ELECTRIC ACTUATOR SPECIFICATIONS
LAX type
Actuator type ( :Voltage code) LAX-030-
LAX-070-
Voltage
100 / 110 V AC ±10 % 50/60 Hz (Code: 1)
200 / 220 V AC ±10 % 50/60 Hz (Code: 2)
Thrust
[N] 300
700
Operation time
[mm/s] 0.39 / 0.47 (50/60 Hz)
0.46 / 0.55 (50/60 Hz)
Stroke
[mm] 7.5
7 to 11.5
Adjustment range
Fixed
Adjust by OPEN / SHUT trimmers
Power consumption
[VA] 4.5
11
Motor
Synchronous motor (Triac control)
Overload protection
Timer
Method of operation
Proportional control (linear motion)
Input signal
4 to 20 mA (Input resistance: 220 )
4 to 20 mA (Input resistance: 250 )
Operation
[Mode A] SHUT by decreased signal OPEN by increased signal (Standard)
[Mode B] SHUT by increased signal OPEN by decreased signal (Option: J)
Impossible to change the mode. Please appoint it at the time of the order.
Indication signal
0 mA : SHUT 1 mA : OPEN (External load resistance: less than 3 k )
Common in mode A / B
Resolution
Less than 0.2 %
Duty cycle
100 / 200 V AC : 100 %
110 / 220 V AC : 50 % 30 min.
Ambient temperature
-10 to 50 ºC
Space heater
Built in to the control board
Manual operation
Manual shaft
Enclosure
Equivalent to IP65 (IEC 60529)
Housing material
Aluminum alloy diecast (acrylic resin baking finish)
Terminal block
For bare wire 0.2 to 1.5 mm² (AWG 26 to 16) Ground terminal: M3
Conduct port
G3/8 Cable gland (for 5 to 10.5 mm cable)
WIRING
Note) • Input signal circuit is non-isolated. Do not connect DC (-) wire to other DC (-) common.
• Do not adjust operating angle of a valve (OPEN/SHUT trimmer).
Please contact us if you need to adjust operating angle.
LAX-070 only
Voltage
100/110V AC
200/220V AC
Input signal
4 to 20mA
Indication signal
0 to 1mA
Ground terminal(M3)
Trimmers
Operation
range
Potentiometer
Indication
signal
Dead band