4.1.4  Outputs 

Main Contactor Output 

The Main Contactor output (terminals COM2, RLO2) closes as soon as the soft starter receives a start 

command and remains closed while the soft starter is controlling the motor (until the motor starts a coast 

to stop, or until the end of a soft stop). The Main Contactor output will also open if the soft starter trips. 
The Main Contactor output can be used to directly control a main contactor coil. 

 

Programmable Output 

The programmable output relay (terminals COM1, RLO1) can be used to signal either trip or run status. 

This relay is normally open. 
Trip: 

The relay closes when the Digistart D2 trips. The relay can be used to operate the shunt-trip mechanism 

of an upstream circuit breaker (in order to isolate the motor branch circuit), or to signal the trip to an 

automation system or externally. The relay will open when the trip is reset. 
Run: 

The relay operates when the soft start is complete, the bypass relays are closed and full voltage is being 

applied to the motor. The relay can be used to operate a contactor for power factor correction capacitors, 

or to signal soft starter run status to an automation system. 

 

4.1.5  Semiconductor Fuses 

Semiconductor fuses can be used with Digistart D2 soft starters to reduce the potential for damage to 

SCRs from transient overload currents and for Type 2 coordination. Digistart D2 soft starters have been 

tested to achieve Type 2 coordination with semiconductor fuses. Suitable Bussmann and Ferraz/Mersen 

semiconductor fuses are detailed below. 

 

Model 

SCR I

2

t (A

2

s) 

Ferraz/Mersen Fuse 

European/IEC Style 

(North American Style) 

Bussmann Fuse 

Square Body 

(170M) 

Bussmann Fuse 

British Style 

(BS88) 

D2-018 

1150 

6.6URD30xxxA0063 

(A070URD30xxx0063) 

170M-1314 

63 FE 

D2-034 

8000 

6.6URD30xxxA0125 

(A070URD30xxx0125) 

170M-1317 

160 FEE 

D2-042 

10500 

6.6URD30xxxA0160 

(A070URD30xxx0160) 

170M-1318 

160 FEE 

D2-048 

15000 

6.6URD30xxxA0160 

(A070URD30xxx0160) 

170M-1318 

180 FM 

D2-060 

18000 

6.6URD30xxxA0160 

(A070URD30xxx0160) 

170M-1319 

180 FM 

D2-075 

51200 

6.6URD30xxxA0250 

(A070URD30xxx0250) 

170M-1321 

250 FM 

D2-085 

80000 

6.6URD30xxxA0315 

(A070URD30xxx0315) 

170M-1321 

250 FM 

D2-100 

97000 

6.6URD30xxxA0315 

(A070URD30xxx0315) 

170M-1321 

250 FM 

D2-140 

168000 

6.6URD31xxxA0450 

(A070URD31xxx0450) 

170M-1322 

500 FMM 

D2-170 

245000 

6.6URD31xxxA0450 

(A070URD31xxx0450) 

170M-3022 

500 FMM 

D2-200 

320000 

6.6URD31xxxA0450 

(A070URD31xxx0450) 

170M-3022 

500 FMM 

 

xxx = Blade Type. Contact Ferraz/Mersen for options. 

 

Digistart D2: User Guide 

 

11 

Issue: F 

 

Summary of Contents for D2-018

Page 1: ......

Page 2: ...impacts of its manufacturing operations To this end we operate an Environmental Management System EMS which is certified to the International Standard ISO 14001 When the products eventually reach the...

Page 3: ...al Installation 5 2 Rating Data 6 2 1 Model Code 6 2 2 Current Ratings 6 3 Mechanical Installation 7 3 1 Dimensions and Weights 7 3 2 Physical Installation 8 4 Electrical Installation 9 4 1 Terminal l...

Page 4: ...ed behaviour or through incorrect operation due to a fault In any application where a malfunction of the starter or its control system could lead to or allow damage loss or injury a risk analysis must...

Page 5: ...starting immediately on first commissioning or operation after transportation always ensure that the control supply is applied before the power so that the contactor state is initialised 1 7 3 STOP f...

Page 6: ...these ratings charts AC53b 4 6 354 1000 metres AC53b 4 20 340 1000 metres 40 C 50 C 40 C 50 C D2 018 18 A 17 A 17 A 15 A D2 034 34 A 32 A 30 A 28 A D2 042 42 A 40 A 36 A 33 A D2 048 48 A 44 A 40 A 36...

Page 7: ...to models D2 140 to D2 200 while the product is energized provides protection against contact and ingress requirements of IP20 Models D2 140 to D2 200 can be installed with optional finger guards in...

Page 8: ...h between the soft starter and solid surfaces D2 140 D2 200 Allow 200 mm 7 9 inch between the soft starter and solid surfaces Soft starters may be mounted side by side with no clearance that is if mou...

Page 9: ...ee Technical Data on page 18 1 L1 3 L2 5 L3 2 T1 4 T2 6 T3 mm2 AWG CSL CSR CSH DI1 DI2 TH1 TH2 COM2 RLO2 COM1 RLO1 mm2 AWG 018 060 075 100 140 200 018 200 10427 A 10 35 8 2 10428 A 14 mm 0 55 inch 25...

Page 10: ...VAC Start Stop To reset a trip open then close DI2 Stop To reset a trip open then close DI2 Start Fuse optional For sizing of the control fuse see Technical Data on page 18 The maximum cable run is d...

Page 11: ...tomation system 4 1 5 Semiconductor Fuses Semiconductor fuses can be used with Digistart D2 soft starters to reduce the potential for damage to SCRs from transient overload currents and for Type 2 coo...

Page 12: ...shunt trip device Soft starter installed with a system protection circuit breaker and main contactor 6 T3 4 T2 2 T1 5 L3 3 L2 1 L1 COM2 RLO2 M K1 K1 08332 B M Motor three phase K1 Main contactor COM2...

Page 13: ...rent A and ramp time B Current ramp starting extends the time soft starter takes to reach the current limit and is suitable for generator set supplies loads requiring an extended start time or applica...

Page 14: ...unction Select the function of the soft starter s programmable output terminals COM1 RLO1 When set to Run the relay will operate when the soft start is complete When set to Trip the relay will operate...

Page 15: ...FWD FWD Phase sequence 08860 A Relay action The relay will close when a trip occurs Reset the trip and resume operation Phase sequence protection The soft starter will allow any phase sequence Digista...

Page 16: ...munication Failure between module and network Check network connections settings and configuration x 9 Starter Communication Failure between starter and module Remove and refit accessory module x 10 B...

Page 17: ...rotection is not adjustable and is only active when the average motor current is 50 or more of the programmed motor FLC If the soft starter frequently trips on current imbalance check that there is no...

Page 18: ...ature 10 C to 60 C Storage temperature 25 C 60 C to 70 C for less than 24 hours Humidity 5 95 Relative Humidity Pollution degree Pollution Degree 3 Vibration IEC 60068 Test Fc Sinusoidal 4 Hz to 13 2...

Page 19: ...Heat Dissipation During Start 3 watts ampere During Run 10 watts typical Approvals UL C UL UL 508 CE EN 60947 4 2 RoHS Compliant with EU Directive 2011 65 EU Digistart D2 User Guide 19 Issue F...

Page 20: ...monitoring motor current motor temperature To use Digistart Soft with the Digistart D2 the soft starter must be fitted with a USB Module Modbus Module or a Remote Operator Digistart D2 Remote Keypad...