Commander S100 User Guide
7.2.5 Menu 5 - PID controller
Parameter
Range
Default
P5.01 PID Fixed Reference Set-Point 1
±100.00 %
0.00 %
P5.02 PID Fixed Reference Set-Point 2
±100.00 %
0.00 %
P5.03 PID Reference Selector
None (0), T2 Analog 1 % (1), T4 Analog 2 % (2), T15 Frequency % (3),
Up/Down % (4), Fixed Ref 1 (5), Fixed Ref 2 (6)
Fixed Reference 2 (6)
P5.04 PID Feedback Selector
None (0), T2 Analog 1 % (1), T4 Analog 2 % (2), T15 Frequency % (3)
None (0)
P5.05 PID Feed Forward Selector
None (0), T2 Analog 1 % (1), T4 Analog 2 % (2), T15 Frequency % (3),
Up/Down % (4), Fixed Ref 1 (5), Fixed Ref 2 (6)
None (0)
P5.06 PID Reference Slew Rate Limit
0.0 to 3200.0 s
0.0 s
P5.07 PID Proportional Gain
0.000 to 4.000
1.000
P5.08 PID Integral Gain
0.000 to 4.000
0.500
P5.09 PID Output Lower Limit
±100.00 %
0.00 %
P5.10 PID Output Upper Limit
0.00 to 100.00 %
100.00 %
P5.11 PID Enable Selector
None (0), Drive Running (1), At Speed (2), At Zero (3), Under Voltage (4),
External Error (5), Drive Ready (6), Drive Healthy (7), Current Limit (8),
Reverse Running (9),Current Loss (10), Threshold Detect (11)
None (0)
P5.12 Threshold Detector Selector
None (0), Ramp Input (1), Ramp Output (2), Output Frequency (3),
Output Current (4), Torque Current (5), Output Voltage (6), DC Bus Voltage (7),
T2 Analog 1 % (8), T4 Analog 2 % (9),
T15 Frequency % (10), Output Power (11), Motor RPM (12),
Percentage Load (13), PID Percentage (14), PID Error (15)
None (0)
P5.13 Threshold Detector Level
0.00 to 100.00 %
0.00 %
P5.14 Threshold Detector Hysteresis
0.00 to 25.00 %
0.00 %
P5.15 Threshold Detector Delay
±25.0 s
0.0 s
P5.16 Threshold Detector Output Invert
Off (0) or On (1)
Off (0)
P5.17 Threshold Detector Function Select
None (0), Hardware Enable (1), Run Forward (2), Run Reverse (3), Run Permit (4),
Forward Limit Switch (5), Reverse Limit Switch (6),
Up/Down % Increase (7), Up/Down % Decrease (8), Up/Down % Reset (9),
Ref Switch Bit 0 (10), Ref Switch Bit 1 (11), Ramp Select (12),
PID Enable (13), External Error (14), Drive Reset (15), Run (16), Reverse (17),
Jog Forward (18), Jog Reverse (19), Fire Mode (20)
None (0)
P5.18 PID Negative Limit Enable
Off (0) or On (1)
Off (0)