8.3.3.3 Service error codes
If an error occurs while accessing a parameter, a Control Techniques defined error code
will be returned. These error codes are listed in
.
Table 8-23 Control Techniques defined service error codes
8.3.4
SI-Interbus setup using non-cyclic data
The SI-Interbus can be configured using the PCP channel, CT Single Word or PPO 4
Word non-cyclic data. The configuration parameters for the slot in which the SI-Interbus
is located can be accessed using the virtual menu 60 (see
Pr 60.56 (Setup menu shortcut)
Changes made to the SI-Interbus configuration parameters will not take effect until the
SI-Interbus has been reset (see
).
A brief interruption in Interbus communications may be seen while the reset sequence is
in progress.
Error
Error Class
Error
Code
Additional Error Code
Parameter Does Not Exist
0x08
(Non-standard error)
0x01
0x00
(No additional information)
Parameter Is Read Only
0x08
(Non-standard error)
0x02
0x00
(No additional information)
Parameter Is Write Only
0x08
(Non-standard error)
0x03
0x00
(No additional information)
Value Outside Permitted
Range
0x08
(Non-standard error)
0x04
0x00
(No additional information)
Decimal Place Error
0x08
(Non-standard error)
0x05
0x00
(No additional information)
Sub-index Zero Access Error
0x06
(Access error)
0x05
0x11
(Attempt to access sub-index
zero)