![Nidec SPDM CONTROL BOX User Manual Download Page 19](http://html1.mh-extra.com/html/nidec/spdm-control-box/spdm-control-box_user-manual_1687805019.webp)
SPDM CONTROL PANEL
1 – TECHNICAL DATA
NIDEC ASI S.P.A. – SPDM CONTROL PANEL USER MANUAL
IMSPDCB2EN
13
Resolution of analog inputs and outputs available for user:
Signal
I/O
Terminals
Sampling rate
Resolution
AnIn1
Differential Input
ME-34(-)/35(+)
10kHz
11 bit + sign
AnIn2
Differential Input
ME-36(-)/37(+)
AnIn3
Differential Input
ME-38(-)/39(+)
AnIn4
Differential Input
ME-40(-)/41(+)
AnOut1
Output
ME-42 / gnd ME-21
AnOut2
Output
ME-43 / gnd ME-21
AnOut3
Output
ME-44 / gnd ME-24
AnOut4
Output
ME-45 / gnd ME-24
Max current regulator bandwidth:
360 rad/s
Max speed regulator bandwidth:
60 rad/s
Protection grade:
IP20
1.4
Admissible environmental conditions
Operation: Operate drive installed in a permanent place and protected from adverse weather in accordance with IEC 721-3-3.
Ambient Temperature
0 to 40 °C.(32 to 104 °F)
Relative Humidity
5 to 95% without condensation
Contamination Levels
(Boards with coating) —
Chemical gases: IEC 721-3-3, Class 3C2
Solid particles:
IEC 721-3-3, Class 3S2
Altitude
Up to 1000 m (3280 ft) above sea level. Over 1000 m (3280 ft) above sea level, the heat dissipation
could require a forced ventilation. Maximum height 3000 m (9840 ft)
Vibrations
Max 0.3 mm/ 0.012in. (from 2 to 9 Hz), max 1 m/s2 3.28ft1s2 (from 9 to 200 Hz) sinusoidal (Class 3 M1)
Environmental
considerations
Avoid exposure to corrosive gases — including hydrogen sulfide
Avoid exposure to strong magnetic fields, nuclear radiation and high levels of RFI from
communication transmitters
Storage
Storage: Store in protective packing and in protected environment in accordance with IEC 721-3-1.
Ambient temperature
-25°C to +70°C ( -13°F to +158°F)
Relative Humidity
Max 95% at 40 °C. - Max 95% at 104 °F.
Atmospheric pressure
from 70 to 106 kPa
Vibrations
Max 1.5 mm / 0.06in. (from 2 to 9 Hz), max 5 m/s2 / 16.4 ft/s2 (from 9 to 200 Hz) sinusoidal (class 1 M3)
Shock
max 100 m/s2 ( 330fUs2 ), 11 ms ( 36fts ) (class 1 M3).
Contamination Levels
Boards with coating —
Chemical gases: IEC 721-3-1, Class 1C2
Solid particles:
IEC 721-3-1, Class 1S3
Environmental Considerations
Avoid exposure to corrosive gases — including hydrogen sulfide
Avoid exposure to strong magnetic fields, nuclear radiation and high levels of RFI from communication
transmitters