5. Settings
Digitax SF
Instruction Manual
5. Parameters
5.
Parameters
No. 50.0
Analog velocity:
Input gain (numerator)
Range
Default
Characteristics
0 to 65,535
Maximum
Rotational
Speed
of Motor
No. 51.0
Analog velocity:
Input gain (denominator)
1 to 65,535
Function
Use
Analog velocity command Input Gain.
Set the value of a rotational speed corresponding to input voltage.
When (numerator/denominator) = 1/2, a motor rotational speed is a half of maximum command
input voltage (±10 V).
The motor rotational speed is max (±10 V) when (numerator/denominator) = 1.
By using this gain, you can adjust the position proportional gain of the host controller.
No. 52.0
Analog velocity:
CCW speed limit (numerator)
Range
Default
Characteristics
0 to 65,535
Maximum
Rotational
Speed
of Motor
No. 53.0
Analog velocity:
CCW speed limit (denominator)
1 to 65,535
Function
Use
Analog velocity command: CCW speed limit.
CCW Speed Limit = Maximum rotational speed ×
=
52.0
53.0
No. 54.0
Analog velocity:
CW speed limit (numerator)
Range
Default
Characteristics
0 to 65,535
Maximum
Rotational
Speed
of Motor
No. 55.0
Analog velocity:
CW speed limit (denominator)
1 to 65,535
Function
Use
Analog velocity command: CW speed limit.
CW Speed Limit = Maximum rotational speed ×
=
54.0
55.0
Maximum Rotational Speed of Motor
Motor Model
Maximum rotational speed
[
rpm
]
MM500, MY500,
6,000
MM101, MY101,
MX201,
MZ201,
MX401,
MZ401,
MX751,
MZ751,
MA201,
MH201,
5,000
MA401,
MH401
MA751,
MH751
4,500
MM102, MH102,
3,000
MM152, MH152,
MM202
Summary of Contents for Control Techniques Digitax-SF DA21223
Page 6: ...6 MEMO Digitax SF Instruction Manual ...
Page 23: ...17 MEMO Digitax SF Instruction Manual 1 Before Use 2 Overview ...
Page 283: ...48 MEMO Digitax SF Instruction Manual 6 Operation 5 Position Control Mode ...
Page 329: ...46 MEMO Digitax SF Instruction Manual 7 Tuning ...
Page 330: ...8 8 Troubleshooting 2 2 4 5 5 6 8 8 9 17 18 19 20 21 22 23 ...
Page 353: ...24 MEMO 8 Troubleshooting Digitx SF Instruction Manual ...