Domestic hot water
Settings for hot water production have been set at the factory, but it may be necessary to adjust them to meet the exact requirements
of the user.
> Domestic hot water
*When selecting a day of the week, the legionella function will start at 1 a.m. and heat the domestic hot water to 65 °C. The function will
only work if supplementary electric heating has been activated.
> Compact P
> Supplementary electric heat
-
ing for hot water
Settings:
Standard setting:
Description:
Off / 5 85 ºC
30 ºC
Off: The supplementary electric heating is deactivated by the
user.
5 - 85 ºC: Indicates the temperature (T11) below which
supplementary electric heating is to help heat domestic hot
water.
> Day of legionella treatment
Settings:
Standard setting:
Description:
None / Mon / Tue / Wed / Thu / Fri / Sat / Sun
None
Here you indicate whether or not the unit is to run a weekly
legionella treatment *.
> Legionella temperature
Settings:
Standard setting:
Description:
50 70 ºC
65 ºC
The temperature of the legionella treatment.
> AIR
Is only shown if activated in Service settings.
> Domestic water setpoint
Settings:
Standard setting:
Description:
5 70 ºC
40 ºC
Here you indicate the desired temperature of the domestic
water. Is only shown if SHW has been selected.
> Day of legionella treatment
Settings:
Standard setting:
Description:
1 21 day(s) / Off
Off
Here you set the amount of days between each legionella treat
-
ment. Is only shown if SHW has been selected.
> Domestic water min. temp.
Settings:
Standard setting:
Description:
5 55 ºC
35 °C
If the domestic water falls below this temperature, supplemen
-
tary electric heating will start up if it has been activated. Is only
shown if SHW has been selected.