the menu items and values. 
When setting the values, the counting speed can be increased by holding down the up or down key for more 
than 5 seconds. 
The menu navigation is a wrap-around system scrolling both forward and backward through the individual 
set-up menus to the desired item. 
Changes take effect only after pressing the two buttons together and leaving the menu item. 
All settings are stored permanently in an EEPROM so settings will not be forgotten even after disconnecting 
from the supply voltage. 

6.2 PASSWORD 

The menu system of the device can be protected by a password, so it is only possible for authorized persons to change the settings. If password access ("PAon") is 
activated, the entire menu system will be locked. For more information, see "6.6 Description of the Menu System." Entering the password will make the entire menu 
accessible again, and the password can be changed in the special menu item 4. If the password is lost or forgotten, restore the factory default settings of the device.  
Use the special menu item 2 to do so. 

 

 

Summary of Contents for NIPRESS DD-400

Page 1: ...ddc4f52a0600p_01 1 17...

Page 2: ...ddc4f52a0600p_01 2 17...

Page 3: ...AFE USE 6 4 INSTALLATION 7 4 1 INSTALLATION INSTRUCTION 7 5 WIRING 8 5 1 EXAMPLES OF ARRANGEMENTS 8 6 PROGRAMMING 9 6 1 CONFIGURATION 9 6 2 PASSWORD SYSTEM 9 6 3 CONFIGURATION EXAMPLE OF THE ANALOGUE...

Page 4: ...transmitters are suitable for the measurement of pressure difference between gases and fluids in the 0 70 bar 0 1015 psi pressure range 2 ORDER CODE NOT ALL COMBINATIONS POSSIBLE NIPRESS D D 4 5 Meas...

Page 5: ...ainless steel 1 4404 316L Housing PA 6 6 Polycarbonate Output 4 20 mA 3 wire 1 or 2 PNP switching output Switching output Short circuit protected PNP output max 125 mA Adjustable switching delay betwe...

Page 6: ...L CONDITIONS OF SAFE USE Make sure the installation is complete with no visible defects before turning on the device The device may only be used within the limitations specified in the technical speci...

Page 7: ...housing is grounded to suppress electronic noise If the grounding of the device is correct no further grounding is needed otherwise the instrument must be grounded Positioning the display The display...

Page 8: ...d and twisted multicore cable for the electrical connection Wiring diagram M12x1 5 pin metal pin configuration Electrical connection M12x1 5 pin Power supply 1 Power supply 3 3 wire signal 2 Switching...

Page 9: ...he two buttons simultaneously pressing both buttons at the same time changes between display mode and configuration mode and confirms the menu items and values When setting the values the counting spe...

Page 10: ...log signal 0 bar 0 psi 4 00 mA 3 bar 43 5 psi 12 00 mA 6 bar 87 psi 20 mA If the value is changed from 0 to 1 in ZP and the EP value from 6 to 5 the output signal changes as follows 1 bar 14 5 psi 4 0...

Page 11: ...ddc4f52a0600p_01 11 17 6 5 STRUCTURE OF THE MENU SYSTEM...

Page 12: ...signal s value Menu 7 Excess value message Set On or Off Menu 8 Switch output selector S1 P1 P2 the switching point reacts to the static pressure at the appropriate input or DIFF difference pressure...

Page 13: ...al to the analog output if P1 or P2 is selected the analog output follows the static pressure on the suitable input By the setting DIFA DIFB and DIFC the analog output follows the calculated differenc...

Page 14: ...ll scale differs from the real full scale value in the application compensation is only possible with an appropriate reference source if the deviation of the measured value is within the defined limit...

Page 15: ...the power supply and the applied supply voltage at the device Output signal slightly offset The diaphragm of the sensor is severely contaminated Cleaning with non aggressive cleaning solutions soft b...

Page 16: ...s or pressurized air for cleaning the diaphragm Before returning the device for repairs it must be cleaned carefully the parts in contact with the medium that might contain harmful substances must be...

Page 17: ...ddc4f52a0600p_01 17 17...

Reviews: