ssa
10.2
Dual SI-Applications fitted
This scenario involves two SI-Applications or MCi2x0 modules (or one of each).
Consider a drive with the following configuration:
•
Slot 1 – MCi2x0
•
Slot 2 - SI-Interbus
•
Slot 3 - SI-Applications
If a parameter read request comes over Interbus to read Pr
71.08
, this will be redirected
to the module in the lowest slot number, i.e. the MCi2x0 in slot 1. The value in _Q08%
from slot 1 will be returned.
If a parameter read request comes over Interbus to read Pr
101.08
, this will be sent
straight to the MCi2x0 in slot 1. The value in _Q08% from slot 1 will be returned.
If a parameter read request comes over Interbus to read Pr
161.08
, this will be sent
straight to the SI-Applications in slot 3. The value in _Q08% from slot 3 will be returned.
If a parameter read request comes over Interbus to read Pr
131.08
, this will be sent
straight to slot 2. As there is no appropriate module fitted in slot 2 (i.e. SI-Applications or
MCi2x0), an error message will be returned, indicating that the parameter does not
exist.
When two SI-Applications or MCi2x0 modules (or one of each) is fitted, it is advisable to
use the direct slot access parameters to ensure the correct, and intended, module is
accessed.