5°C, the circulator and, if necessary, the burner are activated at minimum output
levels to bring the water temperature back to the values for safety (35°C). During
the anti-frost cycle, the symbol
(fi g. 28) appears on the digital monitor.
Circulator anti-blocking function: an operation cycle is actvated every 24 hours.
Switching off for long periods
In case of absence for long periods of time, set the function selector (3 - fi g. 1) to
(OFF). Turn the main system switch OFF.
Close the fuel and water taps of the heating.
In this case, anti-frost device is deactivated: drain the systems, in case of risk of
frost.
4.3 Light signals and faults
The control panel has three LEDs that indicate the boiler operating status:
Green LED
Flashing
Flashing (0.5 seconds on, then 3.5 seconds off ) = boiler in standby, there is no
fl ame.
Flashing (0.5 seconds on, then 0.5 seconds off ) = temporary shutdown of the
appliance due to the following automatic-reset faults:
- water pressure switch (standby time 10 minutes approximately)
- transitory waiting for ignition.
In this phase, the boiler waits for restoration of working conditions. If after the
standby time, the boiler does not restore regular operation, the shutdown will
be permanent and the signal light will be red.
Fixed green
there is fl ame, the boiler works regularly.
Red LED
If the red LED lights up, this indicates the presence of a fault; the monitor shows
a code interpreted as follows:
To restore operation (deactivate alarms):
Faults A 01-02-03
Position the function selector (3 - fi g.1) to
(OFF), wait 5-6 seconds then set it
to ON position.
If the reset attempts do not reactivate the boiler, contact the Technical Assistan-
ce Centre.
Fault A 04
In addition to the fault code, the digital display shows the symbol
.
Check the pressure value indicated by the water gauge:
if it is less than 0.3 bar, position the function selector (3 - fi g.1) to
(OFF) and
adjust the fi lling tap of the system until the pressure reaches a value between 1
and 1.5 bar.
Then position the function selector (3 - fi g.1) to the ON position.
The boiler will perform one purge cycle lasting approximately 2 minutes.
If pressure drops are frequent, request the intervention of the Technical Assi-
stance Service.
Fault A 06
Contact the Technical Assistance Centre.
Fault A 07
Contact the Technical Assistance Centre.
Fault A 08
Contact the Technical Assistance Centre.
Fault A 09 with fi xed red LED lit
Position the function selector (3 - fi g.1) to
(OFF), wait 5-6 seconds then set it
to the ON position.
If the reset attempts do not reactivate the boiler, request the intervention of the
Technical Assistance Service.
Fault A 09 with fl ashing red and green LEDs
The boiler is equipped with an auto-diagnostic system which, based on the total
number of hours in certain operating conditions, can signal the need to clean
the primary exchanger (alarm code 09 with fl ashing red and green LEDs and fl ue
gas meter >2,500). Once the cleaning operation has been completed, using the
special kit supplied as an accessory, the total hour meter will need to be reset to
zero as follows:
- switch
off the power supply
- remove the housing
- loosen the fi xing screw then turn the instrument panel
- loosen the fi xing screws on the cover (F) to access the terminal board (fi g. 13)
- while the boiler is powered up, press and hold the CO button (fi g. 23) for at
least 4 seconds, to check the meter has been reset, power down then power
the boiler; the meter reading is shown on the monitor after the “-C-” sign.
Live electrical parts (230 V AC).
Note: the meter resetting procedure should be carried out after each in-depth
cleaning of the primary exchanger or if this latter is replaced. To check the status
of the total hour meter, multiply the reading by 100 (e.g. reading of 18 = 1800
total hours; reading of 1 = 100 total hours).
The boiler continues to operate normally even when the alarm is activated.
Fault A77
This is an automatic-reset fault, if the boiler does not restart, contact the Techni-
cal Assistance Centre.
Flashing yellow LED
Combustion analysis in progress.
DESCRIPTION
DISPLAY CODE
RED LED
YELLOW LED
GREEN LED
Flame lockout
A01
ON
OFF
OFF
Limit thermostat intervention
A02
fl ashes
OFF
OFF
Fan fault
A03
ON
OFF
OFF
Water pressure switch fault
A04
ON
OFF
ON
Domestic hot water NTC probe fault (not available)
A06
fl ashes
OFF
fl ashes
Fault on heating delivery NTC probe or delivery-return diff e-
rential circuit-breaker
A07
ON
OFF
OFF
Fault on heating return NTC probe or return-delivery diff e-
rential circuit-breaker
A08
ON
OFF
OFF
Intervention of thermal safety device on fl ue gas probe
A09
ON
OFF
OFF
Flue gas NTC probe or heat exchanger cleaning
A09
fl ashes
OFF
fl ashes
False fl ame
A11
fl ashes
OFF
OFF
Low temperature thermostat fault (not available)
A77
ON
OFF
OFF
Combustion analysis procedure in progress
ACO
OFF
fl ashes
OFF