DW1401989  Rev.K2 

Dec 18, 2019 

Class B (Short circuit detection is not available) 

EOL  (10k  ohm)  is  connected  between  A+

B+

  and  A-

B-

  in 

EVA-DIP-SCI.

 

 

Dry contact switches

input switches

are OFF. 

 

 

 

 

 

 

 

 

Figure 4 

Class A (Short circuit detection is not available) 

It is a status that dry contact switches connected between A+

B+

  and A-

B-

in EVA-DIP-SCI are OFF.   

 

 

 

 

 

 

 

 

Figure 5 

Class B (Short circuit detection is available) 

EOL  (10k  ohm)  is  connected  between  A+

B+

  and  A-

B-

  in 

EVA-DIP-SCI. 

Dry contact switches are OFF. 

*Two external inputs can be connected to one input line. 

*Resistor  of  2.2k  ohms

RE-2.2k

is  an  option  and  not  included  in  this 

product.   

B-

B+

A+
A-

Lin+
Lin-
Lout+
Lout-

EOL 

10kΩ

Typical wiring for N/O contacts only

2.2kΩ

2.2kΩ

2.2kΩ

2.2kΩ

EOL 

10kΩ

Loop

-          +

TO NEXT

DEVICE

-          +

Loop

FROM PANEL OR

PREVIOUS DEVICE

Figure 6 

Class A (Short circuit detection is available) 

It is a status that dry contact switches connected between A+

B+

  and A-

B-

  in EVA-DIP-SCI are OFF. 

*Two external inputs can be connected to the input line. 

*Resistor  of  2.2k  ohms

RE-2.2k

is  an  option  and  not  included  in  this 

product.   

B-

B+

A+
A-

Lin+
Lin-
Lout+
Lout-

Typical wiring for N/O contacts only

2.2kΩ

2.2kΩ

Loop

-          +

TO NEXT

DEVICE

-          +

Loop

FROM PANEL OR

PREVIOUS DEVICE

Figure 7 

Normally Close Class B 

A dry contact switch and EOL (10k ohm) are connected in series between 

A+

B+

and A-

B-

  in EVA-DIP-SCI. 

Dry contact switches are ON. 

*Only one external input can be connected to one input line.   

B-

B+

A+
A-

Lin+
Lin-
Lout+
Lout-

Typical wiring for N/C contacts only

EOL 

10kΩ

EOL 

10kΩ

Loop

-          +

TO NEXT

DEVICE

-          +

Loop

FROM PANEL OR

PREVIOUS DEVICE

Figure 8 

 

 

 

 

 

 

 

 

 

EOL 

10kΩ

Typical wiring for N/O contacts only

EOL 

10kΩ

B-

B+

A+
A-

Lin+
Lin-
Lout+
Lout-

Loop

-          +

TO NEXT

DEVICE

-          +

Loop

FROM PANEL OR

PREVIOUS DEVICE

B-

B+

A+
A-

Lin+
Lin-
Lout+
Lout-

Typical wiring for N/O contacts only

Loop

-          +

TO NEXT

DEVICE

-          +

Loop

FROM PANEL OR

PREVIOUS DEVICE

Summary of Contents for EVA-DIP-SCI

Page 1: ...d Input LED red illuminates and the module communicates to the control panel the active status Trouble condition If an overcurrent occurs because SLC Signaling Line Circuit is shorted SCI LED yellow illuminates and the module communicates to the control panel the short status The module also communicates to the control panel the open short status of IDC depending on the Subtype Setting described b...

Page 2: ...ype depending on the wiring configuration as below The subtype is to be set through the Configurator for the control panel Sub Type Input Method Open circuit Detection Short circuit Detection Class Interrupt 1 Normally Open Yes No Class B Disabled 2 Enabled 3 Class A Disabled 4 Enabled 5 Normally Close No Yes Class B Disabled 6 Enabled 7 Normally Open Yes Yes Class B Disabled 8 Enabled 9 Class A D...

Page 3: ...rcuit detection is available It is a status that dry contact switches connected between A B and A B in EVA DIP SCI are OFF Two external inputs can be connected to the input line Resistor of 2 2k ohms RE 2 2k is an option and not included in this product B B A A Lin Lin Lout Lout Typical wiring for N O contacts only 2 2kΩ 2 2kΩ Loop TO NEXT DEVICE Loop FROM PANEL OR PREVIOUS DEVICE Figure 7 Normall...

Page 4: ...nel detects the short circuit 6 Short between terminal Lin Lout and Lin Lout and the SCI LED yellow illuminates The short circuit isolator isolates the devices connected after the short circuited area which makes these devices have no response Upon removal of the short condition the area is automatically connected to go back to the normal standby status and the SCI LED yellow turns off FOR WARRANT...

Page 5: ...s had been paid And the warranty period is three 3 years from the shipment from Nittan s factory 1 3 Notwithstanding anything to the contrary in this warranty terms Nittan shall not be liable to the customer by reason of any representation or implied warranty condition or other term or any duty at common law or under the express terms of this warranty terms for any consequential loss or damage whe...

Reviews: