Nice GDS 450LI Installation And Maintenance Manual Download Page 9

9

Control Inputs / Mode Settings

Control Inputs

The P.E, OPN and STP inputs require a normally closed switch contact and therefore should be shorted to the COM

terminal if not used.  This is done via bridging links already on the circuit board (bottom left corner) The CLS, OSC and

PED inputs require a normally open switch contact and therefore should be left unconnected if not used. All the

switch inputs of this control board including the limit switch inputs require a switch contact only. Do not connect any

switches which provide a voltage to the control board as this will damage the control board. If the desired inputs are

12/24v or has long wiring associated with it use an IM-1 module to isolate it from the control board’s input. The IM-1

is available from the manufacturer.

Powering Accessories

Accessories which require a 24v AC supply can be powered from the transformer output used to power the control

board via the isolated 24v AC supply which is connected to the DIN rail terminals as labelled. However, the

transformer’s current capacity must be checked to allow for the extra power required by the accessories. Never use

the supply connected to the 24v AC supply control board terminals to power any accessory as this can interfere with

the control boards operation. (Blue Wires)

Locks & Lights

Use the lock output terminals on the din rail to switch the 12 volts to an electric lock (if fitted). The load switched by

the lock output terminals must not exceed 30V A.C / D.C @ 5Amps.  If an electromagnetic lock is used, change one

wire on the control board lock output to the normally closed output.  Use the light relay module (if fitted) to switch

the applied voltage to a light. The load switched by the light relay module must not exceed 240V A.C / 30V D.C @ 10

Amps.

Mode Selection

Using the mode selection dip-switches select the desired operating modes. Note the times associated with the

parameters marked with an * can be changed. The auto-close times can be changed using the procedure in the

following section. See the instruction manual for details on how to change the other parameters. See the detailed

CB-6 instruction manual for details on how to change the other parameters.

Position 1

SYNCHRONISING DELAY

OFF - No delay

ON -

Motor 1 starts to open 2 seconds* before Motor 2 and Motor 2 starts to close 2 seconds* before Motor 1.

Position 2

PULSE LOCK OUTPUT

OFF - Lock output is activated for the entire motor drive cycle.

ON -

Lock output pulses for 0.3 seconds* at the start of each drive cycle.

Position 3

LIGHT OUTPUTS WARNING

OFF - Optional light module controls a light with timer which turns light off after 60seconds*.

ON -

Optional light module controls a warning light which activates whenever motors are on.

Position 4

SWIPE MODE (OSC INPUT)

OFF - OSC input terminal has standard Open, Close, Stop action.

ON -

OSC input terminal will only open the door/gate. The input also resets the P.E triggered

auto-close mode so that the P.E input will need to be triggered again before a P.E auto- close cycle will be

initiated.

Position 5

M 2 OUTPUTS STATUS

OFF - The M2 output controls second motor

ON -

The M2 output controls status lights

Summary of Contents for GDS 450LI

Page 1: ...nd Maintenance Manual Sliding Gate Operators Inbuilt Models GDS 450LI 630LI Range Made in Australia from Australian quality imported components DELTA VSD 10 Bennet Ave Melrose Park SA 5039 8374 3466 J...

Page 2: ...is fixed move the gate and sight the rack moving over the pinion wheel check that most of the pinion wheel meshes with the rack Make sure rack runs freely over the pinion wheel any tights spots should...

Page 3: ...if not reverse two of the motor wires at the inverter terminals Inverter settings can be adjusted via the keypad i e Opening speed closing speed and ramp times Automation settings operating modes are...

Page 4: ...llation 6 10 Electrical Cabling Mechanical Installation Electrical Connections Plan view layout conduit positions CB6 Control Board layout CB 6 Control inputs mode settings 4 Delta Variable Speed Driv...

Page 5: ...necessary signs to indicate any danger areas and automatic operation of the gate or door The operators are not designed to be used in any hazardous areas or areas subject to flooding etc All electric...

Page 6: ...position once finished undo wing nut drop enclosure back down then re tighten wing nut Mechanical Installation Ensure gate rolls easily and has been installed in a manner where there is no excessive...

Page 7: ...7 PLAN VIEW LAYOUT CONDUIT POSITION...

Page 8: ...ceiver 7 Motor 2 Limit Switch Inputs 8 Terminals for Isolated 24vAC Supply 21 Firmware Version Label for Limit Switch and Control Inputs 22 Light Control Relay Interface Connector 9 Pedestrian Access...

Page 9: ...exceed 30V A C D C 5Amps If an electromagnetic lock is used change one wire on the control board lock output to the normally closed output Use the light relay module if fitted to switch the applied v...

Page 10: ...a pre set pedestrian access time of 5 seconds which is intended to open the motor connected to M1 output only part way If these default times do not suit your needs simply use the procedure below to a...

Page 11: ...close command input linked to MI3 for speed setting Terminal MI3 Closing Speed Multi Step speed command input Terminal DCM command output terminal used for common PARAMETER NUMBER PARAMETER DESCRIPTIO...

Page 12: ...se led should start to flash if they are the wrong way around turn power off to the operator wait until the inverter powers down then swap over any 2 of the motor phase wire at the inverter Turn power...

Page 13: ...Gate Drive Systems Australia Gate Drive Systems Australia DELTA VDF EL ATA CB 6 DELTA VDF EL DELTA VDF EL ATA CB 6...

Page 14: ...pened by hand To re engage the clutch move the gate by hand Into approx The half way position and turn the Knurled knob clockwise until it is very tight If when turning the knurled knob clockwise and...

Page 15: ...l not run inadvertently Gate rolls freely when in manual Gate wheels and guide rollers in good condition Gate stops are installed and in good condition not loose Gate rack is tight correct clearances...

Page 16: ...ty is negated and will not apply in the following circumstances i If no proof of date of purchase can be produced ii If the product has been used in a manner beyond its design parameters iii If the pr...

Reviews: