Nilan reserves the right to alter these instructions without prior notice
Page 10 af 15
IMPORTANT regarding Danfoss Actuator type AME 140:
Re-installing the actuator must be done as described below:
1. Disconnect the power supply and remove the cover of the actuator.
2. Liberate the gear by pressing down the button as the spindle is turned up (counter clock-
wise)
3. Re-install the actuator and turn on power.
4. DIP-switch nr. 1 should be moved to ON and then to OFF.
5. The actuator is automatically calibrating for up to 6 minutes.
(The LED is flashing when calibrating and is lit constantly when finished).
6. Re-install the cover of the actuator.
The actuator should be placed in an environment of 0°C to 55°C.
Technical specifications, heating surface, water
Connections: 15mm Cu-pipes for flow and return.
Maximum output for Comfort CT300 is 2,0kW at a waterflow of 0,09m
3
/h, a pressure drop of1,9kPa
at the waterside and a flow temperature of 60°C. Pressure tested to13,5Bar..
See electrical chart.
Electrical heating surface should be installed in the ducting (Ø160/Ø200). When retrofitting an elec-
trical heating surface it should be activated in the CTS 700 control panel as described in the user
guide
T7
placed after
reheating surface
.