Ecodesign data Comfort 252 Top
SEC* average climate
- 42.3 kWh/(m2.a)
SEC* cold climate
- 81.4 kWh/(m2.a)
SEC* warm climate
- 17.2 kWh/(m2.a)
SEC-Class
A+
Type
Residential ventilation unit
Type of drive
Variable speed drive
Type of heat recovery system
Recuperative (counterflow heat exchanger)
Thermal efficiency of heat recovery
91 %
Maximum flow rate
253 m3/h (100 Pa)
Electric power input of fan drive, including any motor control
equipment at maximum flow rate
77.6 W
Sound power level (LWA)
36 dB(A)
Reference flow rate
0.049 m3/s (177.1 m3/h)
Reference pressure difference
50 Pa
SPI
0.17 W/(m3/h)
Central demand control
0.85
Maximum internal leakage
1.5 %
Maximum external leakage
2.9 %
Visual filter warning
When a filter needs replacing, an alarm will be displayed on
the control panel. NB! It is important to change filters
regularly to sustain the performance and energy efficiency of
the unit.
Disassembly instructions
www.nilan.dk
* Specific energy consumption
AEC - annual electricity consumption
199 kWh/year (100 m2)
AHS** average climate
4667 kWh (100 m2)
AHS cold climate
9110 kWh (100 m2)
AHS warm climate
2106 kWh (100 m2)
** Annual heating saved
26