1      Safety information

2      Introduction

This document covers the UL conduit box mounting instructions for 
Unidrive M100 to M400, frame size 4 drives and derivatives. 
When fitted, the drive meets the requirement for Type 1 protection 
according to UL50 and UL50E.
Type 1 enclosures are intended for indoor use only. They provide a 
degree of protection to personnel against incidental contact with the 
enclosed equipment and a degree of protection against falling debris.

The following items are supplied in the kit:

Table 2-1 Contents of the kit (CT part number: 3470-0102)

The installed conduit kit does not change the width or depth of the drive. 
However, this conduit kit will add 103 mm (4.0 in) to the height of the 
drive.
Table 2-2 shows the combined drive and conduit box dimensions.

Table 2-2 Dimensions

3      Installation

Figure 3-1 Removing the drive terminal cover

Use flat blade screwdriver to remove the drive terminal cover by 
turning the cover release 30° counter clockwise and sliding the 
cover downward (

1

).

Unidrive M100 to M400 Size 4

UL Conduit Box Installation Sheet

Follow the instructions

The mechanical and electrical installation instructions must be adhered to. Any questions or doubt should be referred to the supplier of the 
equipment. It is the responsibility of the owner or user to ensure that the installation of the drive and any external option unit, and the way 
in which they are operated and maintained, comply with any applicable legislation, regulation, and code of practice in the country in which 
the equipment is used.

Competence of the installer

The drive must be installed by qualified personnel who are familiar with the requirements for safety and EMC. The installer is responsible 
for ensuring that the end product or system complies with all the relevant laws in the country where it is to be used.

WARNING

WARNING

Description

Image

Qty

Conduit box

x 1

Conduit cover

x 1

Grounding clamp

x 3

M4 x 16 torx taptite screw

x 8

UL conduit box installation sheet

x 1

Frame

size

H

W

D

mm

in

mm

in

mm

in

4

362

14.3

115

4.5

175

6.9

Stored charge

The drive contains capacitors that remain charged to a 
potentially lethal voltage after the AC and / or DC power 
supply has been disconnected. If the drive has been 
energized, the power supply must be isolated at least ten 
minutes before work may continue.
Normally, the capacitors are discharged by an internal 
resistor. Under certain, unusual fault conditions, it is possible 
that the capacitors may fail to discharge, or be prevented 
from being discharged by a voltage applied to the output 
terminals. If the drive has failed in a manner that causes the 
display to go blank immediately, it is possible the capacitors 
will not be discharged. In this case, consult Control 
Techniques or their authorized distributor.