OSPWT225-EN 

1/8 

Instruction manual 

Pneumatic Actuated Butterfly Damper WT 

SP-1474 

Please read this manual before installation and use.

GENERAL 

It composed of wafer type butterfly damper and pneumatic actuator.   
The piston incorporating wear ring prevents wear of sliding surface   
and offers superior durability.   

Actuator 

Double-acting type 

TAD   

Single-acting type 

TAO  (Airless SHUT) 

TAC  (Airless OPEN) 

Damper 

WT  type  With heat-resistant damper material this series can be used at fluid 

temperatures ranging from -40 °C to +550 (600) °C.   

PRODUCT CODE 

WT type (Without seat) 

 

      W T  9 

2  T  G 0  - 

-

 

 

(With SUS316 seat)

W T  9 

2  T  G S - 

-

(1) 

(2)  (3) (4) (5) (6) (7) (8)  

(9) 

  (10)    (11)

(1) Actuator 

TAD     
TAO     
TAC     

(2) Damper 

WT       

(3) Voltage

9 : Air 

(4) Sizing code 

0 : Standard 
1 : Light 
2 : Heavy 

(5) Connection 

2 : JIS 5K 

(6) Body material 

T : SCS13A 

(7) Packing material 

G : Expansion graphite 

(8) Seat material 

0 : (Zero) None 

S : SUS316 

(9) Size [mm] 
 

ex. 80 A ® 080 

(10) Option 

FR : Filter Regulator Unit 
LB  : Limit Switch Box 
EP : Positioner 
ES : Smart Positioner 
ER : Smart Positioner 

(11) Positioner control pattern (TAD) 

A  : SHUT by  4 mA « OPEN by 20 mA  
B  : SHUT by 20 mA « OPEN by  4 mA  

(11) Positioner control pattern (TAO) 

C  : OPEN by 20 mA « SHUT by  4 mA (Airless SHUT) 
D  : OPEN by  4 mA « SHUT by 20 mA (Airless SHUT) 

(11) Positioner control pattern (TAC) 

E  : SHUT by  4 mA « OPEN by 20 mA (Airless OPEN) 
T  : SHUT by 20 mA « OPEN by  4 mA (Airless OPEN) 

Summary of Contents for Vpro WT9 2TG0 Series

Page 1: ...seat W T 9 2 T G 0 With SUS316 seat W T 9 2 T G S 1 2 3 4 5 6 7 8 9 10 11 1 Actuator TAD TAO TAC 2 Damper WT 3 Voltage 9 Air 4 Sizing code 0 Standard 1 Light 2 Heavy 5 Connection 2 JIS 5K 6 Body mater...

Page 2: ...t None SUS316 Stem seal Packing Expansion graphite Expansion graphite PRESSURE TEMPERATURE RATING Temperature range 40 to 600 C If the fluid temperature is more than 250 C or less than 20 C option XT...

Page 3: ...erates the upper shaft of the actuator directly TAO TAC type Classification Single acting type Spring return Actuator type TAO 040 TAC 040 TAO 050 TAC 050 TAO 063 TAC 063 TAO 080 TAC 080 TAO 100 TAC 1...

Page 4: ...tioner Ex dmb II B T5 TIIS EP Smart positioner ES ER Smart positioner with 4 to 20mA output ET EU SHUT by 4 mA OPEN by 20 mA A SHUT by 20 mA OPEN by 4 mA B OPEN by 20 mA SHUT by 4 mA spring return Air...

Page 5: ...ly Open TAD SHUT by solenoid off OPEN by power to solenoid TAO Airless SHUT OPEN by power to solenoid SHUT by solenoid off Spring return TAC Airless OPEN SHUT by power to solenoid OPEN by solenoid off...

Page 6: ...rement must be taken taper boring the pipe or pipe liner etc PIPING FLANGES Gasket should be selected appropriately to suit the fluid pressure and temperature Use spring washer to prevent from decreas...

Page 7: ...sure 0 4 to 0 7 MPa Air pressure should not exceed 0 7 MPa during operation test Capacity of compressor and air tank are to be calculated by capacity of piping and air consumption A margin of 30 is re...

Page 8: ...actuator Can be used with no oil supply Confirm the air leakage Confirm the air supply pressure Confirm the dirt or grit inside of cylinder Lubrication Procedure TAD TAO TAC In case of lubricating us...