3.2 Physical Installation
D2-018 ~ D2-100: Allow 100 mm (3.9 inch) between soft starters.
D2-140 ~ D2-200: Allow 200 mm (7.9 inch) between soft starters.
D2-018 ~ D2-100: Allow 50 mm (2.0 inch) between the soft starter and solid surfaces.
D2-140 ~ D2-200: Allow 200 mm (7.9 inch) between the soft starter and solid surfaces.
Soft starters may be mounted side by side with no clearance (that is, if mounted without
communications modules).
The soft starter may be mounted on its side. Derate the soft starter's rated current by 15%.
1
3
4
2
08544.
B
8
Digistart D2: User Guide
Issue: F