... Menu continued from previous page:
SET
Menu normally hidden
(to activate this menu, press knob for 8 secs while the Status Menu is active)
HEATING
PUMP
AUX
OFF
Auxiliary heating released for operation (for both domestic water and central heating)
[OFF, ON]
DELAY
AUX
30
m
Delaying connection of auxiliary heating gives the heat pump a better chance to meet
demand
[0..60]
RESTART
CP
30
m
Compressor restart time to prevent unnecessary wear (between two consecutive starts)
[2..60] minutes
STOP
CP
10
m
Minimum stop time for the compressor (time from stop to start)
[0..15] minutes
COMPRESS
MIN
OFF
°C
Minimum outside temperature for compressor operation. If colder, stopped compressor
and EL takes over [OFF, -25..-10] °C
COMPRESS
MAX
47
°C
Max temperature to permit compressor running. (stop to avoid pressure overload of
condenser)
[40..80] Max. Temperature is Twater (T2) for SHWt and Theat (T1) for central heating.
T SUMMER
15
°C
Level for automatic switch between summer and winter operation
[0..30]
CP LEVEL
RPM
Select compressor operating mode on/off or RPM regulation
[1 LEVEL, RPM]
STOP %
10
Compressor stop capacity
(shown only when RPM compressor level selected)
ST DIFF%
40
Compressor start difference
(shown only when RPM compressor level selected)
U MIN %
25
Minimum voltage to frequency converter
(shown only when RPM compressor level selected)
U MAX %
100
Maximum voltage to frequency converter
(shown only when RPM compressor level selected)
U START%
70
Initial voltage to frequency converter
(shown only when RPM compressor level selected)
U 60°C %
MIN
30
Compressor RPM limit in heating operation as a function of the current setting - curve
max. [MIN, OFF] (shown only when RPM compressor level selected)
U 40°C %
MIN
20
Compressor RPM limit in heating operation as a function of the current setting - curve
min. [MIN, OFF] (shown only when RPM compressor level selected)
GAIN
7
Enhancement of PI regulator (factory setting: 5 % per
℃
)
(shown only when RPM compressor level selected)
TN
3
m
PI regulator integration period (factory setting: 5 minutes)
(shown only when RPM compressor level selected)
VENT HI
50
Capacity for transfer between high/low ventilator speed
U LOW %
50
Voltage for low ventilator capacity
U HI %
100
Voltage for high ventilator capacity
CIRCPUMP
CONTIN
Select operating mode for central heating circulation pump (on/off only with buffer tank)
[CONTIN, ON/OFF]
Important:
The parameters menu HEATPMP must be set by authorized service personnel.
Parameters in gray boxes changed as required, while the other parameters should not be
changed.