4. INSTALLATION 

With the mounting bracket the transmitter can be mounted on smooth surfaces or walls. The mounting bracket is screwed onto the plastic housing of the transmitter. 
Remove the blind caps and use the screws. The use of a sealing armature is required for the device to be replaced during operation. A simple ball valve is suitable for 
lower pressures; higher pressures (above 6 bar) require a three-way blow-off valve. The pressure ports of the device are marked. Make sure that the higher pressure 
is connected to the input “P+”, the lower pressure is connected to the input “P-” pressure port! 

 

4.1 INSTALLATION INSTRUCTION 
Install the device only in a depressurized and disconnected state! 

The medium may be dangerous; therefore, suitable protective clothing, gloves, and goggles are required for the installation process. 
Remove the packaging and the protective cap just before the beginning of the assembly to avoid any damage to the diaphragm. Keep the protective cap! In case the 
unit is not installed immediately, the protective cap must be put back on as soon as possible! Treat any unprotected diaphragm with utmost care, as it can be damaged 
very easily. 
Torque must only be transmitted to the hexagonal screw on the instrument body (torque wrench). When installing the device, avoid applying strong mechanical stress 
on the pressure port! It will result in a shift of the characteristic curve or damage the device. 
The transmitter housing is grounded to suppress electronic noise. If the grounding of the device is correct, no further grounding is needed, otherwise the instrument 
must be grounded. 
 

Positioning the display: 

The display and the operating module can be rotated for easy readability even in unusual mounting positions. The pivoting of the module is limited. Do not rotate the 
display beyond the rotation limits. 

Tightening torques:  

¼" BSP: max. 20 Nm; ½" BSP: max. 50 Nm; 
¼" NPT max. 30 Nm; ½" NPT max. 70 Nm; 

The specified tightening torques must not be exceeded! 
Installation steps for BSP process connection (DIN 3852): 
Do not use any additional sealing material such as Teflon tape! 

Check if the O-ring is intact, its surface even and clean and seat in the designated groove 

accurately. Screw the device into the correct thread by hand! If your device is to be secured with a knurled ring instead of a hexagon head screw, the pressure 
transmitter should only be tightened by hand! Devices with hexagon head screw mounting must be tightened using a suitable open-end wrench (torque wrench)!

  

Do not use any additional sealing material such as Teflon tape! 

Check if the O-ring is undamaged, its surface is flawless and clean and it is seated in the designated 

groove. Screw the device into the correct thread by hand! If your device is secured with a knurled ring instead of a hexagonal screw, the pressure transmitter must 
only be tightened by hand! Devices with hexagonal screw mounting must be tightened using an open-ended wrench (torque wrench)!

 

Installation steps for NPT process connection: 

Use suitable seal (e.g. a PTFE-strip)! Screw the device into the correct thread by hand, and tighten it with a wrench!

 

Summary of Contents for NIPRESS DD-400

Page 1: ...ddc4f52a0600p_01 1 17...

Page 2: ...ddc4f52a0600p_01 2 17...

Page 3: ...AFE USE 6 4 INSTALLATION 7 4 1 INSTALLATION INSTRUCTION 7 5 WIRING 8 5 1 EXAMPLES OF ARRANGEMENTS 8 6 PROGRAMMING 9 6 1 CONFIGURATION 9 6 2 PASSWORD SYSTEM 9 6 3 CONFIGURATION EXAMPLE OF THE ANALOGUE...

Page 4: ...transmitters are suitable for the measurement of pressure difference between gases and fluids in the 0 70 bar 0 1015 psi pressure range 2 ORDER CODE NOT ALL COMBINATIONS POSSIBLE NIPRESS D D 4 5 Meas...

Page 5: ...ainless steel 1 4404 316L Housing PA 6 6 Polycarbonate Output 4 20 mA 3 wire 1 or 2 PNP switching output Switching output Short circuit protected PNP output max 125 mA Adjustable switching delay betwe...

Page 6: ...L CONDITIONS OF SAFE USE Make sure the installation is complete with no visible defects before turning on the device The device may only be used within the limitations specified in the technical speci...

Page 7: ...housing is grounded to suppress electronic noise If the grounding of the device is correct no further grounding is needed otherwise the instrument must be grounded Positioning the display The display...

Page 8: ...d and twisted multicore cable for the electrical connection Wiring diagram M12x1 5 pin metal pin configuration Electrical connection M12x1 5 pin Power supply 1 Power supply 3 3 wire signal 2 Switching...

Page 9: ...he two buttons simultaneously pressing both buttons at the same time changes between display mode and configuration mode and confirms the menu items and values When setting the values the counting spe...

Page 10: ...log signal 0 bar 0 psi 4 00 mA 3 bar 43 5 psi 12 00 mA 6 bar 87 psi 20 mA If the value is changed from 0 to 1 in ZP and the EP value from 6 to 5 the output signal changes as follows 1 bar 14 5 psi 4 0...

Page 11: ...ddc4f52a0600p_01 11 17 6 5 STRUCTURE OF THE MENU SYSTEM...

Page 12: ...signal s value Menu 7 Excess value message Set On or Off Menu 8 Switch output selector S1 P1 P2 the switching point reacts to the static pressure at the appropriate input or DIFF difference pressure...

Page 13: ...al to the analog output if P1 or P2 is selected the analog output follows the static pressure on the suitable input By the setting DIFA DIFB and DIFC the analog output follows the calculated differenc...

Page 14: ...ll scale differs from the real full scale value in the application compensation is only possible with an appropriate reference source if the deviation of the measured value is within the defined limit...

Page 15: ...the power supply and the applied supply voltage at the device Output signal slightly offset The diaphragm of the sensor is severely contaminated Cleaning with non aggressive cleaning solutions soft b...

Page 16: ...s or pressurized air for cleaning the diaphragm Before returning the device for repairs it must be cleaned carefully the parts in contact with the medium that might contain harmful substances must be...

Page 17: ...ddc4f52a0600p_01 17 17...

Reviews: