05-351 / 05-352 / 05-336 / 05-300
64
4.7. Table of time functions
The time function is defined with the ‘time’ rotary switch.
TIME SETTINGS:
For switch functions
For shutter/ventilator control
Times
tim
e
01
23456789A
BCDE
F
Switch-
off time T
Control
time T2
Operating
time T4
Control
time T3
Remarks
0
0
0
no limit
0
ventilator control
1
0,5’’
1,5’’
150’’
0
slow rolling blind control
2
2’’
3’’
90’’
0
rolling blind control
3
4’’
0
30’’
0
rolling blind control
4
6’’
0
15’’
0
rolling blind control
5
10’’
0
0,4’’
0
pulsed rolling blind control
6
20’’
0
no limit
1,5’’
ventilator control
7
30’’
0
150’’
1,5’’
ventilator control
8
1’
0
90’’
1,5’’
rolling blind control
9
3’
0
30’’
1,5’’
rolling blind control
A
5’
0
15’’
1,5’’
rolling blind control
B
7’
0
no limit
3’’
ventilator control
C
9’
0
150’’
3’’
ventilator control
D
15’
0
90’’
3’’
rolling blind control
E
45’
0
30’’
3’’
rolling blind control
F
120’
0
15’’
3’’
rolling blind control