Assembly of Comfort
When mounting the Comfort-unit future service and maintenance should be considered.
For the Comfort CT300 a free place of minimum 60 cm in front of the system and 20 cm
below the system is recommended. The CT300 can be mounted directly on the wall.
In order to ease the mounting each of the connection pieces is labeled. Please notice the labels.
The connection between the unit and the ducting should be a flexible transition.
The system must be level because of the condense outlet. The condense outlet requires a mini-
mum clearance height of 11,5 cm beneath the outlet connection.
The exchanger is low-noise and low-vibration. However, potential vibrations spreading from the
system to the individual building parts must be taken into account. To detach the system from the
floor, we recommend that the system is placed on vibration absorbers. The vibration absorbers
must be placed diagonally on each corner to ensure that the system does not “fall down” from
them.
It is not necessary to re-insulate the system as it is delivered with a 20 mm standard insulation.
1 cm
Comfort
Top
4
∼
Comfort
300 /450 / 600
vibration absorbers
Figure 2: Mounting the Comfort unit