SETTINGS - FINAL POSITIONS
ASSEMBLY - SETTING
(also see fi g. 12-14)
Setting of the fi nal positions
Set the switch DIP 1 on "ON". The upper
horizontal bar of the display fl ashes.
Setting of the upper fi nal position:
with the UP and DOWN buttons in deadman
mode, move the door to the upper fi nal position
and store this position by briefl y pressing the T2
button.
It is necessary to reverse the counting
direction of the electrical transmitter if
error 6 is shown on the display and the
door blocks during movement in the UP
direction.
Set DIP switches 1 to 4 on "ON".
A small "u" appears on the display. To reverse
the counting direction, press button T2 (above
the DIP switch) and keep it pressed until the
u
turns 180° on the display.
Now put DIP switches 2, 3 and 4 on "OFF" -
return to setting the upper fi nal position.
Now the lower horizontal bar fl ashes.
Setting of the lower fi nal position:
With the UP and DOWN buttons in deadman
mode, move the door up to the lower fi nal
position and store this position by briefl
y
pressing the T2 button.
Now the central horizontal bar fl ashes.
Then put the DIP switch 1 on "OFF". Now
the lower bar remains lit, while the central bar
fl ashes.
Check fi nal positions
Move the door UP (upper fi nal position) and
DOWN (lower fi
nal position) until the lower
and central bars remain lit in the lower fi nal
position.
Now the installation mode has completed.
Precision adjustment of the upper and/or
lower fi nal position:
After having set the lower fi nal position, put the
door in the upper fi nal position by briefl y pressing
the UP button. The control unit switches off in
the fi nal position set with the EES limit switch.
If you want to move the upper fi nal position
upwards, it is necessary to set DIP switches 1, 2
and 4 on "ON" (to move it downwards, set DIP
switches 1, 3 and 4 on "ON").
A "0" appears on the display.
By briefl y or repeatedly pressing the T2 button,
a correction factor falling between 1 and 9 steps
can now be set.
Then put all of the DIP switches on "OFF".
Now the fi nal position has been corrected and
will be enabled with the next lifting. Now move
the door into the lower fi nal position by pressing
the DOWN button.
The control unit switches off in the fi nal position
set with the electronic limit switch.
If you want to move the lower fi nal position
downwards, it is necessary to set DIP switches
1, 3 and 4 on "ON" (to move it upwards, set the
DIP switches 1, 2 and 4 on "ON").
A "0" appears on the display.
By briefl y or repeatedly pressing the T2 button,
a correction factor falling between 1 and 9 steps
can now be set.
Then put all of the DIP switches on "OFF".
Now the fi nal position has been corrected and
will be enabled with the next lowering.
This operation can be repeated several times
until the lower fi nal position is perfectly adjusted.
ATTENTION!
The preliminary limit switch is automatically
set by the control unit when programming
the lower fi nal position at about 5 cm above
the lower fi nal position!!!
Partial opening setting
If you want to set a partial opening, now it is
possible to adjust the desired opening by
pressing the UP and DOWN buttons. Press the
T2 button to confi rm the position.
Now the display switches off.